76-5276-05
Page 32 of 82
Maximum Distances between Indoor and Outdoor Units (Compressor on the outdoor unit)
For R-410A WESTRIC Split Systems
Compressor
Capacity
Maximum
Length
Recommended diameters according to the pipe length (outdoor unit compressor)
1 to 5 meters
Up to 10 meters
Up to 15 meters
Up to 20 meters
Up to 30 meters
Vert.
Total
Líq.
Gas.
Líq.
Gas
Líq.
Gas
Líq.
Gas
Líq.
Gas
18 KW
9
30
3/8”
3/4”
3/8”
7/8”
1/2”
7/8”
1/2”
1”
1/2”
1”
20 KW
9
30
3/8”
3/4”
3/8”
7/8”
1/2”
7/8”
1/2”
1”
1/2”
1”
Performance loss
0 %
1 %
2 %
3 %
4 %
Maximum Distances between Indoor and Outdoor Units (Compressor on the indoor unit)
For R-410A WESTRIC Split Systems
Capac.
Comp.
Lenght
Maximum
Recommended diameters according to the length of the pipe
1 to 5 meters
Up to 10 meters
Up to 15 meters
Up to 20 meters
Up to 30 meters
Up to 45 meters
Vert.
Total
Líq.
Gas
Líq.
Gas
Líq.
Gas
Líq.
Gas
Líq.
Gas
Líq.
Gas
18 KW
25
45
3/8”
1/2”
3/8”
5/8”
1/2”
5/8”
1/2”
5/8”
1/2”
3/4”
1/2”
7/8”
20 KW
25
45
3/8”
1/2”
3/8”
5/8”
1/2”
5/8”
1/2”
5/8”
1/2”
3/4”
1/2”
7/8”
Performance loss
0 %
1 %
2 %
3 %
4 %
5 %
When the compressor is above the evaporator up to 6 m., An oil trap should always be made at the beginning of the rise
to the condenser.
When the height exceeds 6 m. a trap should be made every 4 m. approx. between each, the total sum should not exceed
9 m. in height.
When you have greater heights than 9 m. an oil separator must be placed between the compressor and the condensing
coil, to avoid the expulsion of the oil to the circuit and that can not return to the compressor, due to the great height
difference.
Important:
When get the pipes through the walls, cover the tips to avoid the dirt. The refrigeration pipes must be clean of
dirt and oils and at the moment of welding them it is convenient, to circulate low pressure nitrogen to avoid slag, by the
oxidation of the torch inside the pipe.
Once the welding is finished, from the service valves, circulate high pressure nitrogen through the pipes, to expel any
waste that may have.
Once the interconnection is finished, vacuum the pipes from high and low service valves or on the outdoor unit if it lacks of
service vales and charged with refrigerant gas.
If for any reason it is necessary to vacuum from a single pipe and to the indoor unit, warm the, with the hand so that it
opens and make a vacuum to the whole system.
Once finished and with the unit running for a few hours, check that the oil level (where it has a sight hole) is at normal
levels; otherwise, add oil until you reach the level.
Our units comes fully loaded from factory, and allows up to 5 meters of pipes without adding gas.
Содержание IW Series
Страница 1: ......
Страница 2: ...76 5276 05 Page 2 of 82 ...
Страница 4: ...76 5276 05 Page 4 of 82 ...
Страница 6: ...76 5276 05 Page 6 of 82 ...
Страница 11: ...76 5276 05 Page 11 of 82 Different air flow configuration ...
Страница 12: ...76 5276 05 Page 12 of 82 IW 005 006 Side Air Flow Rear Air Return Indoor Unit Dimensions ...
Страница 13: ...76 5276 05 Page 13 of 82 IW 005 006 Front Air Flow Rear Air Return Indoor Unit Dimensions ...
Страница 14: ...76 5276 05 Page 14 of 82 IW 005 Outdoor Unit Dimensions ...
Страница 15: ...76 5276 05 Page 15 of 82 IW 006 Outdoor Unit Dimensions ...
Страница 24: ...76 5276 05 Page 24 of 82 Slideable Electrical Panel View ...
Страница 27: ...76 5276 05 Page 27 of 82 Installation and Assembly ...
Страница 60: ...76 5276 05 Page 60 of 82 Settings for Gmail ...
Страница 61: ...76 5276 05 Page 61 of 82 ...
Страница 62: ...76 5276 05 Page 62 of 82 Place Allow unsafe applications access in YES Configuration for Yahoo ...
Страница 69: ...76 5276 05 Page 69 of 82 ...
Страница 73: ...76 5276 05 Page 73 of 82 Drain Pump Optional ...
Страница 75: ...76 5276 05 Page 75 of 82 PLC Electrical connection diagram with remote display ...
Страница 76: ...76 5276 05 Page 76 of 82 IW 005 006 Control Electrical Diagram ...
Страница 77: ...76 5276 05 Page 77 of 82 IW 005 Power Electrical Diagram ...
Страница 78: ...76 5276 05 Page 78 of 82 IW 006 Power Electrical Diagram ...
Страница 79: ...76 5276 05 Page 79 of 82 IW 005 Power Electrical Diagram no humidifier no resistors Ext Digital Comp ...
Страница 80: ...76 5276 05 Page 80 of 82 IW 005 Power Electrical Diagram with or without humidifier Ext Digital Comp ...
Страница 81: ...76 5276 05 Page 81 of 82 IW 005 Control Electrical Diagram with or without humidifier Ext Digital Comp ...
Страница 82: ...76 5276 05 Page 82 of 82 ...