WESTLOCK CONTROLS CORPORATION
280 MIDLAND AVENUE, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
4/06/10
TECH-385Q/D.W.O. 19105
Page 5 of 5
3.
Field Wiring
See the warnings section of this document for important warnings
pertaining to the wiring of this unit. Remove and replace cover before
and after wiring, per instructions given in the Switch Adjustment section
above.
Required Tools: slotted screw drivers for terminal strip screws (#2), cover
screws (M4, #10 or 5/16 by model), and grounding screw (#8 or M4 by
model); wire strippers as required for field wires.
1.
Wire the AccuTrak monitor strictly according to the wiring diagram on the
inside of the enclosure cover.
2.
Confirm that the ground wire is secure under the green grounding screw in
the enclosure.
3.
Seal all unused conduit entries as required with suitably certified plugs
having an ingress protection rating of IP67 or better.
4.
Ensure that only suitably certified cable glands are used, having an
ingress protection rating of IP67 or better.
5.
Ensure that the temperature rating of all field wiring meets the service
temperature range of the application.