background image

 

Table 2:  Candela at Various Angles 

 

 

Candela at Various AnglesPer UL 1638 

Model Rated 

Candela 

 
  

A1   

A2   

A3   

A4   

A5  A6/A7 

MT4-115-WH 

15.0cd 

   15.0      18.0      14.6     17.7       8.4          0.8 

A5

A7

A4

A3

A6

A1

A2

 

 

 

Table 3:  dBA and Current Ratings for Multitone (Audible Only) 

 

 
 

Tone 

 

Maximum RMS 

Current  

(AMPS) 

Reverberant dBA

 

At 10 Feet Per UL 464 

 

 HI 

STD 

HI 

STD 

Horn 0.050 

0.042 

85 

82 

Bell 0.041 

0.039 

82 

75 

March Time Horn 

0.050 

0.040 

85 

79 

Code-3 Horn 

0.050 

0.042 

82 

75 

Code-3 Tone 

0.042 

0.040 

79 

73 

Slow Whoop 

0.050 

0.042 

85 

79 

Siren 0.045 

0.041 

85 

79 

HI/LO 0.042 

0.039 

82 

75 

 

 

GENERAL NOTE: 

 

If the strobe and audible are wired to operate in unison on a single circuit, add strobe current from Table 1 to audible signal current 
from Table 3 to obtain total current for each unit. 

 

WARNING:  IF MULTITONE STROBE SIGNALS ARE OPERATED WITHIN 15 INCHES OF A PERSON'S EAR, THEY CAN 

PRODUCE A SOUND PRESSURE LEVEL THAT EXCEEDS THE MAXIMUM 120 dBA PERMITTED BY ADA AND OSHA RULES.  
EXPOSURE TO SUCH SOUND LEVELS CAN RESULT IN DAMAGE TO A PERSON'S HEARING. 

 

WARNING:  MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED 

TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES DO NOT EXCEED THE POWER SOURCES’ RATED 
CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED.  
OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO 
ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR 
DEATH TO YOU AND/OR OTHERS. 
 

When calculating the total currents:  Use Table 1 and 3 to determine the highest value of “RMS Current” for an individual strobe 
(across the expected operating voltage range of the strobe), then multiply these values by the total number of strobes; be sure to add 
the currents for any other appliances, including audible signaling appliances, powered by the same source and include any required 
safety factors. 
 

WARNING:  MAKE SURE THAT ALL FUSES USED ON SIGNALING CIRCUITS ARE RATED TO HANDLE THE MAXIMUM 

INRUSH OR PEAK CURRENT FROM ALL DEVICES ON THOSE CIURCUITS.  FAILURE TO DO THIS MAY RESULT IN LOSS OF 
POWER TO THE SIGNALING CIRCUIT AND THE FAILURE OF ALL DEVICES ON THAT CIRCUIT TO OPERATE, WHICH 
COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.

 

 

The Multitone audible signals produce a brief inrush current that lasts for just 50 microseconds but can reach a peak value of 5.0 
Amps. 

P83160 C 

Sheet 2 of 6 

Содержание MT4-115-WH

Страница 1: ...e identified by the symbol All warnings are printed in bold capital letters WARNING PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT THE MULTITONE STROBE SIGNALS MUST BE FIELD SET TO THE DESIRED dBA SOUND OUTPUT LEVEL AND ALARM TONE BEFORE THEY ARE INSTALLED THIS IS DONE BY PROPERLY INSERTING A JUMPER PLUG AND ADJUSTING A FOUR POSITION SWITCH IN ACCORDANCE WITH THESE INSTRUCTIONS...

Страница 2: ...RY AND SECONDARY POWER SOURCES DO NOT EXCEED THE POWER SOURCES RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS When calculati...

Страница 3: ... Table 5 115VAC Multitone Signals are field set for any one of eight alarm tones by setting a four position switch SW1 as shown in Figure 2 and Table 5 Use SW1 POS 2 3 4 to select the desired alarm tone refer to Table below Table 5 Alarm Tones Tone Pattern Description SWI Switch Settings POS POS POS 2 3 4 Horn Broadband Horn Continuous 1 1 1 Factory Setting Bell 1560 Hz Modulated 0 07 Sec ON Repea...

Страница 4: ...nted to a standard 4 inch square by 2 1 8 inch deep electrical box Figure A weather resistant backbox WBB Figure B or a 4 inch square by 1 1 2 inch extension ring and a 4 inch square by 2 1 8 inch deep electrical box Figure C 3 Select largest backbox shown in Mounting Options where possible to provide additional wiring room for easy installation 4 Conduit entrance to backboxes should be selected t...

Страница 5: ...OLATED FROM THIS DOCUMENT OR FROM WHEELOCK MANUALS OR OTHER DOCUMENTS DESCRIBING THE PRODUCT FOR USE IN PROMOTIONAL OR ADVERTISING CLAIMS OR FOR ANY OTHER USE INCLUDING DESCRIPTION OF THE PRODUCT S APPLICATION OPERATION INSTALLATION AND TESTING IS USED AT THE SOLE RISK OF THE USER AND WHEELOCK WILL NOT HAVE ANY LIABILITY FOR SUCH USE The Multitone Strobe products and these instructions are copyrig...

Страница 6: ...SPECIFICATION ABUSE ACCIDENT OR OTHER PERATING CONDITIONS BEYOND WHEELOCK S CONTROL O SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE WITH RESPECT TO THOSE PRODUCTS WHEELOCK DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORMANCE OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER S REQUIR...

Отзывы: