background image

GST18i3

GST18i3

L PE N

L` PE N

MAa

H

GST18i3

L` PE N

L PE N

L N L`

MAb

SV

H

GST18i3

GST18i3

GST18i5

L` PE N

L PE N

L L` PE N Info

MASL

H

SLa

GST18i3

GST18i3

GST18i5

GST18i5

L` PE N

L PE N

L L` PE N Info

L L` PE N Info

MASL

H

SLSL

SLa

Operating Mode

The 

gesis

®

 P MS8-360-1L…

 can control the lighting in two ways:  

In the first mode, the lighting is switched on with the remote control 

gesis

®

 PIR IR B-04 IPD 

and switches off automatically when leaving the room after 

a specified delay time. 
In the second mode the lighting is switched on and off automatically. If there is 
sufficient daylight (above set value), the lighting is not switched on.

Default settings

Various functions of the presence detectors can be changed.

Master

 gesis

®

 P MS8-360-1L:

Slave

 gesis

®

 P MS8-SL:

 

automatic ON/OFF

 

sensitivity on second-highest level

 

delay time 15 minutes

 

brightness threshold 200 Lux

 

sensitivity on second-highest level

Installation

Both presence detectors are pre-assembled with plug connectors. The electrical 
connections are only plugable. For the necessary plug-family please refer to the 
table above.  
All presence detectors are for ceiling installation and are fixed through a hole with a 
diameter of 86 mm. The maximum thickness of the material is 30 mm. 

General Description

The 

gesis

®

 P MS8-360-1L 

(1Lb, 1LSL, SLb, SLSL) are for light control.They switch 

the lighting dependant on movement or brightness, fully automatically or after 
activating the control via remote. Brightness threshold and sensitivity of the sensor 
can be adjusted individually. The lighting is switched off automatically or after the 
last movement and end of the delay time, or is switched off directly via remote.

For covering areas that go beyond the detection range of one detector, slaves  
(

gesis

®

 MS8-260 SL ...

) are used. The slaves report detection of movement 

to the master. The Master controls all further functions. For this reason only the 
sensitivity can be set in the slaves.

Please note that all parameters are set with remote 

gesis

®

 

PIR IPD-16A.

The following versions are available:

Master

Type

Part No. 

Master with direct light connection (MAa) 

gesis

®

 P MS8-360-1L

83.020.0110.1

Master for connection of a cross connector 

(MAb)

gesis

®

 P MS8-360-1Lb 83.020.0110.2

Accessories for cross connector

92.030.0153.1

Master for connecting a slave (MASL)

gesis

®

 P MS8-360-

1LSL

83.020.0110.3

Slave

Type

Part No. 

Slave with direct light connection (SLa)

gesis

®

 P MS8-360-SLb 83.020.0111.1

Slave with connection for another slave (SLSL)

gesis

®

 P MS8-30-SLSL 83.020.0111.2

Application

The sensors are for use in offices, schools, meeting rooms and similar locations. 
The 

gesis

®

 P MS8-360-1L...

 are suitable for small and large rooms, because they 

can be combined with several slaves

 

gesis

®

 

P MS-360-SL.

CAUTION

Since  the  presence  detectors  are  integrated  directly  into  the  plug-
in  installation,  the  appropriate  provisions  for  cable  tension  relief  apply. 
If the presence detector is opened, this can‘t be guaranteed and Wieland makes 
no guarantees. 

Function

Input

*

Output

*

Type

male Plug 
GST18

Type

female Plug 
GST18

MAa

Master

230 V AC

3-pole, bw.

230 V AC

3-pole, white

MAb

Master

3-pole, brown

MASL

Master

3-pole, bw. 

to slave

5-pole, white

SLa

Slave

from master 
or slave

5-pole black

230 V AC

3-pole, white

SLSL

Slave

to slave

5-pole, white

SV

Cross connector

H

Lighting

*cable length 0.5 m

Technical specifications

Type

gesis

®

 P MS8-360-1L...

gesis

®

 P MS8-360-SL...

Network voltage / Fre-

quency

230 V / 50 Hz

230 V / 50 Hz

Standby Consumption

<1 W

<1 W

Relay

NO 230 V, 10 A, 

µ-contact

Load

Ohmic load

2300 W

Fluorescent tubes  
(not compensated)

1200 VA

Halogen incandescent 
bulbs

2300W

Max. capacity

140 µF

Max. starting current

165 A / 20 ms

Operating range

Ø 8 – 12 m, 360°

Ø 8 − 12 m, 360°

LUX range

50 – 1000 Lux

Delay time

15 – 180 min

Sensitivity

four level

four level

Ambient temperature

0 to +50°C

0 to +50°C 

Protection class

IP20

IP20

Humidity

20 – 95% without  

condensation

20 – 95% without 

condensation

Color (housing)

white

white

Mounting hole diameter 

Ø 86 mm

Ø 86 mm

Montage max.  

Materialdicke

30 mm

30 mm

Accessories remote control

... for programming

gesis

®

 PIR IR B-21 IPD 

(83.020.0122.0)

gesis

®

 PIR IR B-21 IPD 

(83.020.0122.0)

... for users

gesis

®

 PIR IR B-04 URM 

(83.020.0122.1)

DANGER

 

Only trained electricians may install and commission this device. They 
must have read and understood this instruction manual before the 
installation.

 

Do not open the device. Do not insert any foreign objects. Keep the device 
away from water and fire. 

 

Only connect or disconnect the device if it hast been de-energised.

 

The relevant standards, directives, regulations and provisions of the parti-
cular country are to be observed.

Doc. # 

BA000957 

– 06/2015 (Rev. A)   

gesis

®

 P MS8-360-1L | MS8-360-1Lb | MS8-360-1LSL | MS8-360-SLb | MS8-360-SLSL

 

EN 

page 

Wieland Electric GmbH
Brennerstraße 10-14
96052 Bamberg
Tel. +49 (951) 9324-0
Fax +49 (951) 9324-198
Internet: www.wieland-electric.com
Email: [email protected]

gesis

Hotline:

Tel.: +49 (951) 9324-996
Fax: +49 (951) 9326-996
Email: [email protected]
Internet: www.gesis.com

Installation Instructions (translation)

gesis

®

 P   MS8-360-1L   

83.020.0110.1 

gesis

®

 P   MS8-360-1Lb   

83.020.0110.2 

gesis

®

 P  MS8-360-1LSL  

83.020.0110.3 

gesis

®

 P  MS8-360-SLb   

83.020.0111.1 

gesis

®

 P  MS8-360-SLSL 

83.020.0111.2

gesis

®

 

presence detector switching

Updated

:

 06/2015  

© 2015 Wieland Electric GmbH

Содержание gesis P MS8-360-1L

Страница 1: ...360 SLb 83 020 0111 1 Slave mit Slaveanschluss SLSL gesis P MS8 30 SLSL 83 020 0111 2 Anwendung Die Melder sind für den Einsatz in Büros Schulen Besprechungsräumen und ähnlichen Räumlichkeiten bestimmt Die Melder gesis P MS8 360 1L eignen sich für kleine und für große Räume da sie mit mehreren Slaves gesis P MS 360 SL ergänzt werden können WARNUNG Nur Elektrofachkräfte dürfen dieses Gerät installi...

Страница 2: ...ünschte Wert dann die Einstellung mit Punkt 4 beenden 3 zum Erhöhen oder zum Verringern um 50 Lux kurz drücken Die grüne LED am Sensor erlischt kurz zum Bestätigen der Aktion Blinkt die rote LED kurz auf ist das Minimum von 50 Lux oder das Maximum von 1000 Lux erreicht 4 kurz drücken um die Einstellung zu speichern Alle LEDs am Sensor erlöschen Nachlaufzeit alle Master gesis P MS8 360 1L Der Zeitr...

Страница 3: ...are for use in offices schools meeting rooms and similar locations The gesis P MS8 360 1L are suitable for small and large rooms because they can be combined with several slaves gesis P MS 360 SL CAUTION Since the presence detectors are integrated directly into the plug in installation the appropriate provisions for cable tension relief apply If the presence detector is opened this can t be guaran...

Страница 4: ... LED on the sensor switches off briefly to confirm action If red LED flashes briefly the minimum of 50 lux or the maximum of 1000 lux is reached 4 Press briefly to save the settings All LEDs on the sensor turn off Switch ON OFF delay time all Master gesis P MS8 360 1L How long the light stays switched on after detection of the last movement can be adjusted between 15 and 180 minutes To set the swi...

Отзывы: