background image

Copyright © Westlock. All rights reserved.

VCIOM-05124

Page 3 of 14

FPAC2 UPgrAde

InstallatIon and operatIon manual

2 rePlACINg The eleCTrONIC MOdUle

step 1: 

Turn off the bus power and remove 

the fieldbus connector and I/O connectors. 
Remove the old electronic module from the 
housing. Put aside screws, washers and other 
accessories. See Figure 3.

step 2:

 Replace the 2-pin fieldbus connector 

with the new 3-pin connector. Make sure to 
connect the grounding (J2 BuS pin #2) to 
the grounding point inside the housing. The 
grounding pin (J2 BuS pin #2) should not be 
connected to the cable shield. The cable’s 
shield should be cut short and taped to avoid 
strains, contact with any metallic surface or 
other wires. See Figure 4.

step 3:

 Install the new electronic module in 

the housing. Make sure to put back washers, 
tighten all screws and reconnect I/O and 
fieldbus connectors. See Figure 5.

step 4:

 Energize the fieldbus (9-32 VDC) and 

verify that all LEDs blink once. If there is 
communication on the fieldbus the BuS LED 

will start blinking at a rate around 1 Hz. If the 

magnets as properly aligned OPEN or CLSD 
LED should light on indicating the current 
valve position.

FIguRE 3
Remove the old FPAC from the housing

FIguRE 4
Replace the old 2-pin fieldbus connector with new 3-pin connector

FIguRE 5
New electronic module installed with I/O connectors on

Содержание FPAC1

Страница 1: ...one rotary valve using the internal Hall Effect sensors as limit switches The application controls the valve position through 1 one DO block and gets the position feedback from 1 one DI block Other c...

Страница 2: ...rade Installation and operation manual Fieldbus input polarity insensitive Fieldbus input J2 J5 analog pos pot Earth ground Embedded hall effect sensors Top opened limit SW Bottom closed limit SW Top...

Страница 3: ...cable shield The cable s shield should be cut short and taped to avoid strains contact with any metallic surface or other wires See Figure 4 Step 3 Install the new electronic module in the housing Ma...

Страница 4: ...t listed contact Westlock to receive the latest DD CF files 0501 or download it directly from the Fieldbus Foundation registered products website link below 2 See Figure 7 Note 2 This URL is maintaine...

Страница 5: ...in the Decommissioned Fieldbus Devices list check if it is available for commissioning If not right click on it and select Place in Standby Wait until this process is finished and the window closes S...

Страница 6: ...inished right click on it and select Properties change device revision to 5 and click on OK See Figure 10 Step 11 If a warning message appears indicating some incompatibilities click OK Right click on...

Страница 7: ...Step 12 Selected the new device from the list and click OK If a warning message appears click OK In the window that will appear DO NOT click Reconcile Device just click Next See Figure 12 Step 13 Clic...

Страница 8: ...on Right click on the device and select Configure Setup The AMS window will open See Figure 14 Figure 14 Figure 15 Figure 16 Step 15 In the menu tree select Transducer Basic Setup Reconfigure the new...

Страница 9: ...n the persistent database Use DeltaV explorer or Control Studio for function blocks configuration as illustrated in the next section Figure 17 Figure 18 6 Reassigning the function blocks in the existe...

Страница 10: ...the DO and DI blocks Sometimes this step is automatically done by the system depending on the system s configuration See Figure 20 Figure 19 Figure 20 Figure 21 Step 22 After unassigning all function...

Страница 11: ...message appears click Yes OK and wait until the download is finished successfully See Figure 23 Figure 22 Figure 24 Figure 23 Step 27 Close the download window and open the Control Studio in online m...

Страница 12: ...mal Acting ACTION_ELEMENT 1 Single Action IO_ASSIGNMENT 1 Top Bot Out0 SIGNAL_ACTION 1 Increase to Close ACTION_ELEMENT 1 Single Action IO_ASSIGNMENT 6 Aux1 Aux2 Out1 SIGNAL_ACTION 0 Increase to Open...

Страница 13: ...ew channel functionality for valve 2 25 TRD2 0 Close 1 Open 2 Stop New channel functionality for valve 2 91 FSTATE TRD 1 Valve 1 New channel to force fault state on transducer 1 92 FSTATE TRD2 Valve 2...

Страница 14: ...relevant notified certification body and therefore the original English document will prevail No rights or liability can be derived from any translation Previous documents VCIOM 05124 EN replaces all...

Отзывы: