Installation and Care of Sealed Lead Acid Batteries
Sealed lead acid batteries are designed to operate in standby service for approximately five years. This is based upon a normal
service condition where there is an ambient of 20 degrees C (68 degrees F) and batteries are completely discharged once every
three months. LENGTH OF SERVICE LIFE WILL BE DIRECTLY EFFECTED BY THE NUMBER OF DISCHARGE CYCLES,
DEPTH OF DISCHARGE, AND AMBIENT TEMPERATURE.
Use Guidelines:
1. Avoid installation and/or operation in close proximity to heat sources. While the operating temperature range is 0 to 49
degrees C (32-120 degrees F), battery life will be maximized at an ambient of 20 degrees C (68 degrees F).
2. Batteries may generate ignitable gases. Because of this, batteries shall be installed in a well ventilated location, away from
spark producing equipment.
3. Batteries shall not be installed in an atmosphere where organic solvents or adhesives may be present. The batteries shall not
be cleaned with oils, thinners, or similar substances. The case and cover of the batteries are ABS plastic resin which may
suffer damage from these chemicals.
4.
Batteries shall not be installed in a heavy vibration or shock location.
5.
Batteries shall have a 1/4” minimum separation between cells.
6.
Insulated gloves shall always be worn when handling batteries.
7. Batteries shall not be crushed, incinerated, or dismantled. The electrolyte contains sulfuric acid which can cause serious
damage to eyes and skin. If contact does occur, flush with water and seek immediate medical attention.
8.
Batteries of different capacities, age, or manufacturer shall not be used together.
Battery Storage
Batteries which are to be stored for an extended period of time should be given a supplementary charge monthly. Batteries should
never be stored in a discharged condition.
The self-discharge rate of batteries is approximately 3% per month when the storage temperature is maintained at 20 degrees C (68
degrees F). The self-discharge rate will vary depending upon temperature. Cooler temperatures cause the self-discharge rate to
decrease. Warmer temperatures cause the self-discharge rate to increase.
Содержание SAFEPATH RSAPE-B
Страница 11: ...Remote SAFEPATH Manual Sheet 11 of 50 Rev C December 1998 Figure 2 Operator s Console ...
Страница 16: ...Remote SAFEPATH Manual Sheet 16 of 50 Rev C December 1998 Figure 3 Panel Mounting ...
Страница 20: ...Remote SAFEPATH Manual Sheet 20 of 50 Rev C December 1998 Figure 4 Typical System Block Diagram ...
Страница 24: ...Remote SAFEPATH Manual Sheet 24 of 50 Rev C December 1998 Figure 11 Output Terminal Block Detail ...
Страница 33: ...Remote SAFEPATH Manual Sheet 33 of 50 Rev C December 1998 Figure 21 Trouble Location Indicator Locations ...
Страница 40: ...Remote SAFEPATH Manual Sheet 40 of 50 Rev C December 1998 Figure 22 Module Layout of the Panel ...
Страница 41: ...Remote SAFEPATH Manual Sheet 41 of 50 Rev C December 1998 Figure 23 Panel Block Diagram ...