Inducer Draft Motor

and

Pressure Switch

Check

Is induced

draft motor

energized?

YES

YES

NO

Is diagnostic

LED flashing 3

times?

Call for heat.

Thermostat

contacts

R & W close.

Jumper

pressure

switch.

Disconnect

electric power

at fuse or

circuit breaker.

Is pressure

switch welded

closed?

Correct blocked

or incorrectly

installed vent.

Check operation.

Repair leaks in

inducer assembly or

replace induced

draft motor. Check

operation.

Check inducer

wiring. If OK,

repair or replace

inducer motor.

Check operation.

Replace pressure

switch. Energize

system. Check

operation.

NO

YES

NO

NO

3A

3F

Is diagnostic

LED flashing 2

times?

3B

3C

3D

3G

3H

3E

3I

3J

3L

YES

NO

Is

pressure

greater than

pressure switch

specs?

YES

Replace pressure

switch. Check

operation.

NO

Is

pressure

greater than

pressure switch

specs?

YES

YES

NO

Does ignitor

glow?

Test for

continuity across

pressure switch.

Place incline

manometer in

series with

pressure switch

tubing.

Remove vent

connector

from furnace

flue collar.

3K

CHART 3

WARNING

!

If diagnostic indicator (LED) 

shows continuous flashing, turn 

off gas supply at source before 

disconnecting electrical power!

INTEGRATED FURNACE

CONTROL MODULE

TROUBLESHOOTING

GUIDE

www.white-rodgers.com

192

TECHNICAL

 HELP