background image

ø12 m

ø6 m

77mm

90mm

95mm

5mm

ø8 m

50 m

2

ø2,7 m

5,5 m

2

ø5,4 m

23 m

2

2,5 

m

0,8 

m

m

ø6 m

28 m

2

ø12 m

113 m

2

Test-mode (

gesis

®

 P MS8-360-1L...)

After the installation of the sensor it can be checked if the chosen position is optimal 
for  the  sensor.  Therefore  the  sensor  is  set  to  test-mode.  The  time  delay  is  shor-
tened to 2 seconds and the switched-off brightness threshold allows a simple test.

For activating the test-mode the remote control 

gesis

®

 

PIR IR B-21 IPD

 is used.

Proceed as following: 

 

press 

[

]

 key on the remote for 4 seconds. If the LED on the sensor is 

flashing red/green, the sensor is in test-mode.

 

press 

[

]

 shortly to quit test-mode. The LED switches off.

Semi- or automatic-mode  

(all master 

gesis

®

 P MS8-360-1L...)

Semi-automatic:

Manually turn on and automatically turn off. For switch-on the remote control  

gesis

®

 PIR IR B-04 IPD 

is necessary. 

Fully automatic (default setting):

Automatic switch-on and -off. The brightness threshold is considered on automatic 
switch-on. Regardless of the brightness value the following settings can be set via 
remote 

gesis

®

 PIR IR B04 IPD:

 

Switch-off delay is considered

 

Sensitivity of each sensor is considered

 

Remote control can be used in both modes

For setting semi- or automatic-mode use remote 

gesis

®

 PIR IR B21 IPD. 

For 

setting the mode with the remote control proceed as following:

1.  Press 

[

]

 briefly. The green LED on the sensor flashes for confirmation. 

2.  Press 

[ZONE 1] 

briefly. The green LED on the sensor switches off briefly. The 

presence detector is now set in programming function for the operating mode.

3.  Press 

[ON / OFF]

 briefly to switch between semi- or automatic mode

3.1  green LED switches off briefly = semi automatic mode
3.2  red LED flashes briefly = full automatic mode

4.  Press 

[

]

 shortly to save the setting. All LEDs on the sensor switch off.

Setting brightness threshold 

(all Master 

gesis

®

 P MS8-360-1L)

If the light intensity is below the parameterized threshold in automatic mode the 
lighting is switched-on, when a movement is detected. If the measured light inten-
sity is above the threshold, the lighting won‘t be switched on in automatic mode. 
The lighting can always be switched on via remote control 

gesis

®

 PIR IR B-04 IPD

regardless of the operating mode.

The threshold can be adjusted to the preset values 100, 250, 400, 600, 800 and 
1000 Lux (default setting 200 Lux). These values can be increased or decreased in 
steps of 50 lux in a range between 50 or 500 lux. For values above 500 lux the fix 
values are available.
For setting the threshold the remote control 

gesis

®

 PIR IR B-21 IPD

 is used.

Proceed as following:
1.  Press 

[

]

 shortly. The green LED flashes on the sensor.

2.  Press 

[xxx LUX] 

briefly. Green LED on the sensor switches off briefly and the 

corresponding value is set. If this value is correct already complete with 4.

3.  Press 

[

]

 to increase or 

[

]

 to decrease value in steps of 50 lux. Green LED on 

the sensor switches off briefly to confirm action. If red LED flashes briefly, the 
minimum of 50 lux or the maximum of 1000 lux is reached.

4.  Press 

[

]

 briefly to save the settings. All LEDs on the sensor turn off. 

Switch-ON/-OFF delay time  

(all Master 

gesis

®

 P MS8-360-1L...)

How long the light stays switched-on after detection of the last movement can be 
adjusted between 15 and 180 minutes. To set the switch-ON/-OFF time the remote 
control 

gesis

®

 PIR IR B-21 IPD

 is used. 

Continue as following:

 

Press 

[

]

 shortly. Green LED on the sensor flashes. 

In the following steps the green LED switches off briefly for confirmation of the 
settings.

 

Press 

[+15 TIME]

 more than 4 seconds to reset the switch-ON/-OFF time to  

15 Minutes.

 

Press 

[30 MIN]

 or 

[60 MIN]

 briefly to parameterize the switch-ON/-OFF time 

to 30 or 60 Minutes.

 

Press 

[+15 TIME]

 briefly to increase or 

[

15 TIME]

 to decrease the switch-

ON/-OFF time. If red LED flashes briefly, the minimum of 15 or the maximum 
of 180 minutes is reached.

 

Press 

[

]

 briefly to save the settings. All LEDs on the sensor switch off for 

confirmation.

Response value sensitivity

The response value sensitivity can be adjusted in four levels. If there are many 
faulty circuits they can possibly be avoided by choosing a lower sensitivity level. 
To change the sensitivity level the remote control 

gesis

 PIR IR B-04 IPD 

is  

necessary:

1.  Press 

[

]

 briefly. Green LED on the sensor flashes for confirmation.

2.  Press 

[ZONE1]

 long to choose the highest sensitivity. Red LED flashes for 

confirmation. 

3.  Press 

[ZONE2] 

long to choose the second highest sensitivity. It is programmed 

as described above.

4.  Press 

[ZONE3] 

long to choose the second lowest sensitivity. It is programmed 

as described above.

5.  Press 

[ZONE4] 

long to choose the lowest sensitivity. It is programmed as 

described above.

6.  Press 

[

briefly to end programming. All LEDs on the sensor switch off.

Dimensions

Detection range (MS8-360-SL)

The detection range can be extended by connecting a  
slave

 

gesis

®

 PIR MS8-360-SL

 unit. Details see image below.

Doc. # 

BA000957 

– 06/2015 (Rev. A)   

gesis

®

 P MS8-360-1L | MS8-360-1Lb | MS8-360-1LSL | MS8-360-SLb | MS8-360-SLSL

 

EN 

page 

© 2015 All rights reserved. This description, including all the diagrams, is protected by 
copyright. Third-party products are named without noting patent rights. The existence of 
these rights must therefore not be ruled out. Changes of any type that are made in the 
hardware or software of the products described result in an exclusion of liability on the part 
of the manufacturer.

Wieland Electric GmbH
Brennerstraße 10-14
96052 Bamberg
Tel. +49 (951) 9324-0
Fax +49 (951) 9324-198
Internet: www.wieland-electric.com
Email: [email protected]

gesis

Hotline:

Tel.: +49 (951) 9324-996
Fax: +49 (951) 9326-996
Email: [email protected]
Internet: www.gesis.com

Installation Instructions (translation)

gesis

®

 P   MS8-360-1L   

83.020.0110.1 

gesis

®

 P   MS8-360-1Lb   

83.020.0110.2 

gesis

®

 P  MS8-360-1LSL  

83.020.0110.3 

gesis

®

 P  MS8-360-SLb   

83.020.0111.1 

gesis

®

 P  MS8-360-SLSL 

83.020.0111.2

gesis

®

 

presence detector switching

Updated

:

 06/2015  

© 2015 Wieland Electric GmbH

Содержание gesis P MS8-360-1L

Страница 1: ...360 SLb 83 020 0111 1 Slave mit Slaveanschluss SLSL gesis P MS8 30 SLSL 83 020 0111 2 Anwendung Die Melder sind für den Einsatz in Büros Schulen Besprechungsräumen und ähnlichen Räumlichkeiten bestimmt Die Melder gesis P MS8 360 1L eignen sich für kleine und für große Räume da sie mit mehreren Slaves gesis P MS 360 SL ergänzt werden können WARNUNG Nur Elektrofachkräfte dürfen dieses Gerät installi...

Страница 2: ...ünschte Wert dann die Einstellung mit Punkt 4 beenden 3 zum Erhöhen oder zum Verringern um 50 Lux kurz drücken Die grüne LED am Sensor erlischt kurz zum Bestätigen der Aktion Blinkt die rote LED kurz auf ist das Minimum von 50 Lux oder das Maximum von 1000 Lux erreicht 4 kurz drücken um die Einstellung zu speichern Alle LEDs am Sensor erlöschen Nachlaufzeit alle Master gesis P MS8 360 1L Der Zeitr...

Страница 3: ...are for use in offices schools meeting rooms and similar locations The gesis P MS8 360 1L are suitable for small and large rooms because they can be combined with several slaves gesis P MS 360 SL CAUTION Since the presence detectors are integrated directly into the plug in installation the appropriate provisions for cable tension relief apply If the presence detector is opened this can t be guaran...

Страница 4: ... LED on the sensor switches off briefly to confirm action If red LED flashes briefly the minimum of 50 lux or the maximum of 1000 lux is reached 4 Press briefly to save the settings All LEDs on the sensor turn off Switch ON OFF delay time all Master gesis P MS8 360 1L How long the light stays switched on after detection of the last movement can be adjusted between 15 and 180 minutes To set the swi...

Отзывы: