6
|
User interface
Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018
29
26
Relay 1 configuration
Default Value
Flags (bit)
Normally open, Bat. life time,
Bat. Ri too high, Bat. Charge fail-
ure
Normally open (0), Backup (1), Soc <25% (2), Bat. life time (3), Bat.
Ri too high (4), Bat. Low (5), Bat. Disconnected (6), Bat. charge fail-
ure (7), Backup left <25% (8)
Unit
LCD name
Modbus address
N/A
Relay 1
0x1027
This field defines the behavior of relay 1 as follows:
Normally open 1 or more enabled state active? Relay contact status
True
No
Open
True
Yes
Closed
False
No
Closed
False
Yes
Open
27
Relay 2 configuration
This field defines the behavior of relay 2 (see "Relay 1 configuration", no. 26 in section 6.2).
Default Value
Flags (bit)
Normally open, Backup
Normally open (0), Backup (1), Soc < 25% (2), Bat. life time (3), Bat.
Ri too high (4), Bat. Low (5), Bat. Disconnected (6), Bat. charge fail-
ure (7), Backup left < 25% (8)
Unit
LCD name
Modbus address
N/A
Relay 2
0x1028
28
Inhibit polarity
Selects the active polarity of the inhibit input. See section 5.4 for more information about the inhibit
function.
Default Value
Values (Modbus value)
High
Low (1), High (2)
Unit
LCD name
Modbus address
N/A
Inhibit polarity
0x1029
29
DC-DC output mode
Select parallel mode in case the UPS module is configure as DC-DC with output connected in parallel
with another unit.
Default Value
Values (Modbus value)
Single
Single (1), Parallel (2)
Unit
LCD name
Modbus address
N/A
DC/DC out mode
0x102A
30
Output enable
Enable/Disable output.
Default Value
Values (Modbus value)
Enabled
Disabled (0), Enabled (1)
Unit
LCD name
Modbus address
N/A
Output enable
0x102B