3.  

Field Wiring 

 

See the warnings section of this document for important warnings 
pertaining to the wiring of this unit. Remove and replace cover before 
and after wiring, per instructions given in the Switch Adjustment section 
above. 

Required Tools: slotted screw drivers for terminal strip screws (#2), cover 
screws (M4, #10 or 5/16 by model), and grounding screw (#8 or M4 by 
model); wire strippers as required for field wires. 

1. 

Wire the AccuTrak monitor strictly according to the wiring diagram on the 
inside of the enclosure cover. 

2. 

Confirm that the ground wire is secure under the green grounding screw in 
the enclosure. 

3. 

Seal all unused conduit entries as required with suitably certified plugs 
having an ingress protection rating of IP67 or better. 

4. 

Ensure that only suitably certified cable glands are used, having an 
ingress protection rating of IP67 or better. 

5. 

Ensure that the temperature rating of all field wiring meets the service 
temperature range of the application.

  