23
2.1 Switching Mode
The lighting switches on in case of presence
and
insufficient brightness, and
off in case of absence
or
sufficient brightness
2.2 Constant Light Control Mode
In
Constant Light Control
mode, the brightness is constantly maintained
at th pre-set value. It can be started fully automatically or manually using the
push button or remote control. Manually switching off, dimming or changing
the settings stops control mode for the duration of the presence.
3. Fitting and connection
3.1 Presence detection
The ideal mounting height is 2.0 - 3.0m.
The detector sensitivity decreases as the mounting height increases. The
presence detector requires a clear line of sight for reliable detection of per-
sons. Office furniture, mobile partitions, plants, suspended lamps, etc. may
have a detrimental effect on presence detection (shading).
GB
M’height
Seated persons
Walking persons
2,0m
3,0m x 3,0m
4,5m x 4,5m ± 0,5m
2,5m
4,0m x 4,0m
6,0m x 6,0m ± 0,5m
3,0m
4,5m x 4,5m
7,0m x 7,0m ± 1,0m
3,5m
---
8,0m x 8,0m ± 1,0m