White Rodgers 1F87-0261 Скачать руководство пользователя страница 2

2

INSTALLATION 

REMOVE OLD THERMOSTAT

1.  Shut off electricity at the main fuse box until installation is 

complete. Ensure that electrical power is disconnected.

2.  Remove the front cover of the old thermostat. 

With wires 

still  attached, 

remove  wall  plate  from  the  wall.  If  the 

old  thermostat  has  a  wall  mounting  plate,  remove  the 
thermostat and the wall mounting plate as an assembly.

3. 

Identify each wire attached to the old thermostat using 
the labels enclosed with the new thermostat.

4.  Disconnect the wires from old thermostat one at a time. 

DO 

NOT LET WIRES FALL BACK INTO THE WALL.

5.  Install new thermostat using the following procedures.

ATTENTION!

This product does not contain mercury. However, this product 
may replace a unit which contains mercury.
Do  not  open  mercury  cells.  If  a  cell  becomes  damaged,  do 
not touch any spilled mercury. Wearing nonabsorbent gloves, 
take up the spilled mercury and place into a container which 
can be sealed. If a cell becomes damaged, the unit should be 
discarded.
Mercury must not be discarded in household trash. When the 
unit  this  product  is  replacing  is  to  be  discarded,  place  in  a 
suitable container. Refer to www.white-rodgers.com for location 
to send the product containing mercury.

ATTACH THERMOSTAT BASE TO WALL

1.  Remove the packing material from the thermostat. Gently 

pull the cover straight off the base. Forcing or prying on the 
thermostat will cause damage to the unit.

2.  Place  base  over  hole  in  wall  and  mark  mounting  hole 

locations on wall using base as a template (see Fig.1).

3.  Move base out of the way. Drill mounting holes.
4.  Push wires through opening in thermostat base.
5.  Fasten  base  loosely  to  wall  using  two  mounting  screws. 

Place  a  level  against  bottom  of  base,  adjust  until  level, 
and then tighten screws. (Leveling is for appearance only 
and will not affect thermostat operation.) If you are using 
existing mounting holes, or if holes drilled are too large and 
do not allow you to tighten base snugly, use plastic screw 
anchors to secure subbase.

6.  Connect  wires  to  terminals  on  base  using  appropriate 

wiring schematic (see figs. 2 through 4).

7.  Push excess wire into wall and plug hole with a fire-resistant 

material  (such  as  fiberglass  insulation)  to  prevent  drafts 
from affecting thermostat operation.

O/B TERMINAL SWITCH SELECTION

The  O/B  switch  on  this  thermostat  is  factory  set  to  the  “O” 
position.  This  will  accommodate  the  majority  of  heat  pump 
applications,  which  require  the  changeover  relay  to  be 
energized in COOL. If the thermostat you are replacing or the 
heat pump being installed with this thermostat requires a “B” 
terminal, to energize the changeover relay in HEAT, the O/B 
switch must be moved to the “B” position.

Mounting

Hole

Mounting

Hole

Opening

for wires

Gas/Elec

Switch

Battery

Door

O/B

Switch

Figure 1. Thermostat Base

GAS / ELEC SWITCH

If your system is a heat pump, the GAS/ELEC Switch must be 
set to ELEC (see Fig. 1) If your system is a single stage, the 
switch must be set to GAS. The switch setting must agree with 
the system configuration selected in the configuration menu.

BATTERY LOCATION

“AA” Alkaline Batteries

Two  “AA”  alkaline  batteries  are  installed  in  your  thermostat 
with  a  battery  tag  to  prevent  power  drainage.  Prior  to  use, 
open  the  battery  door  and  remove  the  battery  tag. To  open, 
pull the battery door as shown by the arrow and lift open. The 
two “AA”  batteries  will  operate  all  functions  or  maintain  time 
and continuously display the temperature during a loss of AC 
power. Installed batteries will also allow programming prior to 
installation. To replace batteries, pull the battery door shown 
by the arrow and lift open. Using the polarity indicated inside 
the battery door, insert the batteries. To close the battery door, 
swing  the  door  down  while  pulling  in  the  direction  of  arrow. 
Once fully down, snap the door back into position.
Thermostat can be powered by system AC power or Battery. If 

 is displayed, the thermostat is battery powered. If 

 

is not 

displayed, thermostat is system powered with optional battery 
back-up. When battery power remaining is approximately half, 
the 

 will be displayed. When 

“Change 

 is displayed, 

install fresh “AA” alkaline batteries immediately. For best results, 
use new premium brand alkaline batteries such as Duracell

®

 or 

Energizer

®

. We recommend replacing batteries every 2 years. 

If the home is going to be unoccupied for an extended period 
(over 3 months) and 

 

is displayed, the batteries should be 

replaced before leaving. When less than two months of battery 
life remain, the setpoint temperature will offset by 10 degrees 
(10 degrees cooler in Heat mode / 10 degrees warmer in Cool 
mode). If offset occurs, the normal setpoint can be manually 
reset  with 

  or 

.  Another  offset  will  occur  within  two 

days if batteries are not replaced. To replace the batteries, set 
system to OFF.

Содержание 1F87-0261

Страница 1: ...7 0261 Thermostat Model Programming Choice 1F87 0261 7 Day Programmable SPECIFICATIONS Electrical Rating Battery Power mV to 30 VAC 50 60 Hz or DC Input Hardwire 20 to 30 VAC Terminal Load 1 0 A per terminal 1 5A maximum all terminals combined Setpoint Range 45 to 90 F 7 to 32 C Differential Single Stage Heat 0 6 F Cool 1 2 F adjustable Differential Heat Pump Heat 1 2 F Cool 1 2 F adjustable Opera...

Страница 2: ...e O B switch on this thermostat is factory set to the O position This will accommodate the majority of heat pump applications which require the changeover relay to be energized in COOL If the thermostat you are replacing or the heat pump being installed with this thermostat requires a B terminal to energize the changeover relay in HEAT the O B switch must be moved to the B position Mounting Hole M...

Страница 3: ...of the next program period To deactivate the EMR function see the Configuration menu on Page 5 The thermostat will then wait until the programmed time to start the system for a temperature change INSTALLATION WIRING DIAGRAMS R C 24 VAC 120 VAC Hot Neutral THERMOSTAT SYSTEM G W Figure 2 Typical wiring diagram for single transformer single stage systems TRANSFORMER Class II Current Limited Changeove...

Страница 4: ...lace the cover line up the cover with the base and press until the cover snaps onto the base The Thermostat Buttons and Switches 1 Raises temperature setting 2 Lowers temperature setting 3 TIME button 4 SYSTEM switch COOL OFF HEAT EMER 5 PRGM program button 6 FAN switch ON AUTO 7 RUN HOLD program button The Display 8 Indicates days of the week 9 Indicates setpoint temperature This is blank when sy...

Страница 5: ... humidity in the home will be lower and a higher setpoint temperature will feel comfortable After 20 minutes of run time the thermostat will start increasing the setpoint temperature in steps of less than one degree as the system continues to run These adjustments will eventually cause the system to satisfy the thermostat and turn the system off to reduce the energy consumption When the Cool Savin...

Страница 6: ...reminder On or OFF If selected On press RUN HOLD to select the time period from 25 to 1975 hours in 25 hour increments In a typical application 200 hours default of run time is approximately 30 days After the selected time of blower operation the thermostat will display Change Filter as a reminder to change or clean your air filter When Change Filter is displayed press the RUN HOLD button to clear...

Страница 7: ...t Current Time and Day 1 Press TIME button once The display will show the hour only EXAMPLE 2 Press and hold either or until you reach the correct hour and AM PM designation AM begins at midnight PM begins at noon 3 Press TIME once again The display window will show the minutes only EXAMPLE 4 Press and hold either or until you reach the correct minutes 5 Press TIME once again The display will show...

Страница 8: ...g Program 1 Move SYSTEM switch to COOL position 2 Follow Enter Heating Program for entering your cooling program using your selected cooling times and temperatures PROGRAMMING If the outside temperature is below 50o F disconnect power to the cooling system before programming Energizing the air conditioner compressor during cold weather may cause personal injury or property damage CAUTION CHECK YOU...

Страница 9: ...hermostat clicks in Cooling if the compressor lock out option is selected in the configuration menu Item 6 Heat Cool or Fan Runs Constantly 1 Possible short in wiring 2 Possible short in thermostat 3 Possible short in Heat Cool Fan system 4 Fan Switch set to Fan On Check each wire connection to verify they are not shorted or touching together No bare wire should stick out from under terminal screw...

Страница 10: ...10 NOTES ...

Страница 11: ...11 NOTES ...

Страница 12: ...www white rodgers com White Rodgers is a division of Emerson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co Homeowner Help Line 1 800 284 2925 ...

Отзывы: