Whale WH1302 Скачать руководство пользователя страница 14

  The Water Heater is equipped with an electronic diagnostic system which will detect fault conditions ranging from
poor gas or d.c. supply to internal Water Heater malfunctions. In the unlikely event of a failure, the red LED on the
Control Panel will light. To diagnose the problem please refer to the table on page 15.

Option 1 -  Whale Space Heater Control Panel

In the unlikely event of a failure, the red LED on the Control Panel will flash a number of times, pause, and repeat
until switched off. Count the number of flashes and refer to the table on page 15.

Gas Lockouts

Gas lockouts 

must be

cleared by moving the gas switch from ‘on’ position to ‘off’ position then back to the ‘on’ 

position. The complete sequence of switch movements 

must be 

completed within 2.5 seconds for a lockout to be

successfully cleared. If there is air in the gas line, e.g. after a gas bottle change, the Water Heater may require 
several attempts before it lights.

Other Lockouts

If the lockout is caused when the unit is operated on electric, the lockout can be cleared by moving the electric switch
from ‘on’ position to ‘off’ position then back to the ‘on’ position. The complete sequence of switch movements 

must

be 

completed within 2.5 seconds for a lockout to be successfully cleared.

Note:

A cycling of the power supply to the unit will not clear a lockout. Some gas lockouts, e.g. Ignition lockout will

still permit use of the appliance in electric only operation.

If the problem persists contact 

Whale® Support on +44 (0)845 217 2933.

Option 2 -  Whale Duo Control Panel 

In the unlikely event of a failure, the red ‘ ! ’LED on the Control Panel will light (see Fig. 30). To identify the lockout
press and hold, both the Water Heater Function Button and ‘ + ’.  at the same time. The temperature control bars will
light to indicate the fault code e.g if 1 bar lights, the fault code is 1, if 2 bars lights, the fault code is 2 etc. Press ‘ + ’
to clear the fault code. Please refer to the table on page 14.

Note:

A cycling of the power supply to the unit will not clear a lockout. Some gas lockouts, e.g. ignition lockout and

combustion air faults will still permit use of the appliance in electric only operation.

If the problem persists, contact 

Whale Support on +44 (0)845 217 2933.

Table 2: Water Heater Fault Finding

14

9. TROUBLE SHOOTING

Number of 

flashes / bars

lit

Fault

Remedy

1

No flame detected

2

Overheat

3

Low/high 

supply voltage

5

Other / internal fault

Check gas supply making sure there is gas in the bottle and no blockage in the gas
line. Ensure propane is used at temperatures below +5°C. Clear lockout as described
above.

Check there is water in the appliance. Whale recommends you wait at least 5 to 10
minutes to allow the heater to cool before clearing lockout as described above

.

Minimum operating voltage is 10V, maximum is 15V, when measured at the Water
Heater. Check battery voltage. If between 10V and 15V, check connections between
Water Heater and battery. Check alternator or external battery charging. Clear 
lockout as described above.

Attempt to clear lockout as described above. If this fails, contact a Whale Authorised
Service Engineer.

Содержание WH1302

Страница 1: ...mensions Plan View Fig 4 Dimensions Front View Fig 5 Installation Locating Diagram Fig 6 Cut Out Hole For Flue Fig 7 Flue Dimensions Fig 8 Reinforce Flue Hole Fig 9 Sealing the Space between Flue and...

Страница 2: ...al Heat Input Gas 1 25kW Standby Consumption Gas 98W Nominal Heat Input Electric 1 2kW Electric 230V a c 50 Hz 600 1200W Maximum Current a c 6 Amps Nominal Voltage 12V d c 10 0V d c min to 15V d c max...

Страница 3: ...vehicle in which the Water Heater is installed in a confined space such as a garage This appliance is not intended for use by persons including children with reduced physical sensory or mental capabi...

Страница 4: ...sure Relief Drain Valve Assembly 1 Male Adaptor Flexible Hose Plumbing Fitting 2 Male Adaptor Flexible Hose Plumbing Fitting 1 Warranty Registration Card 1 Instruction Manual including installation te...

Страница 5: ...ler must check the compatibility of the data plate information with the LPG supply requirements of the vehicle Follow these installation instructions and ensure all relevant personnel read the points...

Страница 6: ...The flue terminal must not be fitted within 300mm of a ventilator for the living space or an opening part of a window Fig 5 Installation Locating Diagram The flue terminal must only be positioned vert...

Страница 7: ...f the flue cover onto the back box and secure with two screws No 6 x 1 2 provided Step 5 Connect Water Heater to Flue Set Water Heater on the floor and slide fully into flue as shown see Fig 12 7 Fig...

Страница 8: ...to the atmosphere at all times Fig 14 Fitting the Pressure Relief Drain Valve Step 7 Secure Water Heater to Floor To secure the Water Heater to the floor use 4 screws No 8 x 1 provided see Fig 15 Fig...

Страница 9: ...wires through the Control Panel mounting frame see Fig 17 and line up the holes with the Control Panel Feed the wires through the cut out in the wall and locate into desired position Secure with 2 scr...

Страница 10: ...es Connect the red flying lead coming from the 8 way connector to a 12V d c supply then connect the white flying lead to the caravan 0V d c Please note Whale recommends that a 5 amp fuse is fitted in...

Страница 11: ...re Relief Valve to prevent back flow of hot water to cold water taps Step 13 Connect Hot Water Supply see Figs 25 26 Screw in the braided hose supplied into the hot water outlet and tighten with a 19m...

Страница 12: ...connected to a suitable 230V a c supply Upon initial operation or to refill after the system has been drained check the drain valve is closed then fill the system with clean fresh water To fill open o...

Страница 13: ...on is illuminated For 1200W press the Water Heater Function key until the high power setting icon is illuminated Note The electric elements will still operate if the appliance is in gas ignition lock...

Страница 14: ...oblem persists contact Whale Support on 44 0 845 217 2933 Option 2 Whale Duo Control Panel In the unlikely event of a failure the red LED on the Control Panel will light see Fig 30 To identify the loc...

Страница 15: ...onsibility that the above equipment complies with the provisions of the following EC Directives Gas Appliance Directive 2009 142 EC on the approximation of the laws of the Member States relating to ap...

Страница 16: ...T19 7TA Tel 44 0 28 9127 0531 Fax 44 0 28 9146 6421 www whalepumps com Email info whalepumps com Copyright Whale 2015 All rights reserved Whale s policy is one of continuous improvement and we reserve...

Отзывы: