20 WhisperPower Battery Charger
12 V 100 A
Code
Condition
Corrective Action
A01
Temperature Sensor (BTS) is defective.
Check and or replace the sensor.
E01
Unit shutdown due to low AC Input
(< 85 +/- 5Vac)
Check AC input source. The unit will
automatically recover when the AC Input
voltage return to > 108 +/-5Vac
E02
Unit shutdown due to high AC Input
(>270 +/- 5Vac)
Check AC input source. The unit will
automatically recover when the AC Input
voltage returns to < 260 +/-5Vac
E03
Battery is connected backwards
Check all battery connections
E04
Charger Internal temperature is too high and it has to shut
down. The unit will automatically recover when the unit
cools down.
The ventilation of the unit is blocked or the
environmental temperature is high. Reduce
charging current or improve the ventilation near
the unit.
E05
Not used.
E06
For non- Lithium Battery type setting:
High battery temperature >70 °C (158°F) is sensed by the
BTS when installed. The unit will shut down. The unit will
automatically recover when the battery temperature has
reduced to 60°C (140°F).
For Lithium battery type setting:
High battery temperature >60 °C (140°F) is sensed by the
BTS when installed. The unit will shut down. The unit will
automatically recover when the battery temperature has
reduced to 55°C (131°F).
Check the battery, charger setting, and its
environment.
E07
For non- Lithium Battery type setting:
Low battery temperature < -25°C (-13°F) is sensed by the
BTS when installed. The unit will shut down. The unit will
automatically recover when battery temperature reaches
-20°C (-4°F).
For Lithium Battery type setting:
Low battery temperature < 0°C (32°F) is sensed by the
BTS when installed. The unit will shut down. The unit will
automatically recover when battery temperature reaches
5°C (41°F).
It is not recommended to charge the battery at
low temperatures.
E08
DC Output fuses are blown.
Check battery connection and replace the fuse
with the same type and rating.
E09
Unit shutdown due to high battery voltage (> 17 Vdc). The
unit will automatically recover when battery Voltage is
reduced to <16Vdc.
Check battery and charger settings. Check also
if there is any other DC supply connected to the
battery banks.
Содержание Supreme WP-BC 12/100-3
Страница 1: ...12 V 100 A WP BC 12 100 3 Enjoy Green Energy Battery Charger Supreme whisperpower com User Manual ...
Страница 2: ...2 WhisperPower Battery Charger 12 V 100 A ...
Страница 24: ...24 WhisperPower Battery Charger 12 V 100 A ...
Страница 25: ...WhisperPower Battery Charger 12 V 100 A 25 ...
Страница 26: ...26 WhisperPower Battery Charger 12 V 100 A ...
Страница 27: ...WhisperPower Battery Charger 12 V 100 A 27 Proposed charging profile 2020 for Litium cell balancing ...