WHL-033 Rev. 1.29.16
63
Part 13 - Installation Checklist
Light Off Activities
Date Completed:
1. Fill the Heating System
Check all piping and gas connections.
Verify all are tight.
Pressurize system (12 - 15 psi).
PSI
Add water to prime condensate cup.
Verify near boiler piping is properly
supported.
Percentage of glycol in system (0 - 50%)
2. Check Gas Pipe
Leak test using locally approved methods
(consult jurisdictional code book).
Check incoming gas pressure (3.5 to 14”
WC).
Static WC
Check the “drop” on light off (less than 1”
WC).
Dynamic WC
3. Check Combustion
Check and adjust (if necessary) carbon
dioxide content.
%CO2 High Fire
%CO2 Low Fire
Check and adjust (if necessary) carbon
monoxide content.
ppm CO High Fire
ppm CO Low Fire
4. Check Electrical
Connections
Ensure all electrical connections of line
voltage (pumps, etc.) and low voltage
circuits (system sensor, outdoor sensor,
etc.) are properly wired.
5. Verify System Operation
Turn up thermostat to verify wiring
connections.
6. Record Ionization
Current
Check uA reading in the status menu (see
Start-Up section, this manual).
uA High Fire
uA Low Fire
7. System Setting
Verify system settings.
CH Setpoint
CH Differential
8. Indirect Water Heater
Verify safety and operation of the indirect
water heater. Record settings.
DHW Setpoint
DHW Differential
9. Convert the Boiler
(500 ONLY)
If necessary, convert the boiler to the
proper fuel type.
Locate the stickers in the appropriate
locations on the boiler.
Verify combustion settings after gas
conversion - Carbon Dioxide.
%CO2 High Fire
%CO2 Low Fire
Verify combustion settings after gas
conversion - Carbon Monoxide.
ppm CO High Fire
ppm CO Low Fire
Mail in conversion registration.
Notes:
Table 27 - Installation Checklist
Allowing the boiler to operate with a dirty combustion
chamber will hurt operation. Failure to clean the heat
exchanger as needed by the installation location could result
in boiler failure, property damage, personal injury, or death.
Such product failures ARE NOT covered under warranty.
In unusually dirty or dusty conditions, care must be taken to
keep boiler cabinet door in place at all times. Failure to do so
VOIDS the warranty.
The boiler requires minimal periodic maintenance under normal
conditions. However, in unusually dirty or dusty conditions,
periodic vacuuming of the cover to maintain visibility of the
display and indicators is recommended.
Periodic maintenance should be performed once a year by a
qualified service technician to assure that all the equipment
is operating safely and efficiently. The owner should make
necessary arrangements with a qualified heating contractor for
periodic maintenance of the boiler. Installer must also inform
the owner that the lack of proper care and maintenance of the
boiler may result in a hazardous condition.
Part 14 - Maintenance Report
Содержание WBMC**500
Страница 36: ...WHL 033 Rev 1 29 16 36 Figure 27 Internal Connection Diagram ...
Страница 59: ...WHL 033 Rev 1 29 16 59 Figure 32 500 Combustion System Replacement Parts Model ...
Страница 60: ...WHL 033 Rev 1 29 16 60 Figure 33 850 Combustion System Replacement Parts Model ...
Страница 61: ...WHL 033 Rev 1 29 16 61 Figure 34 Water Side Replacement Parts All Models ...
Страница 62: ...WHL 033 Rev 1 29 16 62 Figure 35 Cabinet Replacement Parts All Models ...
Страница 69: ...WHL 033 Rev 1 29 16 69 Maintenance Notes ...