2.22.6 Process data from module to PLC (inputs)
5 words are transferred to the PLC.
Word 1
Word 2
Word 3*
Word 4*
Word 5
Count value of
counter 1 (MSB)
Count value of
counter 1 (LSB)
Count value of
counter 2 (MSB)
Count value of
counter 2 (LSB)
Status of
inputs/outputs*
*Word 3 and word 4 are not transferred with the data width is set to 3. Word 5 is
then transferred as word 3. Individual bits are used differently, see below.
Status of inputs/outputs
Bit values of word 5
Description
xxxx xxxx xxxx xxx0 b
Reference movement signal for counter 1 is deleted
xxxx xxxx xxxx xxx1 b
Conclusion of a successful reference movement for counter 1
xxxx xxxx xxxx xx0x b
Positioning movement signal for counter 1 is deleted
xxxx xxxx xxxx xx1x b
Conclusion of a successful positioning movement for counter
1
xxxx xxxx xxxx x0xx b
Status of TRACK N for counter 1 is 0 (0 V)
xxxx xxxx xxxx x1xx b
Status of TRACK N for counter 1 is 1 (24 V)
xxxx xxxx xxxx 0xxx b
Status of END+ for counter 1 is 0 (0 V)
xxxx xxxx xxxx 1xxx b
Status of END+ for counter 1 is 1 (24 V)
xxxx xxxx xxx0 xxxx b
Status of END- for counter 1 is 0 (0 V)
xxxx xxxx xxx1 xxxx b
Status of END- for counter 1 is 1 (24 V)
xxxx xxxx xx0x xxxx b
Status of DIR+/DIRECTION for counter 1 is 0 (0 V)
xxxx xxxx xx1x xxxx b
Status of DIR+/DIRECTION for counter 1 is 1 (24 V)
xxxx xxxx x0xx xxxx b
Status of DIR-/TRAVERSE for counter 1 is 0
(0 V)
xxxx xxxx x1xx xxxx b
Status of DIR-/TRAVERSE for counter 1 is 1 (24 V)
xxxx xxxx 0xxx xxxx b
Status of SPEED for counter 1 is 0 (0 V)
xxxx xxxx 1xxx xxxx b
Status of SPEED for counter 1 is 1 (24 V)
xxxx xxx0 xxxx xxxx b
Reference movement signal for counter 2 is deleted
xxxx xxx1 xxxx xxxx b
Conclusion of a successful reference movement for counter 2
xxxx xx0x xxxx xxxx b
Positioning movement signal for counter 2 is deleted
xxxx xx1x xxxx xxxx b
Conclusion of a successful positioning movement for counter
2
xxxx x0xx xxxx xxxx b
Status of TRACK N for counter 2 is 0 (0 V)
xxxx x1xx xxxx xxxx b
Status of TRACK N for counter 2 is 1 (24 V)
xxxx 0xxx xxxx xxxx b
Status of END+ for counter 2 is 0 (0 V)
xxxx 1xxx xxxx xxxx b
Status of END+ for counter 2 is 1 (24 V)
xxx0 xxxx xxxx xxxx b
Status of END- for counter 2 is 0 (0 V)
xxx1 xxxx xxxx xxxx b
Status of END- for counter 2 is 1 (24 V)
xx0x xxxx xxxx xxxx b
Status of DIR+/DIRECTION for counter 2 is 0 (0 V)
xx1x xxxx xxxx xxxx b
Status of DIR+/DIRECTION for counter 2 is 1 (24 V)
x0xx xxxx xxxx xxxx b
Status of DIR-/TRAVERSE for counter 2 is 0
(0 V)
x1xx xxxx xxxx xxxx b
Status of DIR-/TRAVERSE for counter 2 is 1 (24 V)
0xxx xxxx xxxx xxxx b
Status of SPEED for counter 2 is 0 (0 V)
1xxx xxxx xxxx xxxx b
Status of SPEED for counter 2 is 1 (24 V)
x: Any bit value
b: Binary display
An alternative bit can also be assigned as a feedback bit, depending on word 5 of the
control data.