background image

P83932 D 

Sheet 8 of 8 

 

 

 

 

WARNING:  INSTALLATION OF WHEELOCK 110 CANDELA STROBE PRODUCTS IN SLEEPING AREAS SHOULD BE 

WALL MOUNTED AT LEAST 24" BELOW THE CEILING AS FOLLOWS:  (1) THE ON-AXIS (DIRECTLY IN FRONT OF LENS) 
LIGHT OUTPUT SHOULD BE DIRECTED AT THE EYE-LIDS OF THE SLEEPING PERSON, E.G. PILLOW END OF BED, BED 
HEAD; (2)  NO PART OF THE BED SHALL BE MORE THAN SIXTEEN (16) FEET FROM THE STROBE NOTIFICATION 
APPLIANCE.  INSTALLERS MUST ADVISE OWNERS AND OPERATORS OF BUILDINGS WITH SLEEPING OCCUPANTS, E.G. 
HOTELS AND MOTELS, TO WARN GUESTS, RESIDENTS AND EMPLOYEES TO NOT MOVE THE BED LOCATION TO A 
POSITION VIOLATING POINTS (1) AND (2) ABOVE OR SERIOUS INJURY AND/OR LOSS OF LIFE MAY OCCUR DURING A 
FIRE EMERGENCY. 

 
 
 
 

WARNING:  A SMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES WITHIN A PERSON'S FIELD OF 

VIEW, UNDER CERTAIN CIRCUMSTANCES, MIGHT INDUCE A PHOTO-SENSITIVE RESPONSE IN PERSONS WITH 
EPILEPSY.  STROBE REFLECTIONS IN A GLASS OR MIRRORED SURFACE MIGHT ALSO INDUCE SUCH A RESPONSE.  TO 
MINIMIZE THIS POSSIBLE HAZARD, WHEELOCK STRONGLY RECOMMENDS THAT THE STROBES INSTALLED SHOULD 
NOT PRESENT A COMPOSITE FLASH RATE IN THE FIELD OF VIEW WHICH EXCEEDS FIVE (5) Hz AT THE OPERATING 
VOLTAGE OF THE STROBES.  WHEELOCK ALSO STRONGLY RECOMMENDS THAT THE INTENSITY AND COMPOSITE 
FLASH RATE OF INSTALLED STROBES COMPLY WITH LEVELS ESTABLISHED BY APPLICABLE LAWS, STANDARDS, 
REGULATIONS, CODES AND GUIDELINES. 

 

NOTE:  

NFPA 72/ANSI 117.1 conform to ADAAG Equivalent Facilitation Guidelines in using fewer, higher intensity strobes within the 

same protected area. 

 
 
 
 

CAUTION:  

Check the installation instructions of the manufacturers of other equipment used in the system for any guidelines or 

restrictions on wiring and/or locating Notification Appliance Circuits (NAC) and notification appliances.  Some system communication 
circuits and/or audio circuits, for example, may require special precautions to assure electrical noise immunity (e.g. audio crosstalk). 

 
 
 
 

NOTE:

  This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC 

Rules.  These limits are designed to provide reasonable protection against harmful interference in residential installation.  This 
equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, 
may cause harmful interference to radio communications.  However, there is no guarantee that interference will not occur in a particular 
installation.  If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the 
equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:  1) Reorient or 
relocate the receiving antenna,  2) Increase the separation between the equipment and receiver,  3) Connect the equipment into an 
outlet on a circuit different from that to which the receiver is connected, and  4) Consult the dealer or an experienced radio/TV 
technician for help. 

 
 
 
 

ANY MATERIAL EXTRAPOLATED FROM THIS DOCUMENT OR FROM WHEELOCK MANUALS OR OTHER DOCUMENTS 
DESCRIBING THE PRODUCT FOR USE IN PROMOTIONAL OR ADVERTISING CLAIMS, OR FOR ANY OTHER USE, 
INCLUDING DESCRIPTION OF THE PRODUCT'S APPLICATION, OPERATION, INSTALLATION AND TESTING IS USED AT 
THE SOLE RISK OF THE USER AND WHEELOCK WILL NOT HAVE ANY LIABILITY FOR SUCH USE. 

 
 
 
 

IMPORTANT:  READ SEPARATE "GENERAL INFORMATION" SHEET FOR INFORMATION ON THE PLACEMENT, 
LIMITATIONS, INSTALLATION, FINAL CHECKOUT, AND PERIODIC TESTING OF NOTIFICATION APPLIANCES. 

 

www.PDF-Zoo.com

Содержание CH70-24MCW Series

Страница 1: ...ied by the symbol All warnings are printed in bold capital letters WARNING READ THESE INSTRUCTIONS CAREFULLY FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS CAUTIONS AND WARNINGS COULD RESULT...

Страница 2: ...APACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT O...

Страница 3: ...75 4 5 12 9 0 23 22 5 54 33 0 76 80 4 5 10 9 0 17 22 5 47 33 0 64 85 3 8 5 7 5 10 18 8 25 27 5 33 90 3 8 7 7 5 15 18 8 39 27 5 52 Table 3B Vertical Plane Vertical 15cd 30cd 75cd 110cd Angle in deg UL...

Страница 4: ...P83932 D Sheet 4 of 8 www PDF Zoo com...

Страница 5: ...stems where the chime is set on single stroke SS mode and is cycled on and off while the strobe flashes continuously Figure 2 Chime Appliance and Strobe Appliance operate in unison Red and black wires...

Страница 6: ...niques to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product This is especially important for stiff heavy gauge wires and wires with thick...

Страница 7: ...TIONS SPECIAL ATTENTION SHOULD BE GIVEN TO THE LOCATION OF THE STROBES SO THAT THEIR OPERATING EFFECT CAN BE SEEN BY ALL INTENDED VIEWERS WITH THE INTENSITY NUMBER AND TYPE OF STROBES BEING SUFFICIENT...

Страница 8: ...ons on wiring and or locating Notification Appliance Circuits NAC and notification appliances Some system communication circuits and or audio circuits for example may require special precautions to as...

Страница 9: ...ATION ABUSE ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK S CONTROL SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE WITH RESPECT TO THOSE PRODUCTS WHEELOCK DOES NOT WARRANTY THAT THE OPERATION OF THE...

Отзывы: