Remote
SAFEPATH
Manual Sheet
10
of
50
Rev. C December 1998
Operator Instructions
The SAFEPATH panel provides an operator console for manually activating the panel. The operator console includes a
microphone, a green “NORMAL” indicator, a yellow “TROUBLE” indicator, an “ACKNOWLEDGE” push-button switch, a “RESET”
push-button, a “MANUAL/AUTOMATIC” switch, an “ALL-CALL” switch and four “ZONE SELECT” switches. The operator interface
allows the operator to manually override automatically playing pre-recorded messages with live announcements or an evacuation
tone, to silence internal and external trouble audibles, and to ascertain if the panel has detected a trouble condition. The operator
interface is shown in Figure 3.
The “TROUBLE” and “NORMAL” indicators are visible through a window on the panel door, when door is closed. All other operator
controls are only accessible by opening the panel door.
The “SELECT” LED’s indicate the zones selected for live announcements.
The ”ALARM” LED’s indicate the zones actively in alarm.
The two indicators identify to the operator when the SAFEPATH panel has detected a trouble condition. The yellow “TROUBLE”
indicator will be illuminated whenever there is a trouble detected by the SAFEPATH panel. If no troubles are detected, the green
“NORMAL” indicator will be illuminated.
The “ACKNOWLEDGE” push-button allows the operator to silence the trouble audibles, both internal and external. When a trouble
condition is detected, both the internal and external trouble audibles are sounded. When the “ACKNOWLEDGE” push-button is
depressed, the internal and external trouble audibles will be silenced. The trouble audibles will resound for subsequent trouble
conditions. The Form C trouble output contact will remain in the trouble condition and the “TROUBLE” indicator will remain
illuminated until all trouble conditions have been corrected.
The “RESET” push-button resets the strobe circuits after all initiating circuits are reset.
The “MANUAL/AUTOMATIC” switch has two positions, manual (down) and automatic (up). When the “MANUAL/AUTOMATIC”
toggle switch is in the automatic position, pre-recorded messages may be selected to play in individual circuits via dry contact inputs
and/or a serial communication interface. When the “MANUAL/AUTOMATIC” switch is in the manual position, pre-recorded
messages will not play, and the visual notification appliances are energized and the evacuation tone sounds in all circuits.
The “ALL-CALL” switch overrides any zone selection and allows audible signals to be heard regardless of the position of the four
zone select switches.
The four “ZONE SELECT” switches are numbered 1 through 4. They are used to silence any audible signal and turn off visual
signals in the respective zones, for live announcements only.
Operation Instructions
To make a live announcement:
1. Select specific zones or use “ALL-CALL” as necessary.
2. Remove microphone from its holder.
3. Hold down microphone’s push-to-talk button and talk into microphone.
To manually sound evacuation tone:
1. Move “MANUAL/AUTOMATIC” switch to the manual position.
The evacuation tone will sound in all circuits.
To silence trouble audibles:
1. Depress the “ACKNOWLEDGE” push-button.
To reset strobes:
1. All initiating circuits must be reset.
2. Momentarily depress the “RESET” push-button.
Содержание SAFEPATH RSAPE-B
Страница 11: ...Remote SAFEPATH Manual Sheet 11 of 50 Rev C December 1998 Figure 2 Operator s Console ...
Страница 16: ...Remote SAFEPATH Manual Sheet 16 of 50 Rev C December 1998 Figure 3 Panel Mounting ...
Страница 20: ...Remote SAFEPATH Manual Sheet 20 of 50 Rev C December 1998 Figure 4 Typical System Block Diagram ...
Страница 24: ...Remote SAFEPATH Manual Sheet 24 of 50 Rev C December 1998 Figure 11 Output Terminal Block Detail ...
Страница 33: ...Remote SAFEPATH Manual Sheet 33 of 50 Rev C December 1998 Figure 21 Trouble Location Indicator Locations ...
Страница 40: ...Remote SAFEPATH Manual Sheet 40 of 50 Rev C December 1998 Figure 22 Module Layout of the Panel ...
Страница 41: ...Remote SAFEPATH Manual Sheet 41 of 50 Rev C December 1998 Figure 23 Panel Block Diagram ...