![WFI EKW FX10 Скачать руководство пользователя страница 24](http://html1.mh-extra.com/html/wfi/ekw-fx10/ekw-fx10_installation-manual_967028024.webp)
24
EKW FX10 INSTALLATION MANUAL
BS en 14511 Ratings*
metric (si) units
ARi/iSO 13256-2
metric (si) units
Unit Model
Load Liquid
Flow (gpm)
Source Liquid
Flow (gpm)
Ground Loop Heat Pump
Cooling
Heating
ELT 50°F EST 80°F
ELT 104°F EST 32°F
Capacity Btuh
EER Btuh/W
Capacity Btuh
COP
EKW06
3.0
6.0
-
-
18,700
2.9
EKW08
5.0
8.0
24,490
3.5
25,000
3.2
EKW12
7.0
11.0
36,735
3.7
36,000
3.3
EKW17
11.0
14.0
44,558
3.1
51,500
3.1
All ratings based upon lower Voltage operation of dual Voltage rated units
“-” not rated
ARi/iSO 13256-2
english (iP) units
Unit Model
Load Liquid
Flow (L/s)
Source Liquid
Flow (L/s)
Ground Loop Heat Pump
Cooling
Heating
ELT 10°C EST 27°C
ELT 40°C EST 0°C
Capacity kW
COP
Capacity kW
COP
EKW06
0.19
0.38
-
-
5.5
2.9
EKW08
0.32
0.50
7.2
3.5
7.3
3.2
EKW12
0.44
0.69
10.8
3.7
10.6
3.3
EKW17
0.69
0.88
13.1
3.1
15.1
3.1
All ratings based upon lower Voltage operation of dual Voltage rated units
“-” not rated
ARI/ISO/BS EN Ratings
Unit Model
Ground Loop Heat Pump Cooling
Ground Loop Heat Pump Heating
Load Liquid
Flow (L/s)
Source Liquid
Flow (L/s)
LLT 18°C
LST 35°C
Load Liquid
Flow (L/s)
Source Liquid
Flow (L/s)
LLT 35°C
LST -3°C
Capacity kW
COP
Capacity kW
COP
EKW06
0.4
0.4
7.6
5.1
0.3
0.3
5.9
4.1
EKW08
0.6
0.5
11.4
6.1
0.4
0.4
8.1
4.2
EKW12
0.8
1.0
17.2
5.7
0.6
0.7
12.4
4.3
EKW17
1.0
1.3
21.7
5.4
0.8
0.9
17.1
4.3
All ratings based upon lower Voltage operation of dual Voltage rated units
* Performance verified by ETL