Specifications
Model LS-10 / LH-10
Pt100 » only model LH-10
I max
mA
-
3
I meas
mA
-
1
Max. load R
A
R
A
in Ohm
Current signal output
U
B
in VDC
R
A
≤
(U
B
- 10 V) / 0.02 A - (0.14 Ohm x cable length in m)
Voltage signal output
-
R
A
> 100 kOhm
Insulation voltage
VDC
500
3)
500
3)
3)
Use NEC Class 02 power supply (low voltage and low current max. 100 VA even
under fault conditions)
Accuracy
% of span
≤
0.5
4)
≤
0.25
4)
(
≤
0.5 with pressure
ranges < 0,25 bar)
4)
Including non-linearity, hysteresis, zero point and full scale error (corresponds to
error of measurement per IEC 61298-2).
Adjusted in vertical mounting position with lower pressure connection.
Non-linearity
% of span
≤
0.2 (BFSL) according to IEC 61298-2
Non-repeatability
% of span
≤
0.1
1-year stability
% of span
≤
0.2 (at reference conditions)
Permissible temperature of
Medium
5)
-10 ... +50 °C
+14 ... +122 °F
-10 ... +50 °C
+14 ... +122 °F
{-10 ... +85 °C option FEP-cable}
{+14 ... +185 °F option FEP-cable}
Storage
5)
-30 ... +80 °C
-22 ... +176 °F
-30 ... +80 °C
-22 ... +176 °F
5)
Also complies with EN 50178, Tab. 7, Operation (C) 4K4H, Storage (D) 1K4,
Transport (E) 2K3
Compensated temp range
0 ... +50 °C
+32 ... +122 °F
0 ... +50 °C
+32 ... +122 °F
Temperature coefficients within
compensated temp range
Mean TC of zero
% of span
≤
0.2 / 10 K (< 0.4 for pressure range
≤
250 mbar)
Mean TC of range
% of span
≤
0.2 / 10 K
≤
0.2 / 10 K
Specifications
Model LS-10 / LH-10
CE- conformitiy
EMC directive
2004/108/EEC, EN 61 326 Emission (Group 1, Class B) and Immunity
(industrial locations)
Wiring protection
Short-circuit proofness
Sig+ towards UB-
Reverse polarity protection
UB+ towards UB-
{Lightning protection
EN 61000-4-5; 1,5J}
Weight
kg
Level probe
Approx. 0.18
Approx. 0.20
Cable
Approx. 0.08
Approx. 0.08
Additional weight
Approx. 0.50
Approx. 0.50
7. Starting, operation
GB
Functional test
Observe the ambient and working conditions outlined in section 7 „Technical
data".
Please make sure that the pressure transmitter is only used within the over-
load threshold limit at all times!
The output signal must be proportional to the pressure. If not, this might point to a
damage of the diaphragm. In that case refer to chapter 10 „Troubleshooting“.
7. Starting, operation / 8. Maintenance, accessories
GB
{ } Items in curved brackets are optional extras for additional price.
8. Maintenance, accessories
WIKA pressure transmitters require no maintenance.
Have repairs performed by the manufacturer only.
!
Warning