26
WHL-001 REV. 9.3.14
The building owner is responsible for keeping the exhaust and intake terminations free of snow, ice, or other potential blockages, as
well as scheduling routine maintenance. Failure to keep the vent piping terminations clear and properly maintain the heater could result
in property damage, severe personal injury, or death.
For each floor containing bedroom(s), a carbon monoxide detector and alarm shall be placed in the living area outside the bedrooms,
as well as in the room that houses the heater. Detectors and alarms shall comply with NFPA 720 (latest edition). Failure to comply with
requirements for detectors and alarms could result in property damage, severe personal injury, or death.
E. EXHAUST VENT AND INTAKE PIPE SIZING
1. The exhaust vent and intake pipe size is 2".
2. The total equivalent length of exhaust vent and intake pipe should
not exceed 150 feet
.
a. The equivalent length of elbows, tees, and other fittings are listed in the Friction Loss Table, Table 5:
FRICTION LOSS EQUIVALENT IN PIPING AND FITTINGS
FITTINGS OR PIPING
EQUIVALENT FEET
2”
3”
90 DEGREE ELBOW*
5’
5’
45 DEGREE ELBOW
3’
3’
COUPLING
0’
0’
AIR INLET TEE
0’
0’
STRAIGHT PIPE
1’
1’
CONCENTRIC VENT KIT
3’
3’
V500 2” VENT KIT
1’
N/A
V1000 3” VENT KIT
N/A
1’
V2000 4” VENT KIT
N/A
1’
Table 5 - *Friction loss for long radius elbow is 1 foot less. NOTE: Consult Polypropylene venting instructions for friction loss and pressure
drop equivalents.
b. For example: If the exhaust vent has two 90° elbows and 10 feet of PVC pipe we will calculate:
Exhaust Vent Equivalent Length = (2x5) + 10 = 20 feet.
Further, if the intake pipe has two 90° elbows, one 45° elbow and 10 feet of PVC pipe, the following calculation applies:
Intake Pipe Equivalent Length = (2x5) + 3 + 10 = 23 feet.
Finally, if a concentric vent kit is used we find:
Total Equivalent Length = 20 + 23 + 3 = 46 feet.
The total equivalent length is 46 feet which is well below the maximum of 150 feet.
c. The exhaust vent and intake pipe are intended to penetrate the same wall or roof of the building.
d. Effort should be made to keep a minimum difference in equivalent length between the exhaust vent and intake pipe.
3. The minimum total equivalent length is 16 feet.
F. LONGER VENT RUNS
1. The maximum total equivalent length can be extended by increasing the diameter of both the exhaust vent and intake pipes.
However, the transitions should begin a minimum of 15 equivalent feet from the water heater.
a.
The maximum total equivalent length for increased diameter vent pipes is 200 feet.
b. Transitions should always be made in vertical sections of pipe to prevent the condensate from pooling in the vent pipe.
VENT CONNECTION
REDUCING COUPLING
VENT TRANSITION
2”
3” X 2”
3”
Table 6
– Vent Run Transition
c. Transition
from 2” to 3” pipe should be made at the water heater.
Do not exceed the maximum lengths for vent pipes. Excessive length could result in appliance shutdown and property damage.
Содержание WGR050LP076
Страница 34: ...34 WHL 001 REV 9 3 14 Figure 14...
Страница 53: ...53 WHL 001 REV 9 3 14 Figure 25 Replacement Parts...
Страница 54: ...54 WHL 001 REV 9 3 14 Figure 26 Replacement Parts...
Страница 57: ...57 WHL 001 REV 9 3 14...
Страница 58: ...58 WHL 001 REV 9 3 14...
Страница 59: ...59 WHL 001 REV 9 3 14 MAINTENANCE NOTES...