28 WhisperPower Inverter / Battery Charger
E10
When unit is in By-Pass mode, Battery Charging
voltage too high.
Check battery setting. Check and any other DC
power sources connected to the battery has high
voltage.
E11
Bad Battery classification: E01 (By-Pass Mode)
condition has not been solved. AC Charger has
shutdown.
- Check corrective action in E01 (By-pass Mode)
and restart the charging process by removing
and reconnecting the AC Input Source.
Other conditions leading to Bad Battery
Classification: Battery Voltage remains below
2/5/9.5V after 2/5/15 minutes of charge.
- Check if there is any heavy DC load connected
to the battery as stated in E01 (By-pass mode).
Restart the charging process.
- Change to a new battery.
E12
When unit is in By-Pass mode, Internal transfer
switch temperature is high and shutdown occurs.
Reduce load and check if any ventilation of the
unit is blocked.
E13
AC Output GFCI Tripped.
Reset the GFCI.
Note: This error function is not effective when Load Sense “LdS’ function is in use.
E14
Display panel has communication error.
Check RJ12 cable connected between the main
and Display panel.
E15
AC Back Feed to Unit AC Output.
Check AC Input and AC Output wiring.
E16
Internal Fault. Unit damage.
Consult Customer Service for assistance.
E17
AC Input Current withdrawn from the unit is close
to the set AC Circuit Breaker (Cbr) rating.
Reduce AC load. Check the AC Circuit Breaker
(Cbr) rating match with the external AC Input
Source Branch Breaker rating.
E18
AC Input Current drawn by unit is beyond the
current rating of the transfer switch. (30A for 120V
model, 16A for 230V model). AC Output Switch is
switched off.
Reduce AC Load connected to unit. Press and
hold ‘
Escape
’ button for 5 seconds to reset AC
Output Switch to provide AC Output from AC
Input Source.
E19
Battery temperature sensed by BTS is > 60°C.
Battery charging cycle terminates.
Cool down the battery. Battery charging cycle
will automatically resume when the temperature
drops to below 50 °C.
E20
Battery temperature sensed by BTS is > 55 °C and
is close to battery temperature thermal shutdown
Check battery and environmental temperature or
add ventilation to the battery compartment.
E21
Battery temperature sensed by BTS is < 0 °C.
Battery charging cycle terminates.
Check battery and environmental temperature.
The charging cycle will resume when temperature
increases to > 5 °C.