The configuration menu allows you to set certain thermostat 
operating  characteristics  to  your  system  or  personal 
requirements. To enter the menu: Set your thermostat to OFF 
and press the 

 and 

 buttons simultaneously. The display 

will show the first item in the configuration menu. Press RUN/

Configuration Menu

Menu 

Reference 

Number

Press

Key

Displayed 

(Factory

Default)

Press 

 or 

 

to select from 
listed options

Comments

1

 and 

SS

HP

Select Single Stage (SS) or
Heat Pump (HP, 1 compressor)

2

RUN/HOLD*

CS

(OFF)

On

Select Cool Savings Feature On or OFF

RUN/HOLD*

CS

(3)

1, 2, 3, 4, 5, 6

If CS selected On, selects Cool Savings value

3

RUN/HOLD*

E

(On)

OFF

Select Energy Management Recovery On or OFF

4

RUN/HOLD*

CR Heat

(ME)

FA, SL

Select Adjustable Anticipation, cycle rate, 
Heat Single Stage

5

RUN/HOLD*

CR Cool

(FA)

SL

Select Adjustable Anticipation, cycle rate, 
Cool Single Stage

6

RUN/HOLD*

CL

(OFF)

On

Select Compressor lockout OFF or On

7

RUN/HOLD*

L

(On)

OFF

Select Display Light On or OFF

8

RUN/HOLD*

Temp

(0 HI)

4 LO to 

4 HI

Select temperature display adjustment higher or lower 

9

RUN/HOLD*

o

F

o

C

Select 

o

F / 

o

C Display (temperature units in Fahrenheit 

or Celsius)

10

RUN/HOLD*

Change Filter

(OFF)

On

Select filter replacement indicator OFF or On

RUN/HOLD*

Change Filter

(200 h)

25 to 1975

If Change Filter selected On, selects time interval for 
Change Filter Indicator. (in 25 hour increments)

11

RUN/HOLD*

Returns to normal operation

*Press 

RUN/HOLD

 to advance to next item or 

TIME

 to move backwards to previous item

INSTALLER/CONFIGURATION MENU 

1)  System Configuration

 - Selects SS (Single Stage) or HP 

(Heat Pump) operating mode. Default configuration is SS. 
For Heat Pump operation choose HP.

2)  Select  CS  (Cool  Savings™)

  -  With  Cool  Savings™ 

enabled,  the  thermostat  will  make  small  adjustments  to 
the  Setpoint  temperature  during  periods  of  high  demand 
to  reduce  cooling  system  running  time  and  save  energy. 
When the cooling system has been running for more than 
20 minutes, humidity in the home will be lower and a higher 
setpoint temperature will feel comfortable. After 20 minutes 
of run time, the thermostat will start increasing the setpoint 
temperature in steps of less than one degree as the system 
continues to run. These adjustments will eventually cause 
the system to satisfy the thermostat and turn the system off 
to reduce the energy consumption. When the Cool Savings 
feature is active and making adjustments, the display will 
show “Save”. The amount of the adjustments to the setpoint 
temperature is dependent on the Cool Savings value that 
is set, 1 being the least adjustment and 6 being the most 
adjustment.  With  this  feature  set  to  OFF,  no  change  will 
occur  when  the  cooling  system  is  continuously  running 
during the periods of high demand. Periods of high demand 
will  normally  occur  during  the  late  afternoon  and  early 
evening on the hottest days of the summer.

3)  Select  Energy  Management  Recovery 

-  Energy 

Management  Recovery  (E)  On  enables  the  thermostat 
to  start  heating  or  cooling  early  to  make  the  building 
temperature  reach  the  program  setpoint  at  the  time  you 
specify.  Heating  will  start  5  minutes  early  for  every  1°  of 
temperature required to reach setpoint. 

4  &  5)  Select  Cycle  Rate  Selection

  -  The  factory  default 

setting  for  Single  Stage  Heat  is  Medium  Cycle  (ME).  For 
Single Stage Cool the default setting is fast (FA). To change 
cycle rate, press the 

 and 

 buttons. 

 

The cycle rate differentials for different settings are:

MODE 

Fast 

Medium 

Slow

 

(FA) 

(ME) 

(SL)

SS Heat 

0.6°F 

  0.8°F 

1.2°F

SS Cool 

1.2°F 

1.7°F

6)  Select Compressor Lockout CL OFF or ON

 - Selecting 

CL On will cause the thermostat to wait 5 minutes between 
cooling  cycles.  This  is  intended  to  help  protect  the 
compressor from short cycling. Some newer compressors 
already have a time delay built in and do not require this 
feature. Your  compressor  manufacturer  can  tell  you  if  the 

HOLD to change to the next menu item or press TIME to go 
backwards to the previous item in the menu. To exit the menu 
and return to the program operation, press PRGM. If no keys 
are pressed within fifteen minutes, the thermostat will revert to 
normal operation.

Содержание 1F87-0261

Страница 1: ...7 0261 Thermostat Model Programming Choice 1F87 0261 7 Day Programmable SPECIFICATIONS Electrical Rating Battery Power mV to 30 VAC 50 60 Hz or DC Input Hardwire 20 to 30 VAC Terminal Load 1 0 A per terminal 1 5A maximum all terminals combined Setpoint Range 45 to 90 F 7 to 32 C Differential Single Stage Heat 0 6 F Cool 1 2 F adjustable Differential Heat Pump Heat 1 2 F Cool 1 2 F adjustable Opera...

Страница 2: ...e O B switch on this thermostat is factory set to the O position This will accommodate the majority of heat pump applications which require the changeover relay to be energized in COOL If the thermostat you are replacing or the heat pump being installed with this thermostat requires a B terminal to energize the changeover relay in HEAT the O B switch must be moved to the B position Mounting Hole M...

Страница 3: ...of the next program period To deactivate the EMR function see the Configuration menu on Page 5 The thermostat will then wait until the programmed time to start the system for a temperature change INSTALLATION WIRING DIAGRAMS R C 24 VAC 120 VAC Hot Neutral THERMOSTAT SYSTEM G W Figure 2 Typical wiring diagram for single transformer single stage systems TRANSFORMER Class II Current Limited Changeove...

Страница 4: ...lace the cover line up the cover with the base and press until the cover snaps onto the base The Thermostat Buttons and Switches 1 Raises temperature setting 2 Lowers temperature setting 3 TIME button 4 SYSTEM switch COOL OFF HEAT EMER 5 PRGM program button 6 FAN switch ON AUTO 7 RUN HOLD program button The Display 8 Indicates days of the week 9 Indicates setpoint temperature This is blank when sy...

Страница 5: ... humidity in the home will be lower and a higher setpoint temperature will feel comfortable After 20 minutes of run time the thermostat will start increasing the setpoint temperature in steps of less than one degree as the system continues to run These adjustments will eventually cause the system to satisfy the thermostat and turn the system off to reduce the energy consumption When the Cool Savin...

Страница 6: ...reminder On or OFF If selected On press RUN HOLD to select the time period from 25 to 1975 hours in 25 hour increments In a typical application 200 hours default of run time is approximately 30 days After the selected time of blower operation the thermostat will display Change Filter as a reminder to change or clean your air filter When Change Filter is displayed press the RUN HOLD button to clear...

Страница 7: ...t Current Time and Day 1 Press TIME button once The display will show the hour only EXAMPLE 2 Press and hold either or until you reach the correct hour and AM PM designation AM begins at midnight PM begins at noon 3 Press TIME once again The display window will show the minutes only EXAMPLE 4 Press and hold either or until you reach the correct minutes 5 Press TIME once again The display will show...

Страница 8: ...g Program 1 Move SYSTEM switch to COOL position 2 Follow Enter Heating Program for entering your cooling program using your selected cooling times and temperatures PROGRAMMING If the outside temperature is below 50o F disconnect power to the cooling system before programming Energizing the air conditioner compressor during cold weather may cause personal injury or property damage CAUTION CHECK YOU...

Страница 9: ...hermostat clicks in Cooling if the compressor lock out option is selected in the configuration menu Item 6 Heat Cool or Fan Runs Constantly 1 Possible short in wiring 2 Possible short in thermostat 3 Possible short in Heat Cool Fan system 4 Fan Switch set to Fan On Check each wire connection to verify they are not shorted or touching together No bare wire should stick out from under terminal screw...

Страница 10: ...10 NOTES ...

Страница 11: ...11 NOTES ...

Страница 12: ...www white rodgers com White Rodgers is a division of Emerson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co Homeowner Help Line 1 800 284 2925 ...

Отзывы: