Check all local codes for requirements, especially for the size and 

type of gas supply line required.

Note: 

Never use plastic pipe. Check to confirm whether your local 

codes allow copper tubing or galvanized.

Note:

 Since some municipalities have additional local codes, it is 

always best to consult your local authority and installation code.

Installing a New Main Gas Cock 

Each appliance should have its own manual gas cock.

A  manual  main  gas  cock  should  be  located  in  the  vicinity  of 

the unit. Where none exists, or where its size or location is not 

adequate, contact your local authorized installer for installation 

or relocation.

Compounds used on threaded joints of gas piping shall be resistant 

to the action of liquefied petroleum gases. The gas lines must be 

checked for leaks by the installer. This should be done with a soap 

solution watching for bubbles on all exposed connections, and if 

unexposed, a pressure test should be made. 

Never use an exposed flame to check for leaks. Appliance must 

be disconnected from piping at inlet of control valve and pipe 

capped or plugged for pressure test. Never pressure test with 

appliance connected; control valve will sustain damage!

A gas valve and ground joint union should be installed in the gas 

line upstream of the gas control to aid in servicing. It is required 

by the National Fuel Gas Code that a drip line be installed near 

the gas inlet. This should consist of a vertical length of pipe tee 

connected into the gas line that is capped on the bottom in which 

condensation and foreign particles may collect.

The use of the following gas connectors is recommended:

—  ANS Z21.24 Appliance Connectors of Corrugated Metal Tub-

ing and Fittings

—  ANS  Z21.45 Assembled  Flexible Appliance  Connectors  of 

Other Than All-Metal Construction

The above connectors may be used if acceptable by the authority 

having jurisdiction. The state of Massachusetts requires that a flex-

ible appliance connector cannot exceed three feet in length.

Pressure Testing of the Gas Supply System

1.   To check the inlet pressure to the gas valve, a 1/8" (3mm) N.P.T. 

plugged tapping, accessible for test gauge connection, must be 

placed immediately upstream of the gas supply connection to 

the appliance.

2.  The  appliance  and  its  individual  shutoff  valve  must  be 

disconnected from the gas supply piping system during any 

pressure testing of that system at test pressures in excess of 

1/2 psig (3.5 kPa).

3.   The appliance must be isolated from the gas supply piping 

system by closing its individual manual shutoff valve during 

any pressure testing of the gas supply piping system at test 

pressures equal to or less than 1/2 psig (3.5 kPa).

Figure 3

Attention!

 If one of the above procedures results in pressures in 

excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve, 

it will result in a hazardous condition.

Checking Manifold Pressure
VF24FP3-1 

Natural  gas  will  have  a  manifold  pressure  of 

approximately 3.5" w.c. (.871kPa) for maximum input or 1.7" w.c. 

(.423kPa) for minimum input at the pressure regulator outlet with 

the inlet pressure to the pressure regulator from a minimum of 5.0" 

w.c. (1.120kPa) for the purpose of input adjustment to a maximum 

of 10.5" w.c. (2.614kPa). 

VF24FP2-2

  Natural  gas  will  have  a  manifold  pressure  of 

approximately 6.0" w.c. (1.49kPa) at the pressure regulator outlet 

with the inlet pressure to the pressure regulator from a minimum 

of 7.0" w.c. (1.74kPa) for the purpose of input adjustment to a 

maximum of 10.5" w.c. (2.615kPa). 

VF24FP3-1

 Propane gas will have a manifold pressure approximately 

10.0"w.c.  (2.49kPa)  for  maximum  input  or  6.3"w.c.  (1.568kPa) 

for minimum input at the pressure regulator outlet with the inlet 

pressure to the pressure regulator from a minimum of 11.0"w.c. 

(2.739kPa) for the purpose of input adjustment to a maximum of 

13.0"w.c. (3.237kPa). 

VF24FP2-2

 Propane gas will have a manifold pressure approximately 

10.0"w.c. (2.49kPa) at the pressure regulator outlet with the inlet 

pressure to the pressure regulator from a minimum of 11.0"w.c. 

(2.739kPa) for the purpose of input adjustment to a maximum of 

13.0"w.c. (3.237kPa). 

GAS SUPPLY

Recommended Gas Pipe Diameter

Pipe Length

Schedule 40 Pipe

Inside Diameter

Tubing, Type L 

Outside Diameter

Nat.

L.P.

Nat.

L.P.

0-10 feet

0-3 meters

1/2”

12.7mm

3/8”

9.5mm

1/2”

12.7mm

3/8”

9.5mm

10-40 feet

4-12 meters

1/2”

12.7mm

1/2”

12.7mm

5/8”

15.9mm

1/2”

12.7mm

40-100 feet

13-30 meters

1/2”

12.7mm

1/2”

12.7mm

3/4”

19mm

1/2”

12.7mm

100-150 feet

31-46 meters

3/4”

19mm

1/2”

12.7mm

7/8”

22.2mm

3/4”

19mm

Содержание VF24FP2-2

Страница 1: ...er to page 6 WARNING If not installed operated and main tained in accordance with the manufacturer s in structions this product could expose you to sub stances in fuel or from fuel combustion which can cause death or serious illness Do not store or use gasoline or other flamma ble vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any a...

Страница 2: ...n 11 Placement of Glowing Embers Rock Wool 12 Operation Instructions Flame Appearance 12 VF24FP3 1 Lighting Instructions 13 VF24FP2 2 Lighting Instructions 14 Pilot Flame Characteristics 15 16 Main Burner and Thermostat Operation 16 VF24FP2 2 Conversion to 10 000 BTU s for Bedroom Installation 16 Wiring 17 Troubleshooting 18 Parts List 19 How to Order Repair Parts 19 Parts View 20 Optional Brick L...

Страница 3: ... of high surface temperature and should stay away to avoid burns or clothing ignition Young childrenshould becarefullysupervisedwhen they are in the same room with the appliance Do not place clothing or other flammable material on or near the appliance Installation and repairshould be done by a QUALIFIED SERVICE PERSON This appliance should be inspected before use and at least annually by a profess...

Страница 4: ...perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on walls of newcylindersandtanks ispossible Therefore peopleshould be particularly alert and careful when new tanks or cylinders are placed in service Odor fade can occur in new tanks or reinstalled old tan...

Страница 5: ...r your gas company before changing spud orifice size WARNING Failure to keep the primary air opening s of the burner s clean may result in sooting and property damage Instructions to Installer 1 Installer must leave instruction manual with owner after installation 2 Installermusthaveownerfilloutandmailwarrantycardsupplied with unvented room heater 3 Installer should show owner how to start and opera...

Страница 6: ...tinuous water vapor retarder with a rating of one perm or less with openings gasketed or sealed and b Weatherstripping has been added on openable windows and doors and c Caulking or sealants are applied to areas such as joints around window and door frames between sole plates and floors between wall ceiling joints between wall panels at penetrations for plumbing electrical and gas lines and at othe...

Страница 7: ...amount of BTU Hr used BTU Hr maximum the space can support BTU Hr actual amount of BTU Hr used Example 25 600 BTU Hr maximum the space can support 38 000 BTU Hr actual amount of BTU Hr used Warning If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction provide adequate combustion and ventilation air by...

Страница 8: ...uge connection must be placed immediately upstream of the gas supply connection to the appliance 2 The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1 2 psig 3 5 kPa 3 The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff ...

Страница 9: ...place opening to any combustible wall or material should not be less than 4 inches 2 Clearances from the top of the fireplace opening to the ceiling should not be less than 30 inches Mantel Clearances for Built in Installation Figure 5 Do not attach combustible material to the mantel of your fireplace This is a fire hazard Figure 6 No greeting cards stockings or ornamentation of any type should bepla...

Страница 10: ...g flange will secure the fireplace 6 Placeleftmantelsideagainstbase Insertdowelsinbreastboard into left mantel side 7 Use four 4 pre drilled screw holes on back of breastboard to secure breastboard to mantel sides with four 4 Phillips wood screws 8 Place mantel top onto mantel 9 Installation of fireplace into mantel is completed Installation of Trim 1 Lower bottom louver 2 Remove screen from fireplace...

Страница 11: ...ng the appliance the gas supply will enter on right hand side See Gas Supply Page 8 3 Insert fireplace into enclosure 4 Attach nailing flanges to framing with a screw or nail 5 Finishedwallsurfacewillbeflushtotheleadingedgeoffireplace top and sides 6 Installation of built in fireplace is completed Installation of Trim 1 Lower bottom louver 2 Remove screen from fireplace 3 Remove top louver from fireplace...

Страница 12: ...cked as the log set is installed In normal operation at full rate after 10 to 15 minutes the flame appearance should be sets of yellow flames NOTE all flames will be random by design flame height will go up and down Glowing embers rock wool can cover the pan burner in between the front and middle logs but very little is necessary to cover this area Excess ember material causes the yellow flame to becom...

Страница 13: ...le Turn ON OFF switch to OFF position and or set thermostat if present to lowest setting If applicable Turn off all electric power to the heater 1 STOP Read the safety information label 2 Make sure the manual shutoff valve is fully open 3 This gas log set is equipped with an ignition device piezo which lights the pilot If piezo ignitor does not light the pilot refer to Step 7 4 Turn gas control kn...

Страница 14: ... setting 3 Turn off all electric power to the appliance if applicable 4 Pushingascontrolknobslightlyandturnclockwise to OFF Do not force 5 Wait ten 10 minutes to clear out any gas Then smell for gas including near floor If you smell gas STOP Follow B in the safety information on other side If you do not smell gas Go to the Next step 6 Find pilot the pilot is located in front of rear log 7 Turn manu...

Страница 15: ...ing the thermocouple This will cause the thermocouple to cool When the thermocouple cools the heater will shut down Correct Flame Pattern Correct Flame Pattern THERMOCOUPLE LPG THERMOCOUPLE NATURAL THERMOPILE PILOT PILOT THERMOCOUPLE NATURAL THERMOCOUPLE LPG VF24FP3 1 Pilot Figure 13 VF24FP2 2 Pilot Figure 15 Incorrect Flame Pattern Incorrect Flame Pattern THERMOCOUPLE LPG THERMOCOUPLE NATURAL THE...

Страница 16: ...lint from carpeting bedding materials etc Logs Be careful cleaning and handling logs so as not to damage them If logs break or fall apart in handling spray the broken pieces and fibers with water sweep up and discard main burner orifice marked 1 30mm 9 ForPropane LP gas only remove 20 000 BTU main burner orifice marked 55 from orifice fitting and replace with 10 000 BTU main burner orifice marked 64 10 ...

Страница 17: ... be checked with a millivolt meter 0 1000 MV range Remote Receiver Use the following steps to place the remote receiver adjacent to the gas valve Attention The remote receiver bracket is not used in this installation 1 The remote receiver can not be placed behind the gas valve and burner assembly 2 When facing the appliance the remote receiver must be placed to the right of the gas valve and burne...

Страница 18: ...rect Replace gas regula tor 7 ODS pilot lights but flame goes out when control knob is released a Control knob not fully pressed in Press in control knob fully b Control knob not pressed in long enough After ODS pilot lights keep control knob pressed in 30 seconds c Manual Shutoff valve not fully open Fully open manual shutoff valve d Thermocouple connection loose at control valve Hand tighten unti...

Страница 19: ...T SHOWN P 263 NIPPLE 8 NOT SHOWN 15465 TUBING VALVE TO PILOT REGULATOR NAT NOT SHOWN 15466 TUBING PILOT REGULATOR TO PILOT NAT NOT SHOWN R 7063 PILOT REGULATOR NAT VF24FP2 2 ONLY 19 R 5170 PILOT ASSEMBLY LPG 19 R 5171 PILOT ASSEMBLY NAT 21 P 265 ORIFICE NAT 20 000 BTU 21 P 266 ORIFICE NAT 10 000 BTU 21 P 193 ORIFICE LPG 10 000 BTU 25 24157 VALVE NAT 25 24158 VALVE LPG 26 R 2480 INLET REGULATOR LPG...

Страница 20: ...24161 0 1207 Page 20 PARTS VIEW VF24FP2 THERMOSTATIC VALVE VF24FP3 MILLIVOLT VALVE ...

Страница 21: ...inserting the 2 side brick liners 4 Loosen top and bottom 10 x 1 2 screws from each side of firebox 5 Place the 2 liner mounting brackets over the front edges of the 2 side brick liners Attach liner mounting brackets to outer casing with 4 four 10 x 1 2 screws from Step 4 6 Replacelogsintoburnerassembly Referto LogPlacement Page 12 7 Attach screen assembly to fireplace 8 Installation of optional bri...

Страница 22: ...to motor Align and attach blower assembly to outer casing side See Figure 2 10 Snap Heyco into blower shield side 11 Placeblowershieldsideadjacenttomotor Routeblowermotor wires through Heyco on blower shield side See Figure 3 and Figure 4 VFS BK for Unvented Gas Fireplace Model VF24FP2 2 VF24FP3 1 12 Attach black wire from wire harness to OFF terminal on AUTO OFF ON switch 13 Attach white black wi...

Страница 23: ...ed on left front of valve cover on burner assembly Insert blower shield front adjacent to blower motor and blower shield side Align clearance hole on blower shield front with left front screw hole on valve cover Attach blower shield front to valve cover with 10 x 1 2 screw See Figure 3 for not installed or Figure 4 for installed 25 For fireplace that is not installed replace burner assembly into in...

Страница 24: ... screws at interior top of inner casing that were loosened in Step 6 30 Attach burner assembly to inner bottom with three 3 10 x 1 2 screws from Step 5 31 Attach rear log support to inner casing with three 3 10 x 1 2 screws from Step 4 32 Place and align blower diverter on top of inner casing Attach deflector to top of inner casing with two 2 10 x 1 2 screws See Figure 6 33 Attach top louver with t...

Страница 25: ...g the ground the appliance cord plug can be plugged into the adapter and be electrically grounded CAUTION Labelallwirespriortodisconnectionwhenservic ing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing Oiling Blower Motor The blower motor does not have oiling holes Do not attempt to oil the blower motor WARNING Unplugging of blower accessor...

Страница 26: ...rt number and description coincide 1 2 3 Index Number Part Number Description VPF24BR 1 Brass Trim Kit 1 11328 Trim Top 2 11326 Trim Left 3 11327 Trim Right VPF24SS 1 Stainless Steel Trim Kit 1 20227 Trim Top 2 20228 Trim Left 3 20229 Trim Right VPF24HP 1 Hammered Pewter Trim Kit 1 20224 Trim Top 2 20225 Trim Left 3 20226 Trim Right ...

Страница 27: ...24161 0 1207 Page 27 SERVICE NOTES ...

Страница 28: ...24161 0 1207 Page 28 Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 PH 618 233 7420 or 800 851 3153 FAX 618 233 7097 or 800 443 8648 info empirecomfort com www empirecomfort com ...

Отзывы: