WIKA operating instructions flow switch, model FSD-3
EN
14153887.01 09/2016 EN/DE/FR
Window function
The window function allows for the control of a defined range.
When the flow rate is between window high (FH) and window low (FL), the output
switches on.
■
Contact normally open (FNO): Active
■
Contact normally closed (FNC): Inactive
When the flow rate is outside window high (FH) and window low (FL), the output
does not switch on.
■
Contact normally open (FNO): Inactive
■
Contact normally closed (FNC): Active
Delay times (0 ... 50 s)
This makes it possible to filter out unwanted flow peaks of a short duration or
high frequency (damping).
The flow rate must be present for at least a certain pre-set time for the output to
switch on. The output does not immediately change its status when it reaches the
switching event (SP), but rather only after the pre-set delay time (DS).
If the switching event is no longer present after the delay time, the switching
output does not change.
The output only switches back when the flow rate has fallen down to the reset
point (RP) and stays at or below the reset point (RP) for at least the pre-set delay
time (DR).
If the switching event is no longer present after the delay time, the switching
output does not change.
Fig.: Window function
5. Commissioning, operation
Fig.: Delay times
Содержание FSD-3
Страница 38: ...38 WIKA operating instructions flow switch model FSD 3 EN 14153887 01 09 2016 EN DE FR...
Страница 74: ...74 WIKA Betriebsanleitung Str mungsschalter Typ FSD 3 DE 14153887 01 09 2016 EN DE FR...
Страница 110: ...110 WIKA mode d emploi pour le capteur de d bit type FSD 3 FR 14153887 01 09 2016 EN DE FR...
Страница 111: ...111 WIKA mode d emploi pour le capteur de d bit type FSD 3 FR 14153887 01 09 2016 EN DE FR...