2

Tools and Parts

Gather the required tools and parts before starting installation. 
Read and follow the instructions provided with any tools listed 
here.

Tools Needed

Parts Needed

Check local codes. Check the existing drain configuration before 
purchasing parts.

Parts Supplied

System Requirements

IMPORTANT:

The blower and duct system must be properly sized in order 
to provide adequate cooling and heating performance. For 
proper cooling operation, the airflow through the indoor coil 
should be 350 to 450 CFM per ton of cooling capacity (or 
350 to 450 CFM per 12,000 Btu/h) based on the rating of the 
outdoor unit.

All air passing over the evaporator coil must be filtered. 

Evaporator coils are matched to specific outdoor units to 
obtain an ARI rating. The orifice installed on each evaporator 
coil is chosen for the Btu/h capacity of the coil. The factory-
installed orifice size is stamped on the orifice body, and is 
identified with a label on the orifice extension stub. The orifice 
size must match the size called for on the refrigerant charging 
table found on the outdoor unit. A selection of replacement 
orifices is available from the distributor.

Location Requirements

When the evaporator coil is installed in an attic, above a finished 
ceiling, or in any location where condensate overflow would 
result in property damage, the installer must provide an auxiliary 
drain pan in addition to the primary and secondary drains. The 
auxiliary drain pan must be connected to a drainage system 
separate from the primary condensate drain.

Drain Requirements

All vertical mount models come from the factory with right 
and left front drain connections.

Multiposition models come from the factory with right and left 
front drain connections for vertical installations and left front 
drain connections when installed in the horizontal position.

Minimum ¾" copper or PVC drain lines are recommended.

NOTE: Check local codes before connecting drain lines to an 
existing drainage system.

A field-fabricated auxiliary drain pan, with a drainpipe to the 
outside of the building, is required in all installations over a 
finished living space or in any area that may be damaged by 
overflow from the main drain pan. In some localities, local 
codes may require an auxiliary drain pan for any horizontal 
installation.

INSTALLATION INSTRUCTIONS

Inspect Shipment

Check the evaporator coil rating plate to confirm 
specifications are as ordered.

Upon receipt of equipment, inspect it for possible shipping 
damage. Examine the evaporator coil inside the carton if the 
carton is damaged.

If damage is found, it should be noted on the carrier’s freight 
bill. Damage claims should be filed with the carrier 
immediately. Claims of shortages should be filed with the 
seller within 5 days.

NOTE: If any damages are discovered and reported to the carrier, 
do not install the evaporator coil, because your claim may be 
denied.

Install Upflow/Downflow Evaporator Coil 

IMPORTANT:

The evaporator coil must be installed in the discharge 
(supply) air of a gas unit. 

NOTE: Do not install an evaporator coil in the return air, or 
excessive condensation will occur within the unit.

Install the evaporator coil level with the drain connection to 
ensure proper drainage.

To avoid damage to the plastic drain pan, minimum spacing 
is required between the drain pan and a unit heat exchanger. 
A minimum spacing of 2" (5.1 cm) is required for a gas unit. 
See “Evaporator Coil Drain Pan Clearances.”

Torch

Tape measure

Flat-blade screwdriver

¹⁄₄

" nut driver

¹³⁄₁₆

" open end wrench

Level

Field-fabricated auxiliary drain pan (in some installations)

Evaporator coil may be provided as a separate coil or 
mounted in a duct extension.

If secondary drain is not installed, the secondary access 
must be plugged.

CAUTION

Содержание WCC

Страница 1: ...s type of equipment should be determined prior to installation Read this entire instruction manual as well as the instructions supplied in separate equipment before starting the installation All models are designed for indoor installation only Install the conditioned air plenum ducts and air filters not provided in accordance with NFPA 90B Standard for the Installation of Warm Air Heating and Air ...

Страница 2: ...d left front drain connections when installed in the horizontal position Minimum copper or PVC drain lines are recommended NOTE Check local codes before connecting drain lines to an existing drainage system A field fabricated auxiliary drain pan with a drainpipe to the outside of the building is required in all installations over a finished living space or in any area that may be damaged by overfl...

Страница 3: ...o the plastic drain pan Typical drain pipe routings to avoid interference with vent piping are shown in the Typical Drain Pipe Routing illustration Typical Drain Pipe Routing VerifyOrificeSize IMPORTANT The proper orifice size is dependent on indoor coil outdoor unit combination and application Consult the outdoor unit information to determine if the indoor unit has the correct orifice installed C...

Страница 4: ...tailpiece has cooled verify the position of the white Teflon seal and hand tighten the nut 12 Torque the nut to 20 to 30 ft lbs 2 77 to 4 15 m kg 13 Replace the suction line grommet and insulation ASSISTANCE OR SERVICE If you need further assistance you can write to the below address with any questions or concerns Whirlpool Home Cooling and Heating 14610 Breakers Drive Jacksonville FL 32258 Please...

Отзывы: