Calculating Vent System Length

To calculate the length of the system you need, add the 

equivalent feet (meters) for each vent piece used in the system.

Vent System

Vent Piece

45° elbow

2.5 ft (0.8 m)

90° elbow

5 ft (1.5 m)

     

3

1

/

4

" x 10" 

(8.3 cm x 25.4 cm) 

flat elbow

12 ft (3.7 m)

7" (17.8 cm) 

wall cap

0 ft (0.0 m)

   

3

1

/

4

" x 10" 

(8.3 cm x 25.4 cm) 

to 7" (17.8 cm)

4.5 ft (1.4 m)

3

1

/

4

" x 10" 

(8.3 cm x 25.4 cm) 

to 7" (17.8 cm) 

90° elbow

5 ft (1.5 m)

Example vent system

1 - 90° elbow

= 5 ft (1.5 m)

1 - wall cap

= 0 ft (0.0 m)

8 ft (2.4 m) straight

= 8 ft (2.4 m)

System length

= 13 ft (3.9 m)

Maximum Recommended Length

7" (17.8 cm) Round Vent

= 50 ft (15.2 m)

3

1

/

4

" x 10" (8.3 x 25.4 cm) 

Rectangular Vent

= 35 ft (10.7 m)

Electrical Requirements

Observe all governing codes and ordinances.
Ensure that the electrical installation is adequate and in 

conformance with National Electrical Code, ANSI/NFPA 

70 (latest edition), or CSA Standards C22.1-94, Canadian 

Electrical Code, Part 1 and C22.2 No. 0-M91 (latest edition), 

and all local codes and ordinances.
If codes permit and a separate ground wire is used, it is 

recommended that a qualified electrician determine that 

the ground path is adequate.
A copy of the above code standards can be obtained from:

National Fire Protection Association 

1 Batterymarch Park 

Quincy, MA 02169-7471

CSA International 

8501 East Pleasant Valley Road 

Cleveland, OH 44131-5575

 

A 120 volt, 60 Hz., AC only, 15-amp, fused electrical 

circuit is required.

 

If the house has aluminum wiring, follow the procedure 

below:

1. 

Connect a section of solid copper wire to the 

pigtail leads.

2. 

Connect the aluminum wiring to the added section 

of copper wire using special connectors and/or tools 

designed and UL listed for joining copper to aluminum.

Follow the electrical connector manufacturer’s recommended 

procedure. Aluminum/copper connection must conform 

with local codes and industry accepted wiring practices.

 

Wire sizes and connections must conform with the rating 

of the appliance as specified on the model/serial/rating 

plate. The model/serial/rating plate is located inside the 

range hood on the left wall.

 

Wire sizes must conform to the requirements of the National 

Electrical Code, ANSI/NFPA 70 (latest edition) or CSA 

Standards C22. 1-94, Canadian Electrical Code, Part 1 

and C22.2 No. 0-M91 (latest edition) and all local codes 

and ordinances.

Wall cap

 

 

 

 

90˚ elbow

2 ft (0.6 m)

6 ft (1.8 m)

Содержание UXT5230BFS

Страница 1: ...irlpool ca HOTTE D ASPIRATION DE 30 76 2 CM Instructions d installation et Guide d utilisation et d entretien Au Canada pour assistance installation ou service composer le 1 800 807 6777 ou visiter notre site Web à www whirlpool ca Table of Contents Table des matières 2 Model Modèle UXT5230BF IMPORTANT READ AND SAVE THESE INSTRUCTIONS FOR RESIDENTIAL USE ONLY IMPORTANT LIRE ET CONSERVER CES INSTRU...

Страница 2: ...ll safety messages will follow the safety alert symbol and either the word DANGER or WARNING These words mean follow instructions instructions DANGER WARNING RANGE HOOD SAFETY 2 INSTALLATION REQUIREMENTS 4 Tools and Parts 4 Location Requirements 4 Venting System 5 Electrical Requirements 6 INSTALLATION INSTRUCTIONS 7 RANGE HOOD USE 11 Range Hood Controls 11 RANGE HOOD CARE 11 Cleaning 11 WIRING DI...

Страница 3: ...ains one or more chemicals known to the State of California to cause cancer WARNING This product contains one or more chemicals known to the State of California to cause birth defects or other reproductive harm IMPORTANT SAFETY INSTRUCTIONS READ AND SAVE THESE INSTRUCTIONS ...

Страница 4: ...ange hoods are factory set for vented installations Models that are capable of being installed as non vented recirculating require charcoal filters See the Assistance or Service section for information on ordering charcoal filters For Mobile Home Installations The installation of this range hood must conform to the Manufactured Home Construction Safety Standards Title 24 CFR Part 328 formerly the ...

Страница 5: ...akeup air systems when using ventilation systems greater than specified CFM of air movement The specified CFM varies from locale to locale Consult your HVAC professional for specific requirements in your area Venting Requirements Vent system must terminate to the outdoors except for non vented recirculating installations Do not terminate the vent system in an attic or other enclosed area Do not us...

Страница 6: ...fied electrician determine that the ground path is adequate A copy of the above code standards can be obtained from National Fire Protection Association 1 Batterymarch Park Quincy MA 02169 7471 CSA International 8501 East Pleasant Valley Road Cleveland OH 44131 5575 A 120 volt 60 Hz AC only 15 amp fused electrical circuit is required If the house has aluminum wiring follow the procedure below 1 Co...

Страница 7: ...l mark the upper holes on the brackets 3 Install Brackets Using a 2 Phillips screwdriver install the drywall anchors Using 8 18 x 1 4 2 x 25 mm flat head 2 Phillips screws install the mounting brackets using the upper holes NOTE For installations to a surface other than drywall it is recommended that a qualified contractor determine the anchoring method 4 Prepare Range Hood Set the range hood on i...

Страница 8: ...13 mm drill bit drill a hole in each of the dots marked previously on either the wall or upper cabinet Using the outside edges of the holes mark the vent opening Using a jigsaw or keyhole saw cut the vent opening 7 17 8 cm Round Vent System Using the 7 17 8 cm round vent mounting plate draw the vent opening outline on the underside of the cabinet Place the vent mounting plate on the bottom of the ...

Страница 9: ... rectangular vent knockout C OR For wall vent installations remove the rear rectangular vent knockout B 7 17 8 cm Round Vent Installations Remove both top knockouts C and D 9 Attach Vent Damper or Transition 31 4 x 10 8 3 x 25 4 cm Rectangular Vent Damper Using 2 short Phillips head screws install the 31 4 x 10 8 3 x 25 4 cm rectangular damper over the top or rear vent knockout removed in Step 8 N...

Страница 10: ...A together Use a UL listed CSA approved wire connector and connect the 2 black wires B together Connect the green or bare ground wire C from the power supply to the green ground screw in the electrical box and tighten the screw securely Reinstall the electrical box cover Reconnect power Option 2 Power Cord Kit Installations For optional power cord kit installations follow the instructions supplied...

Страница 11: ...stainless steel do not use cleaners that contain chlorine Cleaning Method Liquid detergent or all purpose cleaner Rinse with clean water and dry with a soft lint free cloth Glass cleaner to remove fingerprints For stainless steel models rub in the direction of the grain to avoid scratching or damaging the surface For stainless steel models use Stainless Steel Cleaner and Polish Part Number 31462A ...

Страница 12: ...ed 3 BR RD Common LED Driver Output 700mA 2 15 VDC Input 120 VAC Motor Resistance GY Speed 2 Wattage Rating 110 W WH Speed 1 BR YL 1 6 5 4 3 2 M S15 RD BK BU LED LED BK WH BR Speed 1 RD Speed 2 GY Speed 3 YL Lamp BK Line 8 uF 4 1 L 2 3 For supply connection use wires suitable for at least 167 F 75 C Switch Operation L 1 Lamps 120 V 1 5 Ohms L 2 Speed 1 120 V 1 5 Ohms L 3 Speed 2 120 V 2 0 Ohms L 4...

Страница 13: ...tomer assistance Spanish speaking hearing impaired limited vision etc For further assistance If you need further assistance you can write to Whirlpool Corporation with any questions or concerns at Whirlpool Brand Home Appliances Customer eXperience Center 553 Benson Road Benton Harbor MI 49022 2692 Please include a daytime phone number in your correspondence In Canada Call the Whirlpool Canada LP ...

Страница 14: ...utions etc 5 Defects or damage caused by the use of non genuine Whirlpool parts or accessories 6 Conversion of products from natural gas or L P gas 7 Damage from accident misuse abuse fire floods acts of God or use with products not approved by Whirlpool 8 Repairs to parts or systems to correct product damage or defects caused by unauthorized service alteration or modification of the appliance 9 C...

Страница 15: ...areil ménager Assurez vous de toujours lire tous les messages de sécurité et de vous y conformer AVERTISSEMENT DANGER Voici le symbole d alerte de sécurité Ce symbole d alerte de sécurité vous signale les dangers potentiels de décès et de blessures graves à vous et à d autres Tous les messages de sécurité suivront le symbole d alerte de sécurité et le mot DANGER ou AVERTISSEMENT Ces mots signifien...

Страница 16: ...e et évacuer adéquatement les gaz veiller à acheminer l air aspiré par un conduit jusqu à l extérieur ne pas décharger l air aspiré dans un espace vide du bâtiment comme une cavité murale un plafond un grenier un vide sanitaire ou un garage AVERTISSEMENT POUR RÉDUIRE LE RISQUE D INCENDIE UTILISER UNIQUEMENT DES CONDUITS MÉTALLIQUES AVERTISSEMENT POUR MINIMISER LE RISQUE D UN FEU DE GRAISSE SUR LA ...

Страница 17: ...00 BTU Une prise de courant électrique reliée à la terre est nécessaire Voir la section Spécifications électriques Assurer l étanchéité au niveau de chaque ouverture découpée dans le plafond ou le mur pour l installation de la hotte de cuisinière Ces hottes de cuisinière ont été configurées à l usine pour une installation avec décharge à l extérieur Les modèles pouvant être installés dans une conf...

Страница 18: ...mur ou le toit à acheter séparément B Bouche de décharge à travers le mur avec clapet à acheter séparément Installations dans les régions au climat froid On doit installer un clapet anti retour supplémentaire à l arrière pour minimiser le reflux d air froid et incorporer un élément d isolation thermique pour minimiser la conduction de chaleur par l intermédiaire du conduit d évacuation de l intéri...

Страница 19: ...it d évacuation rectangulaire de 31 4 x 10 8 3 x 25 4 cm 35 pi 10 7 m Spécifications électriques Observer les dispositions de tous les codes et règlements en vigueur S assurer que l installation électrique est correcte et qu elle satisfait aux exigences de la plus récente édition de la norme National Electrical Code ANSI NFPA 70 ou de la norme CSA C22 1 94 Code canadien de l électricité partie 1 e...

Страница 20: ... À l aide d un tournevis Phillips n 2 installer les chevilles d ancrage À l aide des vis à tête plate n 8 18 x 1 4 2 x 25 mm Phillips n 2 installer les brides de montage en utilisant les trous supérieurs REMARQUE Pour les installations sur une surface autre qu un panneau de gypse il est recommandé de faire appel à du personnel qualifié pour déterminer la méthode d ancrage 4 Préparation de la hotte...

Страница 21: ... 2 13 mm percer un trou à chaque marque effectuée précédemment sur la paroi ou le placard supérieur En utilisant les extrémités externes des trous marquer l ouverture de l évacuation Utiliser une scie sauteuse ou une scie à guichet pour découper l ouverture d évacuation Circuit d évacuation pour conduit circulaire de 7 17 8 cm À l aide de la plaque de montage de conduit circulaire de 7 17 8 cm mar...

Страница 22: ...cule amovible rectangulaire arrière du conduit d évacuation B Installations pour système d évacuation circulaires de 7 17 8 cm Retirer les deux opercules supérieurs C et D 9 Fixation du clapet anti reflux ou du raccord de transition d évacuation Clapet anti flux pour conduit rectangulaire de 31 4 x 10 8 3 x 25 4 cm À l aide de 2 vis courtes à tête Phillips installer le clapet anti reflux rectangul...

Страница 23: ...hotte et de les fixer à la paroi à l aide de vis à tête bombée n 8 18 x 5 8 4 2 x 16 mm 11 Raccordement du circuit d évacuation Raccorder le circuit d évacuation à la hotte Assurer l étanchéité des jointures avec des brides de conduit ou du ruban adhésif pour conduit Vérifier que les clapets anti reflux fonctionnent correctement 12 Raccordement électrique Option 1 Installations avec raccordement p...

Страница 24: ...la section Utilisation de la hotte Si la hotte ne fonctionne pas vérifier que le coupe circuit ne s est pas déclenché et qu aucun fusible n est grillé Déconnecter la source de courant électrique et inspecter les connections du câblage REMARQUE Pour pouvoir tirer le plus grand parti de la nouvelle hotte de cuisinière lire la section Utilisation de la hotte UTILISATION DE LA HOTTE La hotte de cuisin...

Страница 25: ...n 2 retirer la vis de la patte de retenue du filtre 2 Pour retirer le filtre tirer le loquet du filtre vers l avant de la hotte et tirer le rebord avant du filtre vers le bas 3 Installations avec évacuation à l extérieur Laver le filtre métallique si nécessaire au lave vaisselle ou dans une solution de détergent chaude Pour les installations sans évacuation à l extérieur recyclage Remplacer le fil...

Страница 26: ...mun Pilote DEL Sortie 700mA 2 15 VDC Entrée 120 VAC Résistance du moteur GRIS Vitesse 2 Puissance nominale 110 W BL Vitesse 1 MAR JA 1 6 5 4 3 2 M S15 R N BU DEL DEL N BL MAR Vitesse 1 R Vitesse 2 GRIS Vitesse 3 JA Lampe N Ligne 8 uF 4 1 L 2 3 Pour approvisionner la connection utilisez des cables appropiés pour au moins 167 F 75 C Fonctionnement du commutateur L 1 Lampes 120 V 1 5 Ohms L 2 Vitesse...

Страница 27: ...te Whirlpool Brand Home Appliances Centre pour l eXpérience de la clientèle Whirlpool Canada 200 6750 Century Ave Mississauga Ontario L5N 0B7 Veuillez inclure dans votre correspondance un numéro de téléphone où l on peut vous joindre dans la journée SI VOUS AVEZ BESOIN DE SERVICE 1 Avant de nous contacter pour obtenir un dépannage veuillez déterminer si des réparations sont nécessaires pour votre ...

Страница 28: ...SENTE Le service doit être fourni par une compagnie de service désignée par Whirlpool Cette garantie limitée est valide uniquement aux États Unis ou au Canada et s applique exclusivement lorsque le gros appareil ménager est utilisé dans le pays où il a été acheté La présente garantie limitée est valable à compter de la date d achat initial par le consommateur Une preuve de la date d achat initial ...

Отзывы: