EN
WIKA operating instructions model A2G-50
40202780.03 07/2017 EN/DE
19
5. Commissioning, operation
5.5 Selecting the measuring range
1. Determine the correct pressure range.
2. Determine the version of the measuring instrument (see table 1).
3. Determine the desired pressure unit (see chapter 5.4).
4. Find the desired measuring range number (see “Range” in illustration).
5. Place jumpers J1, J2 and J3 to set the desired pressure range in
accordance with the illustration.
A2G-50 versions and settable pressure ranges
Version 1
MB Pressure unit
Pa
kPa
mbar
inchWC
mmWC
psi
1
-100 ... +100 -0.10 ... +0.10 -1.00 ...
+1.00
-0.40 ...
+0.40
-10.2 ...
+10.2
-0.0145 ...
+0.0145
2
0 ... 100
0 ... 0.10
0 ... 1.0
0 ... 0.40
0 ... 10.2
0 ... 0.0145
3
0 ... 250
0 ... 0.25
0 ... 2.50
0 ... 1.00
0 ... 25.5
0 ... 0.0363
4
0 ... 500
0 ... 0.50
0 ... 5.00
0 ... 2.00
0 ... 51.0
0 ... 0.0725
5
0 ... 1,000
0 ... 1.00
0 ... 10.0
0 ... 4.00
0 ... 102.0
0 ... 0.1450
6
0 ... 1,500
0 ... 1.50
0 ... 15.0
0 ... 6.00
0 ... 153.0
0 ... 0.21725
7
0 ... 2,000
0 ... 0.20
0 ... 20.0
0 ... 8.00
0 ... 204.0
0 ... 0.2900
8
0 ... 2,500
0 ... 2.50
0 ... 25.0
0 ... 10.00
0 ... 255.0
0 ... 0.3625
Version 2
MB Pressure unit
Pa
kPa
mbar
inchWC
mmWC
psi
1
0 ... 1,000
0 ... 1.0
0 ... 10.0
0 ... 4.00
0 ... 102.0
0 ... 0.1450
2
0 ... 1,500
0 ... 1.5
0 ... 15.0
0 ... 6.00
0 ... 153.0
0 ... 0.21725
3
0 ... 2,000
0 ... 2.0
0 ... 20.0
0 ... 8.00
0 ... 204.0
0 ... 0.2900
4
0 ... 2,500
0 ... 2.5
0 ... 25.0
0 ... 10.00
0 ... 255.0
0 ... 0.3625
5
0 ... 3,000
0 ... 3.0
0 ... 30.0
0 ... 12.00
0 ... 306.0
0 ... 0.4350
6
0 ... 4,000
0 ... 4.0
0 ... 40.0
0 ... 16.00
0 ... 408.0
0 ... 0.5800
7
0 ... 5,000
0 ... 5.0
0 ... 50.0
0 ... 20.00
0 ... 510.0
0 ... 0.7250
8
0 ... 7,000
0 ... 7.0
0 ... 70.0
0 ... 28.00
0 ... 714.0
0 ... 1.0150
MB = measuring range