 Evaporator Coil Drain Pan Clearances

If the plenum ductwork is larger than the drain pan in any 
direction, the gaps between the drain pan and the plenum 
walls must be closed off to avoid bypass of air around the 
sides of the drain pan. Use field-fabricated sheet metal 
angles wide enough to support the coil where the drain pan is 
located and attach them to the inside of the plenum. The 
drain pan will rest on the metal angles. If the connection 
between the plenum and any duct occurs below the apex of 
the coil, seal this seam with sealant.

Install Condensate Drains

Plastic Drain Pan 

The drain pan has a primary and an optional secondary drain with 

³⁄₄

" NPT female connections. The connectors required can be 

³⁄₄

NPT male PVC or metal pipe and should be hand tightened to a 
torque of approximately 37 in/lbs to avoid damage to the drain 
pan connection. An insertion depth between 0.355" to 0.485" 
(0.9 cm to 1.2 cm) (3 to 5 turns) should be expected at this 
torque. If the secondary drain line is required, it must be run 
separately from the primary drain and should end where it is 
easily seen. Water coming from this line means the coil primary 
drain is plugged and needs clearing.

A trap must be installed in the drain line below the bottom of the 
drain pan. If a copper drain line is used, solder a short piece of 
pipe to the connector before installing a drain fitting. 

NOTE: Do not over-torque the 

³⁄₄

" copper connector to the plastic 

drain connection. 

When completing the drain line, use a wet rag or heat sink 
material on the short piece of pipe to avoid damage to the plastic 
drain pan.

Typical drain pipe routings to avoid interference with vent piping 
are shown in the “Typical Drain Pipe Routing” illustration.

Typical Drain Pipe Routing

Verify Orifice Size

IMPORTANT: The proper orifice size is dependent on indoor coil/
outdoor unit combination and application. Consult the outdoor 
unit information to determine if the indoor unit has the correct 
orifice installed.

Connect Refrigerant Lines

Refrigerant lines must be connected by a licensed, EPA certified 
refrigerant technician in accordance with established procedures.

IMPORTANT:

Connecting refrigerant lines must be clean, dehydrated, 
refrigerant-grade copper lines. 

Evaporator coils should be installed only with specified line 
sizes for approved system combinations.

Handle the refrigerant lines gently during the installation 
process. Sharp bends or possible kinking in the lines will 
cause a restriction.

A. Coil pan width plus insulation 

thickness times 2

B. Bottom flange detail—can be 

either

C. Gas furnace

D. Field fabricated support for 

uncased coil

E. 2" (5.1 cm) from top of furnace to 

bottom of coil pan. Must be 6" 
(15.2 cm) for oil furnaces.

F. Coil support 

 

A

B

B

D

C

F

E

Do not use the coil pan that shipped with the unit on 
an OIL furnace or any application where the temperature 
of the drain pan may exceed 300ºF (149ºC). A high 
temperature drain pan (Kit Numbers HTP-A, -B, -C and 
-D for nominal widths of 14", 17

¹⁄₂

", 21" and 24

¹⁄₂

" [35.6, 

44.5, 53.3 and 62.2 cm] respectively) should be used for 
this type of application. A field fabricated metal drain 
pan can also be used.

WARNING

A. Air handler
B. Drain connection

C. Positive liquid seal required at trap

A. Secondary drain pipe routing
B. Primary drain pipe routing

3" (7.6 cm)

Minimum

2" (5.1 cm) Minimum

A

C

B

A

80.0%

B

92.6%

A

B

92.6%

B

A

Содержание WCC

Страница 1: ...s type of equipment should be determined prior to installation Read this entire instruction manual as well as the instructions supplied in separate equipment before starting the installation All models are designed for indoor installation only Install the conditioned air plenum ducts and air filters not provided in accordance with NFPA 90B Standard for the Installation of Warm Air Heating and Air ...

Страница 2: ...d left front drain connections when installed in the horizontal position Minimum copper or PVC drain lines are recommended NOTE Check local codes before connecting drain lines to an existing drainage system A field fabricated auxiliary drain pan with a drainpipe to the outside of the building is required in all installations over a finished living space or in any area that may be damaged by overfl...

Страница 3: ...o the plastic drain pan Typical drain pipe routings to avoid interference with vent piping are shown in the Typical Drain Pipe Routing illustration Typical Drain Pipe Routing VerifyOrificeSize IMPORTANT The proper orifice size is dependent on indoor coil outdoor unit combination and application Consult the outdoor unit information to determine if the indoor unit has the correct orifice installed C...

Страница 4: ...tailpiece has cooled verify the position of the white Teflon seal and hand tighten the nut 12 Torque the nut to 20 to 30 ft lbs 2 77 to 4 15 m kg 13 Replace the suction line grommet and insulation ASSISTANCE OR SERVICE If you need further assistance you can write to the below address with any questions or concerns Whirlpool Home Cooling and Heating 14610 Breakers Drive Jacksonville FL 32258 Please...

Отзывы: