SETTINGS:
The Switch (SW1) of the Multitone Signal, shown in Figure 1, is used to set the desired dBA sound output level and alarm tone. The
factory settings are shown below. Read these instructions carefully before changing any of these factory settings.
Figure 1:
PC Board Layout Showing Location
of the Switch (SW1)
1 2
3
4
SW1
4
3
2
1
SW1
+ AUD -
SLIDE HERE FOR (0)
SLIDE HERE FOR (1)
O
O
N
N
Figure 2:
Switch (SWI) Settings
POS 1
POS 2
POS 3
POS 4
SLIDE HERE FOR (1)
SLIDE HERE FOR (0)
USE A SMALL SCREWDRIVER TO
CHANGE THE SWITCH POSITION.
The factory settings are: HIGH dBA SW1 POS 1 set on 1 HORN TONE SW1 POS 2, 3, 4 set on 1, 1, 1
STEP 1:
The 115VAC Multitone Strobe signals cannot be field set for input voltage.
Set desired dBA sound output level as follows (refer to Figure 2 and Table 4).
Table 4: dBA Sound Output Level Settings
Decibel Level (dBA)
SW1 Switch Settings (POS 1)
High dBA
1 (Factory Setting)
Standard dBA
0
STEP 2:
Set desired alarm tone as follows (refer to Figure 2 and Table 5).
115VAC Multitone Signals are field set for any one of eight alarm tones by setting a four-position switch (SW1) as shown in Figure 2
and Table 5. Use SW1 POS 2, 3, 4 to select the desired alarm tone (refer to Table below).
Table 5: Alarm Tones
Tone Pattern
Description SWI
Switch
Settings
POS
POS
POS
2
3
4
Horn
Broadband Horn (Continuous)
1
1
1
(Factory Setting)
Bell
1560 Hz Modulated (0.07 Sec. ON/Repeat)
1
0
1
March Time Horn
Horn (0.25 Sec. ON/0.25 Sec. OFF/Repeat)
0
0
1
Code-3 Horn
Horn (ANSI S3.41 Temporal Pattern)
1
1
0
Code-3 Tone
500 Hz (ANSI S3.41 Temporal Pattern)
0
1
1
Slow Whoop
500-1200 Hz Sweep (4.0 Sec. ON/0.5 Sec. OFF/Repeat)
0
1
0
Siren
600-1200 Hz Sweep (1.0 Sec.ON/Repeat)
1
0
0
HI/LO
1000/800 Hz (0.25 Sec. ON/Alternate)
0
0
0
NOTE
: The Code-3 Horn and Code-3 Tone (set on HIGH dBA) incorporate the temporal pattern specified by ANSI/NFPA for
standard emergency evacuation signaling.
They should be used only for fire evacuation signaling and not for any other purpose
.
The Horn and Bell Tones can be used on coded systems with a minimum On-Time of 1/4 second. All other tones are recommended
for use only on continuous (non-coded) systems.
P83160 C
Sheet 3 of 6