EKW FX10 INSTALLATION MANUAL
1. application overview
The application is created for an FX10 Universal Controller with no expansion board. The application is designed to
operate WaterFurnace E Series water–water heat pumps in either of three modes: Aqua-stat, S-Plan, or Setpoint.
The application will provide load entering water temperature setpoint control for comfort heating and cooling,
domestic hot water temperature setpoint control, and basic features such as a random start and anti-short cycle delay
for the compressor, low water coil temperature limit, safety switch sensing, and system fault lockout. The controller
will provide the following modes of operation: Aqua-stat Control, S-Plan, Setpoint Control, Emergency Shutdown, and
Lockout. The application will be designed for use with open N2, LON, and BACnet systems.
2. inputs and Outputs Configuration
CS-SSWWE-01
REV B
E-Series Single Stage Water-to-Water
Controls Specification
Page 5 of 12
Created on 1/31/2007
5
3.
Inputs and Outputs Configuration
SINGLE STAGE WW WITH STAGING
SETPOINT CONTROL
Input Name
Input
Location
Output Name
Output
Location
Entering Load Water Temperature
AI 1
Reversing Valve
BO1
Leaving Load Water Temperature
AI 2
Compressor Start/Stop
BO2
Entering Source Water Temperature
AI 3
Secondary Unit Heat/Cool
Select
BO3
Source low water coil temperature limit
Protection
AI 4
Secondary Unit Enable (Y2)
BO4
Load low water coil temperature limit
Protection
AI 5
Secondary Unit S-Plan Comfort
Select Enable
BO5
Leaving Source Water Temperature
AI 6
Alarm
BO6
Accessory Output 1/Src Pump
BO7
Compressor Proving
BI 1
Accessory Output 2/Load Pump
BO8
Emergency Shutdown
BI 2
Load Water Valve Control
B09
Low Suction Pressure Switch
BI 3
Source Low Temp Limit Select - 30ºF/-1°C
BI 4
Unused
PWM1
Load Low Temp Limit Select - 30ºF/-1C°
BI 5
Unused
PWM2
Spare
BI 6
Y1/System Enable
BI 7
Source Flow Proving
BI 8
Aqua-stat O/Heating-Cooling select
BI 9
S-Plan Comfort Select
B10
Stage 1 High Pressure
BI11
Load Flow Proving
BI12
XP10 Expansion Card
Input Name
Input
Location
Output Name
Output
Location
Unused
AI 1
Unused
BO 1
Unused
AI 2
Unused
BO 2
Unused
AI 3
Unused
BO 3
Unused
AI 4
Unused
BO 4