2.2.  Calibration 

Note 1:

 Switch actuation can be confirmed using a signal detection device    

such as a multimeter or ohmmeter, set for “continuity”. 
 

Note 2:

 For NAMUR P+F NJ2-V3-N type sensors, use test meter, P+F model 

#1-1350 or equivalent to check sensor actuation and calibration. If the proper 
meter is not available, contact the factory for additional assistance with the 
test procedure.  
 

Note 3:

  Adjust cams by hand by pushing/pulling the cam against the shaft 

spring to disengage from the mating spline, rotating to adjust and re-engaging 
firmly onto spline. 
 

Required Tools:

 Signal detection device (see note 1); slotted screw driver for 

cover screws (M4, #10 or 5/16 by model) 
 

Switch Adjustment (two switches): 
1. 

Remove unit cover as follows: loosen (but do not remove) captive screws, 
rotate cover slightly to grip corners, pull firmly.  
DO NOT PRY COVER WITH TOOLS. 

2. 

With valve in the closed position, adjust bottom cam until bottom switch 
(#2) actuates. 

3. 

Stroke valve to the open position, adjust top cam until top switch (#1) 
actuates. 

4. 

Cycle actuator several times to confirm proper switch indication at each 
end of stoke. Finely adjust cams if necessary.  

5. 

Skip to Field Wiring section or replace unit cover, applying approximately 
20 in-lbs of torque to cover screws. 

 
 

 

TOP CAM

TOP CAM

PUSH DOWN, TURN

PUSH DOWN, TURN

& RELEASE

& RELEASE

MAGNUM & MAGPAC

MAGNUM & MAGPAC

PROXIMITY

PROXIMITY

SWITCH

SWITCH

MECHANICAL

MECHANICAL

SWITCH

SWITCH

iNDUCTIVE

iNDUCTIVE

PROXIMITY

PROXIMITY

SENSOR

SENSOR

BOTTOM CAM

BOTTOM CAM

LIFT UP, TURN

LIFT UP, TURN

& RELEASE

& RELEASE

 

 

Отзывы: