Remote
SAFEPATH
Manual Sheet
13
of
50
Rev. C December 1998
Note 3:
If no amplifier is installed in the slot then the current for that amplifier is zero. If there is an amplifier the alarm current
depends on the model of the amplifier installed in the slot and the signal used for evacuation.
Model Alarm Current full power SIN wave as per UL testing
SALL-15S Series The sum of the currents of the self amplified speakers.
SAA-10S/SE
Series
(total
wattage
of connected speakers) x 69 + 240mA
SAA-40S/SE
Series
(total
wattage
of connected speakers) x 55 + 400mA
SAA-80S/SE
Series
(total
wattage
of connected speakers) x 56 + 600mA
Alarm Current for: Temporal Worst case
CODE-3
tone
Typical Voice TONE HI/LO
SAA10S/SE
Series 250mA 350mA 750mA
SAA40S/SE
Series 600mA 750mA 1600mA
SAA80S/SE
Series 1000mA
1050mA
2500mA
Note 4:
Use the rated current for the optional trouble audible attached to the system.
Note 5:
If no strobes are installed in the zone the current is zero. If strobes are installed, the current is the sum of the current ratings
of all the strobes attached to the zone.
Battery Capacity Calculations:
The battery capacity depends on two factors; the current being drawn from the battery and the amount of time that the current is
being drawn. The battery capacity is measured in amp hours. The total amp hours of batteries needed is (the standby current) x
(time in standby) + (the alarm current) x (time in alarm).
Sample Calculation:
The system is equipped with an RMS-1, a remote trouble audible that is rated for 100mA, and three amplifiers. The first amplifier is
an SAA-10S Series with 10 watts of speakers attached and 1 amp of strobes attached. The second amplifier is an SAA-80S Series
with 60 watts of speakers attached and 2 amps of strobes attached. The third amplifier is an SALL-15S Series with 10, 100mA self
amplified speakers attached and no strobes attached. The system is designed for 24 hours of standby and 15 minutes of alarm.
Standby Calculations:
System Controller Board 150mA
Amplifier
1
125mA
Amplifier
2
300mA
Amplifier
3
100mA
Amplifier
4
0mA
Optional
RMS-1
40mA
Optional Trouble Audible 100mA
_______
Total:
815mA
=
.815
amps
Alarm Current Calculations:
System Controller Board 150mA
Amplifier
1
350mA
Amplifier
2
1050mA
Amplifier
3
1000mA
Amplifier 4 None 0mA
Optional
RMS-1
750mA
Optional Trouble Audible 100mA
Zone
1
Strobes 1000mA
Zone
2
Strobes 2000mA
Zone 3 Strobes 0mA
Zone 4 Strobes 0mA
________
Total:
5725mA
=
5.725
amps
Battery Capacity Calculations:
24 hours x .815 amps + 1/12 hour (5 minutes) x5.725 amps = 20.04 amp hours minimum capacity. Any de-rating factor must also
be included.
Содержание SAFEPATH RSAPE-B
Страница 11: ...Remote SAFEPATH Manual Sheet 11 of 50 Rev C December 1998 Figure 2 Operator s Console ...
Страница 16: ...Remote SAFEPATH Manual Sheet 16 of 50 Rev C December 1998 Figure 3 Panel Mounting ...
Страница 20: ...Remote SAFEPATH Manual Sheet 20 of 50 Rev C December 1998 Figure 4 Typical System Block Diagram ...
Страница 24: ...Remote SAFEPATH Manual Sheet 24 of 50 Rev C December 1998 Figure 11 Output Terminal Block Detail ...
Страница 33: ...Remote SAFEPATH Manual Sheet 33 of 50 Rev C December 1998 Figure 21 Trouble Location Indicator Locations ...
Страница 40: ...Remote SAFEPATH Manual Sheet 40 of 50 Rev C December 1998 Figure 22 Module Layout of the Panel ...
Страница 41: ...Remote SAFEPATH Manual Sheet 41 of 50 Rev C December 1998 Figure 23 Panel Block Diagram ...