Setting Regeneration Cycle Times
Step 1CT -
Press NEXT and
▼
simultaneously for 5
seconds and release. If screen in Step 2CT does not appear,
the lock on the valve is activated. To unlock press
▼
,
NEXT, REGEN,
▲
in sequence, then press NEXT and
▼
simultaneously for 5 seconds and release.
Step 2CT -
Adjust the length of the backwash from 1-20
minutes or OFF using the
▲
or
▼
buttons.
Press NEXT to go to Step 3CT. Press REGEN to exit
Regeneration Cycle Times.
Step 3CT -
Adjust the length of the regenerant draw
from 1-99 minutes or OFF using the
▲
or
▼
buttons.
Press NEXT to go to Step 4 CT. Press REGEN to return
to previous step.
Step 4CT -
Adjust the length of the second backwash
from 1-20 minutes or OFF using the
▲
or
▼
buttons.
Press NEXT to go to Step 5 CT. Press REGEN to return
to previous step.
Step 5CT -
Adjust the length of rinse from 1-20
minutes or OFF using the
▲
or
▼
buttons.
Press NEXT to go to Step 6 CT. Press REGEN to return
to previous step.
Step 6CT -
Adjust the length of fi ll from 0.1-99.9
minutes or OFF. Regenerant refi lls at a rate of 0.5 gpm,
1.9 lpm.
Press NEXT to exit Regeneration Cycle Times. Press
REGEN to return to previous step.