FPAC2 UPgrAde
InstallatIon and operatIon manual
8 APPeNdIx A - sOMe dIFFereNCes beTweeN FPAC1 reV 2, 3, 4 ANd FPAC2 reV 5
For the complete set of features for each device revision refer to IOMs VCIOM-05123 and
TECH-485.
8.1 Transducer basic parameters mapping
Look up at the old FPAC transducer block configuration and take note of the value in the ACTION_
ELEMENT parameter. This parameter has to be mapped into 3 (three) other parameters in the
new FPAC2 standard transducer block, as indicated in the table below:
TAble 1 - TrANsdUCer PArAMeTers bAsIC CONFIgUrATION MAPPINg
FPAC1 rev 2,3,4 Transducer
FPAC1 rev 2,3,4 Transducer
FPAC2 rev 5 standard Transducer blocks
Transducer
Transducer 1 (Valve 1)
Transducer 2 (Valve 2)
0
ACTION_ELEMENT = No Selection
ACTION_ELEMENT = 0: No Selection
IO_ASSIgNMENT = 0: No Selection
ACTION_ELEMENT = 0: No Selection
IO_ASSIgNMENT = 0: No Selection
1
ACTION_ELEMENT = Single Action
ACTION_ELEMENT = 1: Single Action
IO_ASSIgNMENT = 1: Top,Bot,Out0
SIgNAL_ACTION = 0: Increase to Open
ACTION_ELEMENT = 0: No Selection
IO_ASSIgNMENT = 0: No Selection
3
ACTION_ELEMENT = Double Action
ACTION_ELEMENT = 1: Double Action
IO_ASSIgNMENT = 1: Top,Bot,Out0
SIgNAL_ACTION = 0: Increase to Open
ACTION_ELEMENT = 0: No Selection
IO_ASSIgNMENT = 0: No Selection
4
ACTION_ELEMENT = Single Action,
Reverse Acting
ACTION_ELEMENT = 1: Single Action
IO_ASSIgNMENT = 1: Top,Bot,Out0
SIgNAL_ACTION = 1: Increase to Close
ACTION_ELEMENT = 0: No Selection
IO_ASSIgNMENT = 0: No Selection
6
ACTION_ELEMENT = Double Action,
Reverse Acting
ACTION_ELEMENT = 1: Double Action
IO_ASSIgNMENT = 1: Top,Bot,Out0
SIgNAL_ACTION = 1: Increase to Close
ACTION_ELEMENT = 0: No Selection
IO_ASSIgNMENT = 0: No Selection
8
ACTION_ELEMENT = Independent,
both Normal Acting
ACTION_ELEMENT = 1: Single Action
IO_ASSIgNMENT = 1: Top,Bot,Out0
SIgNAL_ACTION = 0: Increase to Open
ACTION_ELEMENT = 1: Single Action
IO_ASSIgNMENT = 6: Aux1,Aux2,Out1
SIgNAL_ACTION = 0: Increase to Open
9
ACTION_ELEMENT = Independent,
1Reverse Acting 2Normal Acting
ACTION_ELEMENT = 1: Single Action
IO_ASSIgNMENT = 1: Top,Bot,Out0
SIgNAL_ACTION = 1: Increase to Close
ACTION_ELEMENT = 1: Single Action
IO_ASSIgNMENT = 6: Aux1,Aux2,Out1
SIgNAL_ACTION = 0: Increase to Open
10
ACTION_ELEMENT = Independent,
1Normal Acting 2Reverse Acting
ACTION_ELEMENT = 1 = Single Action
IO_ASSIgNMENT = Top,Bot,Out0
SIgNAL_ACTION = 0: Increase to Open
ACTION_ELEMENT = 1: Single Action
IO_ASSIgNMENT = 6: Aux1,Aux2,Out1
SIgNAL_ACTION = 1: Increase to Close
11
ACTION_ELEMENT = both Reverse
ACTION_ELEMENT = 1 = Single Action
IO_ASSIgNMENT = Top,Bot,Out0
SIgNAL_ACTION = 1: Increase to Close
ACTION_ELEMENT = 1: Single Action
IO_ASSIgNMENT = 6: Aux1,Aux2,Out1
SIgNAL_ACTION = 1: Increase to Close
TAble 2 - dIFFereNCes beTweeN dI blOCk ChANNels
dI.ChANNel block - discrete Input Channels
FPAC1 rev 2,3,4
FPAC2 rev 5
Notes
0
No Transducer Connection
0
No Transducer Connection
No change
9
Open/Close
9
TRD1: 0-Closed / 1-Opened
Same channel number and same functionality for valve 1
10
Open
10
TRD1: 0-Not Opened / 1-Opened
Same channel number and same functionality for valve 1
11
Close
11
TRD1: 0-Not Closed / 1-Closed
Same channel number and same functionality for valve 1
12
Open/Close/Stop
12
TRD1: 0-Closed / 1-Opened / 2-Stopped
Same channel number and same functionality for valve 1
13
Maskable Signal
13
TRD1: Maskable Signal
Same channel number and same functionality for transducer 1
14
Auxiliary Input
14
Auxiliary Input 1
Same channel number and same functionality for AuX1 input
15
Auxiliary Input 2
15
Auxiliary Input 2
Same channel number and same functionality for AuX2 input
16
Open/Close for second valve (when available) 29
TRD2: 0-Closed / 1-Opened
Channel number has changed. Same functionality for valve 2
17
Open for second valve (when available)
210 TRD2: 0-Not Opened / 1-Opened
Channel number has changed. Same functionality for valve 2
18
Close for second valve
211 TRD2: 0-Not Closed / 1-Closed
Channel number has changed. Same functionality for valve 2
-
-
212 TRD2: 0-Closed / 1-Opened / 2-Stopped
New channel functionality for valve 2
-
-
213 TRD2: Maskable Signal
New channel functionality for transducer 2
8.2 discrete Input (dI) Channels
For a complete description of the channels refer to IOMs VCIOM-05123 and TECH-485.