background image

INSTALLER CONFIGURATION

BEFORE TURNING POWER ON, please
read the following instructions. Before
operating the system, you must configure
the thermostat to operate properly with
your equipment.

The thermostat, as it comes from the factory,
is configured to operate a standard multi-
stage electric forced hot air system with a
single stage air conditioning compressor
and fan. In this configuration, the thermostat
will turn on the fan immediately on a call for
heat. If you are unsure whether your system
requires the thermostat to control the fan,
contact your furnace/air conditioning system
manufacturer or a qualified heating/air
conditioning service person.

Your new thermostat has an Installer table,
which allows you to customize the thermostat
to meet your requirements.

(The thermostat also has a User menu,
Keypad Lockout menu and a Service
menu
; these menus are explained further
in the Operating Instructions.)

The menu settings can be changed at any time
to meet system or personal requirements.

ENTERING THE  CONFIGURATION
MENUS

After properly wiring the thermostat, turn on
power to the system. Momentarily press

PROGRAM 

RUN

 to make certain the

thermostat is in the run program mode, then
press TIME 

FWD

 and TIME 

BACK

  at the

same time to enter the User Configuration
menu. When the display changes to the first
item in the configuration menu, release the
buttons. Then press and hold SET 

TIME

 and

SET 

DAY

 for approximately 3 seconds to

enter the Installer table. The display will
change to show the first item on the Installer
table (multi-stage/heat pump selection).  Use
the following text, along with the Installer
table
, to guide you through the selections.

Once in the table, you set each item to the
proper selection using 

 or 

, then

press TIME 

FWD

 to change the display to

the next item or TIME 

BACK

 to return to the

previous item.

To exit the table at any time, press PRO-

GRAM 

RUN

.

MULTI-STAGE/HEAT PUMP MODE.

(Installer table step 1.) Use this item to select
the system type (multi-stage or heat pump).
IF YOU HAVE A HEAT PUMP SYSTEM,
you must select HEAT PUMP here. This
sets up proper default values for most heat
pump systems. This selection also makes
available some additional menu items that
apply only to heat pump systems.

HEAT PUMP COMPRESSOR
CONFIGURATION.

(Installer table step 2; this item is displayed
only when heat pump was selected in step 1.)
Use this item to select the number of heat
pump compressors.

ELECTRIC HEAT FAN
CONFIGURATION.

(Installer table step 3.) This item determines
whether fan control will be through the
thermostat or through the heating system. If
you have an electric heat or other system that
REQUIRES the thermostat to control the fan,
set this item ON. This allows the thermostat
to energize the fan immediately on a call for
heat. If you are unsure if the system requires
the thermostat to control the fan, contact the
equipment manufacturer or a qualified
heating and air conditioning service person.
If your system controls fan operation (as
with most fossil fuel systems), set this item
to OFF. Note that with heat pump systems,
the fan always cycles with the compressor.

SET CYCLE HEAT, COOL, AUX
(ANTICIPATION).

(Installer table steps 4 through 6; step 6 is for
heat pump only). These items allow the cycle
times in heating, cooling and auxiliary (heat
pump systems only) to be increased or
decreased. The factory set values can be
adjusted higher for longer cycles or lower for
shorter cycles.

NOTE: Some manufacturers still instruct you
to set the anticipator to the current draw of
the equipment. That instruction applies only
to mercury bulb or mechanical thermostats; it
does not apply to this digital thermostat. As
configured at the factory, this thermostat will
maintain an accurate temperature. No further
adjustment is necessary, although you can
use these items to customize the performance
of the thermostat to your requirements.

The adjustment range for HEATING is from
1 to 40 (9 to 40 for heat pump). The factory
preset is 5 (13 for heat pump). The adjust-
ment range for COOLING is from 9 to 40.
The factory preset is 12 (13 for heat pump).
The cooling will not go below 9 because
compressors require a longer cycle. The
adjustment range for AUXILIARY (heat
pump only) is from 1 to 40. The factory
preset is 6.

The chart on page 7 shows how this
adjustment range affects thermostat perfor-
mance.

PROGRAMMABLE COOL FAN-
OFF AND FAN-ON DELAY.

(Installer table steps 7 and 8.) These items
allow a selection of 0 to 127 seconds of fan-
off delay after the thermostat has satisfied the
call for cool, or a fan-on delay of 1 to 30
seconds on a call for cool (or heat pump
compressor activation).

The fan-off delay allows the fan to continue
running after the compressor has shut off.
This distributes the cool air that would
otherwise stay trapped in the air conditioning
coils through the ducts. Ideally the timing
would be set so the fan shuts off just as the
cool air is exhausted. If this timing is set too
long the fan may begin blowing warm air
before it shuts off. Shortening the fan-off
delay will prevent this.

A short delay to allow the A-coil to cool
off (or warm up in heat pump) before the
fan turns on may be preferred. This also
allows the compressor and the fan to come
on at slightly different times, which allows
full power to the compressor on start up.
Recommended setting for fan-on delay is
10 seconds or less.

PROGRAMMABLE HEAT FAN-
OFF DELAY.

(Installer table step 9.) This item allows a
selection of 0 to 127 seconds of fan-off delay
after the thermostat has satisfied the call for
heat if ELECT HEAT FAN (Step 3) is
selected ON.

The fan-off delay allows the fan to continue
running after the burner, heating element,
etc. has shut off. This distributes the heat that
would otherwise stay trapped in the ducts.
Ideally the timing would be set so the fan
shuts off just as the warm air is exhausted. If
this timing is set too long the fan may begin
blowing cool air before it shuts off. Shorten-
ing the fan-off delay will prevent this.

PUMP (FOSSIL FUEL KIT ALTER-
NATIVE STEPS 10 - 13).

(Installer table step 10; heat pump only) This
item controls heat pump compressor
operation with a fossil fuel auxiliary. This
item may eliminate the need for a separate
fossil fuel kit, although we recommend that
you consult the heat pump system manufac-
turer before using this feature instead of a
kit. This item will allow the thermostat to
turn the heat pump compressor off if the
auxiliary is on for more than one minute,
to prevent compressor head pressure from
getting too high. To use this feature instead
of a kit, select PUMP OFF.

5

Содержание 1F95CA-391

Страница 1: ...t or incorrect wiring will damage thermostat and could cause personal injury and or property damage Do not use on circuits exceeding specified voltage Higher voltage will damage thermostat and could cause shock or fire hazard Thermostat installation and all compo nents of the system shall conform to Class II circuits per the NEC code To prevent electrical shock and or equipment damage disconnect e...

Страница 2: ...es from the old thermostat one at a time DO NOT let the wires fall back into the wall Install the new thermostat using the follow ing procedures ATTACH BASE TO WALL Remove packing material from the thermo stat Place fingers of one hand on the center top and bottom portion of the thermostat Grasp the base in the other hand on top and bottom center and gently pull straight out Forcing or prying on t...

Страница 3: ...ection for proper thermostat configuration THERMOSTAT TERMINALS Upper L SA SB SC OT Malfunction Light Remote Sense A Remote Sense B Remote Sense C Outdoor Sensor Comfort Alert Interface Module THERMOSTAT TERMINALS Upper L SA SB SC OT Malfunction Light Remote Sense A Remote Sense B Remote Sense C Outdoor Sensor Comfort Alert Interface Module 3 THERMOSTAT TERMINALS Lower SYSTEM C R HM W2 DHM E W1 Y2...

Страница 4: ...YSTEM ONLY If you have a single stage compressor system see the diagram below A relay customer provided should be installed as shown in Fig 5 to switch the fan speed to the next lower speed on a call for dehumidification from the thermostat The reduction in air flow allows the coil to remove more humidity from the air The relay should be rated for blower motor load Since this configuration reduces...

Страница 5: ...h 6 step 6 is for heat pump only These items allow the cycle times in heating cooling and auxiliary heat pump systems only to be increased or decreased The factory set values can be adjusted higher for longer cycles or lower for shorter cycles NOTE Some manufacturers still instruct you to set the anticipator to the current draw of the equipment That instruction applies only to mercury bulb or mech...

Страница 6: ... in sequence after HEAT if HEAT PUMP is selected Program RUN TIME FWD Heat Pump ONLY TIME FWD TIME FWD TIME FWD TIME FWD TIME FWD TIME FWD TIME FWD 6 SET CYCL AUX 08 1 to 40 9 HEAT FAN DELA OFF 00 0 to 127 seconds 10 PUMP ON OFF 11 COMP OFF DELA 60 0 to 99 7 COOL FAN DELA OFF 00 0 to 127 seconds 8 5 5 5 5 5 5 5 5 7 7 7 7 7 7 5 5 FAN DELA ON 01 1 to 30 seconds Selects time delay for fan ON Applies ...

Страница 7: ...nst premature compressor failure by locking out the compressor for at least five minutes after each cycle When the thermo stat is in compressor lockout the word COOL will flash on the display With heat pump systems the word HEAT will flash if the lockout occurs during a heat cycle During this period the compressor will not be energized COMFORT ALERT WITH ACTIVE PROTECTION Installer table step 16 T...

Страница 8: ...t service interval SERVICE REMINDER 8 1 Step Press Button s Displayed Press or to select COMMENTS Factory Default PAD TIME OFF Hrs or REM PAD TIME No of Hrs ON or OFF Set Humidifier Maintenance Reminder SERVICE 3 FLTR TIME OFF Hrs or REM FLTR TIME No of Hrs ON or OFF Set Air Filter Maintenance Reminder TIME FWD Service Button Menu Returns to Normal Operation PRGM RUN 2 SET PAD TIME 100 Hrs 25 to 1...

Страница 9: ...e and yellow for second stage EMERGENCY heat pump only Press SYSTEM to select EMER mode The LED indicator will glow red for first stage Aux in emergency mode A flashing red LED indicates a malfunction in the system HUMIDIFIER SYSTEM IF INSTALLED 1 Press SYSTEM until HEAT is shown at the top of the display 2 Press the HUMIDITY button once and release Then press the to the maximum humidity setpoint ...

Страница 10: ...t does not respond when keys are pressed or the thermostat is not operating properly you may use the reset button located on the back of the thermostat body see fig 2 Thermostat programming and configuration will not be affected by pressing the reset button However the clock will need to be reset RESETTING THERMOSTAT CONFIGURATION AND PROGRAMMING The thermostat can be reset back to default program...

Страница 11: ... the size Digital thermostats normally provide precise narrow or wide temperature swing of the Heating System equipment may be temperature control and may cycle faster than influencing the cycle rate someoldermechanicalmodels Afastercycle ratemeanstheunitturnsononoffmorefrequently but runs for a shorter time so there is no increase in energy use If you would like to increase the cycle time refer t...

Страница 12: ... will indicate HOLD and the number of hours remaining in the hold period will be indicated with the word HRS To adjust the length of time for the override press TIME FWD or TIME BACK The time you select will become the new number of hours for the Hold Til timing Once your time is selected let the thermostat revert back to normal operation on its own to accept the change Many furnaces have safety d...

Отзывы: