WARNING: THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR RATED INPUT VOLTAGE RANGE.  

THE APPLICATION OF IMPROPER VOLTAGE MAY RESULT IN DEGRADED OPERATION OR DAMAGE TO THESE 
PRODUCTS, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR 
OTHERS. 

 

WARNING:  CANDELA SETTING WILL DETERMINE THE CURRENT DRAW OF THE PRODUCT. 

 

Table 2:  Strobe Current Ratings (AMPS) for 24VDC 

Rated Average Current (RMS) 

Voltage 

15cd 

30cd 

75cd 

110cd 

16.0VDC 

0.070 

0.114 

0.220 

0.289 

24.0VDC 

0.049 

0.085 

0.137 

0.180 

33.0VDC 

0.043 

0.065 

0.105 

0.143 

16.0VRMS 

0.113 

0.190 

0.339 

0.458 

24.0VRMS 

0.095 

0.138 

0.224 

0.282 

33.0VRMS 

0.098 

0.133 

0.202 

0.244 

Rated Peak Current * 

Voltage 

15cd 

30cd 

75cd 

110cd 

16.0VDC 

0.125 

0.182 

0.356 

0.454 

24.0VDC 

0.110 

0.149 

0.260 

0.334 

33.0VDC 

0.145 

0.195 

0.294 

0.368 

16.0VRMS 

0.450 

0.630 

1.310 

1.560 

24.0VRMS 

0.525 

0.665 

1.030 

1.215 

33.0VRMS 

0.905 

1.030 

1.290 

1.410 

 

*  Time duration of Strobe Peak Current is 1 millisecond. 

 

NOTE

:  Strobe Inrush Current is less than Rated Peak Current. 

 

WARNING:  MAKE SURE THAT THE TOTAL AVERAGE CURRENT AND TOTAL PEAK CURRENT REQ UIRED BY ALL 

APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, NAC CIRCUITS, 
SM, DSM SYNC MODULES AND THE PS-12/24-8 POWER BOOSTER DO NOT EXCEED THE POWER SOURCES’ RATED 
CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED.  
OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO 
ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY 
OR DEATH TO YOU AND/OR OTHERS. 
 
 

When calculating the total average or peak currents:  Use Table 2 to determine the highest value of “Rated Average Current” for an 
individual chime strobe (across the expected operating voltage range of the chime strobe), or the highest value of “Rated Peak Current” 
(whichever is higher) of an individual chime strobe (across the expected voltage range of the chime strobe), then multiply the value by 
the total number of chime strobes; be sure to add the currents for the chimes and any other appliances, including audible signaling 
appliances, powered by the same source and include any required safety factors. 
 
 
If the peak current exceeds the power supplies’ inrush capacity, the output voltage provided by the power supplies may drop below the 
lis ted voltage range of the appliances connected to the supply and the voltage may not recover in some types of power supplies.  For 
example, an auxiliary power supply that lacks filtering at its output stage (either via lack of capacitance and/or lack of battery backup 
across the output) may exhibit this characteristic. 
 
 

CAUTION:  

The

 

Chime Strobe is not designed to be used on coded systems in which the applied voltage is cycled on and off. 

 
 
 

www.PDF-Zoo.com

Содержание CH70-24MCW Series

Страница 1: ...ied by the symbol All warnings are printed in bold capital letters WARNING READ THESE INSTRUCTIONS CAREFULLY FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS CAUTIONS AND WARNINGS COULD RESULT...

Страница 2: ...APACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT O...

Страница 3: ...75 4 5 12 9 0 23 22 5 54 33 0 76 80 4 5 10 9 0 17 22 5 47 33 0 64 85 3 8 5 7 5 10 18 8 25 27 5 33 90 3 8 7 7 5 15 18 8 39 27 5 52 Table 3B Vertical Plane Vertical 15cd 30cd 75cd 110cd Angle in deg UL...

Страница 4: ...P83932 D Sheet 4 of 8 www PDF Zoo com...

Страница 5: ...stems where the chime is set on single stroke SS mode and is cycled on and off while the strobe flashes continuously Figure 2 Chime Appliance and Strobe Appliance operate in unison Red and black wires...

Страница 6: ...niques to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product This is especially important for stiff heavy gauge wires and wires with thick...

Страница 7: ...TIONS SPECIAL ATTENTION SHOULD BE GIVEN TO THE LOCATION OF THE STROBES SO THAT THEIR OPERATING EFFECT CAN BE SEEN BY ALL INTENDED VIEWERS WITH THE INTENSITY NUMBER AND TYPE OF STROBES BEING SUFFICIENT...

Страница 8: ...ons on wiring and or locating Notification Appliance Circuits NAC and notification appliances Some system communication circuits and or audio circuits for example may require special precautions to as...

Страница 9: ...ATION ABUSE ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK S CONTROL SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE WITH RESPECT TO THOSE PRODUCTS WHEELOCK DOES NOT WARRANTY THAT THE OPERATION OF THE...

Отзывы: