20      WhisperPower Inverter / Battery Charger

   

Absorption to 
Float Current

10

8

12V/3000W Models

: Selectable Range: 20A, 15A, 10A, 5A, 2A

(Default 10A)

.

12V/2000W Models

: Selectable Range: 15A, 10A, 8A, 4A, 2A 

(Default 8A)

.

Float Voltage

 13.8

Float voltage is based on the battery type chosen. All battery types have 
selectable ranges of 13.0 – 14.0V. 

(Default on GEL Battery is 13.8V

Recharge 
Voltage

12.8

Battery Recharge Voltage Selectable Range: 12.8 to 14.0V (0.1V step)* 

(Default on GEL, AGM, Flooded, PGM battery setting is 12.8V* and Li 
setting is 13.2V)

Battery 
Temperature 

: High > 35 °C

(Default)

: Normal 15 - 35°C 

: Low < 15°C

AC Input 
Circuit 
Breaker 

*

     30

30

Shore (AC in Display): Range: 16A, 20A, 30A (Default), 
Generator (AUX in Display): Range: 16A, 20A, 30A (Default)

Factory 
Default

Select 

to reset all settings to default.

* Circuit Breaker setting representation:  

SPW

 (Shore Power Wattage) for AC input power when no signal on Digital Input

GPW

 (Generator Power Wattage) for AUX input, when +12V on Digital Input

Understanding the Display Icons during Unit Operation

Icons

Meaning

Solid: Unit is running in Battery Charger mode and is charging the battery. Input current limit 
set under SPW is applicable when on generator, symbol changes to AUX solid, and current 
limit set under GPW is applicable.

Solid: Unit is running in By-Pass mode. (The transfer switch is switched to AC Input Source).

-  AC Output power is running from AC Input Source.
-  AC Output is available at both the AC Output socket and the AC Output Hardwire terminal 

if AC Output switch is turned On (indicated by AC Output indicator located on the left side 
of the Display and also the Main unit being On). 

Note: Press and hold the ‘

Escape

’ button on the Display panel for 5 seconds to toggle AC 

Output switch On/Off .

Solid: AC Input is available and is in the operating range.

Flashing: AC Input is detected and is under verifi cation before switching to By-Pass mode. 

This normally takes about 10 seconds.

Solid: Unit is running in Battery Mode (The transfer switch is switched to Inverter)

-  AC Output power is running from the inverter
-  AC Output is available at both the AC Output socket and the AC Output Hardwire terminal 

if AC Output switch is turned On (indicated by AC Output indicator located on the left side 
of the Display and also the Main unit being On). 

Note: Press and hold the ‘

Escape

’ button on the Display panel for 5 seconds to toggle AC 

Output switch On/Off . 

Содержание 12 VDC-2000 VA

Страница 1: ...12 VDC 3000 VA 12 VDC 2000 VA 120 VAC 60 Hz Enjoy Green Energy Inverter Charger Supreme Combi whisperpower com User Manual Inverter Charger ...

Страница 2: ...2 WhisperPower Inverter Battery Charger ...

Страница 3: ...WhisperPower Inverter Battery Charger 3 Inverter Charger 120V Series 12V 2000W 80A 61122085 12V 3000W 100A 61123006 User Manual Manual Edition 20210929 ...

Страница 4: ...r errors or omissions Note as well that specifications and product functionality may change without notice Important Please be sure to read and save the entire manual before using your Whisper Power Sinewave Inverter Charger Misuse may result in damage to the unit and or cause harm or serious injury Read manual in its entirety before using the unit and save manual for future reference Model Number...

Страница 5: ...eanse right away with soap and water for a minimum of 15 minutes and seek medical attention Batteries produce explosive gases DO NOT smoke or have an open spark or fire near the system Keep unit away from moist or damp areas Avoid dropping any metal tool or object on the battery Doing so could create a spark or short circuit which goes through the battery or another electrical tool that may create...

Страница 6: ...ce with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the follo...

Страница 7: ... Inverter Battery Charger 7 TABLE OF CONTENTS 1 INTRODUCTION 8 2 PRODUCT DESCRIPTION 8 3 UNDERSTANDING THE UNIT 9 4 INSTALLING THE UNIT 14 5 UNIT OPERATION 17 6 TROUBLESHOOTING 29 7 SPECIFICATIONS 30 8 WARRANTY 32 ...

Страница 8: ...s of batteries The built in transfer switch will automatically switch the load to the battery power when the utility power is interrupted This manual will explain how to use this unit safely and effectively Please read and follow these instructions and precautions carefully 2 PRODUCT DESCRIPTION The Sinewave Inverter Charger includes the items listed below Inverter Charger base unit Multi Function...

Страница 9: ...ure to follow these instructions can damage the unit and could also result in personal injury or loss of life CAUTION Before beginning unit installation please consider the following The unit should be used or stored in an indoor area away from direct sunlight heat moisture or conductive contaminants When placing the unit allow a minimum of three inches of space around it for optimal ventilation M...

Страница 10: ...wer to the loads based on Amps x hour energy consumption It is recommended to purchase as much battery capacity as possible AC Load Estimated run time on 12V Battery bank on 12V Input Models 12V 120AH 12V 240AH 50 W 22 hrs 44 hrs 100 W 11 5 hrs 23 hrs 200 W 5 hrs 11 hrs 500 W 2 hrs 4 hrs 1000 W 49 mins 2 hrs 1500 W 27 mins 1 hr 2000 W 15 mins 49 mins 2500 W N R 37 mins 3000 W N R 27 mins N R Not R...

Страница 11: ...ice when not in use or when troubleshooting It could also be an A B A B OFF type switch to select either one of the two or both paralleling battery banks if available D DC Input Cable All DC Input Wires should be insulated multi strand low resistance wires The DC wires must be copper and with minimum 105o rating Model Thinnest DC Input Wires Gauge Used 1 5 m 5 feet Recommended 2 25 m 7 5 feet 3 m ...

Страница 12: ...wer supply line Additional AC circuit breakers serve individual circuits and one of the AC circuit breakers will serve the unit During By Pass mode the AC Input source will serve the AC Output Load and also the AC Input current for the charger when it is used to charge the battery Model AC Input Circuit Breaker to serve the unit AC Input Wire 120VAC series 30A maximum 6 mm2 10 AWG minimum Follow t...

Страница 13: ...o the optional Battery Temperature Sensor The thermistor installed inside the ring terminal is used to measure the battery terminal temperature and the unit will make compensation on battery charging voltage for battery charging M Digital Input Port Program Port Can BUS Port Digital Input Port This port is used for connecting to a slave contact of an external Transfer Switch or Relay to control th...

Страница 14: ...nd the unit The more clearance for ventilation around the unit the better the performance Mounting the Unit Choose an appropriate mounting location The unit can be mounted in any direction Use the mounting template below to mark the positions of the mounting screws Drill the 4 mounting holes and place the unit in position and fasten the unit to the mounting surface mounting surface DC Input Connec...

Страница 15: ...he unit s Chassis DC Ground Lug located near the DC Input terminal and the other side of the cable to the common grounding point For a Recreation Vehicle the common ground point is usually the vehicle chassis or a dedicated DC ground bus For Marine the common ground point is usually the DC ground bus or engine negative bus Note Do not use the Chassis DC Ground Lug for your AC Grounding For AC Grou...

Страница 16: ...for more details Use the following procedure to install the BTS Connect the RJ12 end of the BTS cable to the BTS Port on the main unit Install the ring terminal end of the BTS cable to the negative terminal of the battery bank Digital Input Port Connection optional If an input power selection switch or relay is present the auxillary signalling contact may be used to provide a differently programme...

Страница 17: ...tlet Turns unit On and be sure the unit is running in Battery Power Mode Check Set the Load Sense LdS setting to off Press the RESET button until hearing a click to reset the GFCI socket Plug in the AC Loads and verify the AC Load is ON Note Be aware that a tripped GFCI outlet can only be Reset when there is a continuous AC Input supplying to the GFCI Socket 5 UNIT OPERATION The unit is preset wit...

Страница 18: ...1 sec Display turns off and the unit cannot be turned on again but after about 3 sec when hearing the deactivation of the internal relays Note When AC Input is available this Power button cannot be used to turn OFF the unit Menu Set button Press once to view unit setting on display See more details on Viewing and Change Unit Setting section and button The or button can be used to scroll through DC...

Страница 19: ...0 12 5V 0 1V step Default voltage is set to 11 0V Battery Low Recovery 12 0 Battery Low Recovery Voltage selectable ranges is 11 5 13 0V 0 1V step Default voltage is set to 12 0V Audible Buzzer Default Buzzer is enabled Unit buzzes when Warning or Error occurs Buzzer is disabled Unit does not buzz when Warning and Error occur AC Charger Default AC Charger is enabled Charge battery when AC Input is...

Страница 20: ...attery Charger mode and is charging the battery Input current limit set under SPW is applicable when on generator symbol changes to AUX solid and current limit set under GPW is applicable Solid Unit is running in By Pass mode The transfer switch is switched to AC Input Source AC Output power is running from AC Input Source AC Output is available at both the AC Output socket and the AC Output Hardw...

Страница 21: ... and the battery is 13 5V Second bottom bar flashing indicates the battery is in Bulk charging stage and the battery is 12 5V Bottom bar flashing indicates the battery is in Bulk charging stage and the battery is 11 5V No bar indicates the battery is in Bulk charging stage and the battery is 10 5V Battery icon flashing indicates the battery is in Bulk charging stage and the battery is below 10 5V ...

Страница 22: ... Inverter only b Load Sense Function Load Sense Mode This Load Sense function is only effective when the unit is running as inverter Battery power mode Off Unit provides continuous AC Output power all the time 10 Load Sense power setting is set to 10W Unit will provide continuous AC Output only when the AC load connected to the AC Output is 10W AC Output will switch back to pulsing AC Output every...

Страница 23: ... to be with a minimum of 0 5V above the Battery Low Disconnect BLd Voltage and has to be with a minimum of 0 5V below the Battery Low Recovery bLr Voltage Battery Under Voltage Recovery Selectable range 11 5 13 0V 0 1V step Default 12 0V The Battery Low Recovery Voltage has to be with a minimum of 0 5V above the Battery Low Alarm bLA Voltage Battery Over Voltage Disconnect 16 5 V Not User selectab...

Страница 24: ...bulk and float voltage for the battery bank When selecting the Float voltage it has to be with a minimum of 0 4V below Bulk Voltage setting The Recharged Voltage determines the restart cycle of the battery bank The charger will go through a full recharge cycle when the battery voltage drops to the Recharge Voltage set value When selecting the Recharge Voltage it has to be with a minimum of 0 4 bel...

Страница 25: ...on AGM battery type Setting to Nor will have no change to the selected charging voltage Setting to HI temperature will compensate the charging voltage by 0 27V on GEL and Flooded battery type and 0 21V on AGM battery type Optional Battery Temperature Sensor BTS Installed If the temperature measured by the BTS is below 25 C the charging voltage will be compensated with 0 027V per C on GEL and Flood...

Страница 26: ...put power demand exceeds the current limit set for the circuit breaker on the input source to prevent this external breaker from tripping Independent current limiting settings can be programmed for normal shore AC input and for generator The limiting value for Generator input may be programmed and applied GPW by activating the Digital Input port with 12V signal In Generator mode with detected AC v...

Страница 27: ...n unit is in Battery Inverter mode unit senses the battery voltage is too high and inverter has shutdown Check battery voltage or determine if any external charger is connected to the battery bank that leads to high battery voltage E03 When unit is in Battery Inverter mode AC output is overloaded or short circuited and inverter has shutdown Check load connected to the output Reduce load and restar...

Страница 28: ... between the main and Display panel E15 AC Back Feed to Unit AC Output Check AC Input and AC Output wiring E16 Internal Fault Unit damage Consult Customer Service for assistance E17 AC Input Current withdrawn from the unit is close to the set AC Circuit Breaker Cbr rating Reduce AC load Check the AC Circuit Breaker Cbr rating match with the external AC Input Source Branch Breaker rating E18 AC Inp...

Страница 29: ...d DC over voltage under voltage or other shutdown type errors in addition to overload Check battery voltage For 120V model GFCI may have tripped Reset GFCI Charger did not supply charging current Check charger setting Charger may be set to Off Set Charger function CHG to On Unit had determined the battery is bad See also description in Error Code E01 By Pass Mode and E11 Check battery and remove t...

Страница 30: ...r Mode 3 0 ADC DC Input Voltage operating range 10 5 16 5 VDC Under Voltage Alarm 11 0 12 5 VDC Under Voltage Alarm Recovery 11 5 13 0 VDC Under Voltage Shutdown 10 5 12 0 VDC Under Voltage Recovery 11 5 13 0 VDC Over Voltage Shutdown Recovery 16 5 16 0 VDC AC Transfer Switch Transfer Time 30 ms Transfer Relay Rating 30A AC Input Source Setting 15 20 30A AC Output Hardwire max 30A AC Output Socket...

Страница 31: ...r Factor Correction 95 Efficiency 80 Safety and Environmental Conformance UL 458 CSA C22 2 No 107 2 01 EMI EMC FCC Part 15 Class B Agency Markings cETLus Operating Temperature 0 C to 40 C 32 F to 104 F Storage Temperature 20 C to 60 C 4 F to 140 F Relative Humidity 5 90 non condensing Operating Altitude Up to 9 843ft 3000m above sea level Weights and Dimensions Weights 2000W Series 8 0 kg 17 6 lbs...

Страница 32: ...efer to the Whisper Power general conditions of sales 8 1 Exclusion of warranty No warranty claims will be accepted for damage resulting from handling usage or processing that does not explicitly appear in this manual Cases of damage arising from the following causes are notably excluded from the warranty Surge voltage on the battery input for example 48 V on the battery input of an WP INVERTER CH...

Страница 33: ...fore returning product to retail store After speaking to a customer service representative if products are deemed non working or malfunctioning the product may be returned to the purchasing store within 30 days of orig inal purchase Any defective unit that is returned to manufacturer within 30 days of the date of purchase will be replaced free of charge If such a unit is returned more than 30 days...

Страница 34: ...34 WhisperPower Inverter Battery Charger ...

Страница 35: ...WhisperPower Inverter Battery Charger 35 ...

Страница 36: ...Enjoy Green Energy WhisperPower BV Kelvinlaan 82 9207 JB Drachten The Netherlands www whisperpower com sales whisperpower com ...

Отзывы: