High heat sources (generating heat 100
o
F / 37
o
C or greater,
such as boiler flue pipes, space heaters, etc.) may damage
plastic components of the boiler as well as plastic vent pipe
materials. Such damages ARE NOT covered by warranty. It is
recommended to keep a minimum clearance of 8” from high
heat sources. Observe heat source manufacturer instructions,
as well as local, state, provincial, and national codes, laws,
regulations, and ordinances when installing this boiler and
related components near high heat sources.
Failure of the boiler or components due to incorrect operating
conditions IS NOT covered by product warranty.
4. Gas control system components must be protected from
dripping water during operation and service.
5. If the boiler is to replace an existing boiler, check for and
correct any existing system problems, such as:
•
System leaks
•
Location that could cause the system and boiler to
freeze and leak
•
Incorrectly sized expansion tank
6. Clean and flush system when reinstalling a boiler.
NOTE:
When installing in a zero clearance location, it may
not be possible to read or view some product labeling. It is
recommended to make note of the boiler model and serial
number.
Use extreme care not to drop the boiler or cause bodily injury
while lifting the boiler.
Gas conversion should be performed BEFORE the boiler is
installed. Carefully follow the gas conversion instructions
when performing the conversion.
Failure to follow these instructions could result in property
damage, severe personal injury, or death.
This boiler is approved for installation on combustible
flooring, but must never be installed on carpeting. Installing
this boiler on carpeting could result in fire, property damage,
severe personal injury, or death.
B. Flooring
Assure that the floor and structure of the installation location
are sufficient to support the full installed weight of the
boiler, including water content of the heat exchanger and
related piping. Failure to ensure the floor and structure of the
installation location are structurally sound before installation
of the boiler can result in structural failure, substantial
property damage, severe personal injury, or death.
C. Leveling
In order for the condensate to properly flow out of the
collection system, the area where you locate the boiler must
be level. Location must also fully support the weight of the
filled boiler.
Figure 2 - Correct and Incorrect Leveling
D. Clearances for Service Access
NOTE:
If you do not provide the minimum clearances shown in
Figure 3 it might not be possible to service the boiler without
removing it from the space.
NOTE:
A combustible door or removable panel is acceptable
front clearance.
The space must be provided with combustion / ventilation air
openings correctly sized for all other appliances located in the
same space as the boiler. The boiler cover must be securely
fastened to prevent the boiler from drawing air from the boiler
room. This is particularly important if the boiler is in a room with
other appliances. Failure to comply with the above warnings
could result in substantial property damage, severe personal
injury, or death.
All boilers eventually leak. It is recommended to install a catch
pan beneath the boiler. This catch pan should be sized with a
maximum depth of 2”, and a minimum diameter 2” greater than
the diameter of the boiler. The catch pan should empty into
an open drain line. This drain line should be 3/4” ID minimum,
piped to an open drain. Failure to follow these instructions could
result in property damage. Such damages ARE NOT covered by
product warranty.
This boiler must be installed upright in the vertical position as
described in this manual. DO NOT attempt to install this boiler
in any other orientation. Doing so will result in improper boiler
operation and property damage, and could result in serious
personal injury or death.
Содержание WBMC**500
Страница 36: ...WHL 033 Rev 1 29 16 36 Figure 27 Internal Connection Diagram ...
Страница 59: ...WHL 033 Rev 1 29 16 59 Figure 32 500 Combustion System Replacement Parts Model ...
Страница 60: ...WHL 033 Rev 1 29 16 60 Figure 33 850 Combustion System Replacement Parts Model ...
Страница 61: ...WHL 033 Rev 1 29 16 61 Figure 34 Water Side Replacement Parts All Models ...
Страница 62: ...WHL 033 Rev 1 29 16 62 Figure 35 Cabinet Replacement Parts All Models ...
Страница 69: ...WHL 033 Rev 1 29 16 69 Maintenance Notes ...