Westinghouse PS-1002 Скачать руководство пользователя страница 25

ardized  units.  To  install  the  switchgear  adapter,  first  re­

move  the  adapter  housing if it  is  shipped  installed  on  the 

transformer  and  then  align  the  transformer  with  the 
switchgear.  When  aligned,  there  should  be  1 7  inches  be· 
tween  the face  of the  transformer  throat  and the  face  of 
the  switchgear  throat,  and  the  centerline  of the  switch­
gear  throat  should  coincide  with  the  centerline  of the  H2 
or  X2  bushing  in  the  transformer  throat.  Refer  to  the 
transformer  outline,  outline  details  and  station  plan 
drawings. 

Next,  bolt  the  flexible  connectors  to  the  switchgear 

bus  b ars.  The  number  of  flexible  connectors  supplied  are 
determined  by  the  transformer  current  and  not  by  the 

current  rating  of  the  bus  bar.  Check  the  length  of flexi· 
ble  connectors.  There  should  be  approximately  0.375 
inch  ( 1 0  mm) slack  to  permit  some  movement of the bus 
bars to expansion  and contraction and possible settling of 
the  transformer.  Next,  make  the  ground  bus connection 
between  the  transformer  an d  switchgear.  Before  reinstall· 
ing  the  adapter  housing,  check  electrical  clearances  as 
indicated  on  the  outline  drawing and the tightness of con­
nections  and  supports.  Complete  the  installation  by  as· 
sembling  the  housing.  Install  the  adjustable  plate  so that 
the switchgear throat is sealed  by the  gasket. 

6.6 

Pr

e

paratio

for Energization 

The  following  are  instructions  that  must  be  followed 
when  preparing  the  transformer  for  energization.  These 

instructions  provide  minimum  requirements  to  determine 
the  transformer's  readiness  for  service.  Check  off  e ach 
section as it is completed .  

1 .  ( 

) Pressure Test 

Check  the  integrity  of the  transformer tank  by  introduc­

ing  dry  air  or  dry  nitrogen  through  the  pressure  test  fit· 

ting  (this  may  be  identified  as  the  air  test  valve  or  gas 
sampling  valve  on  the transformer outline) until  a positive 

internal  pressure  of  3  to 

psig  is established.  Allow  the 

tank  to stand  for one  to two hours, then examine  the tank 
an d  fittings  for  leaks. 

leak  above the liquid level  can  be 

located  by  applying  a  soap  solution  to  all  joints,  pipe  fit· 

tings  and  cable  connections.  The  transformer  must  be 
de-energized when checked by this method. 

When  the  pressure  test  is complete, reduce the  internal 

pressure. 

2 .   ( 

) Insulating  Liquid  Test 

Before  energizing  the  transfom1er ,  the  liquid  must  be 

tested  in  accordance  with  Section  8 . I .   The  dielectric 

strength of new liquid must be 26  KV  or higher. 

3 .  

)  Insulation Meggar Test 

23 

To  insure  that  no  grounding  of  the  windings  exists,  a 

1 000  volt  meggar  test  and  a  power  factor  test  should  be 

made.  Refer  to  Section  8.3  for  allowed values  of  insula­
tion  resistance.  Compare  measured  insulation  power 
factor to the values measured at the factory. 

4. 

)  Ratio Test 

ratio  test  should  be  made  at  all  tap  positions  to  insure 

proper  transformer  ratios  and  tap  changer  connection . 

5 .   ( 

) C ontinuity Test 

There  should  be  a  continuity  check  of  all  windings.  If 
possible,  measure  the  winding  resistance  and compare  to 

the  factory  test  values.  An  increase  of more  than  1 0% 

could  indicate  loose  internal  connections.  Use  a  wheat· 
stone  or  Kelvin  Bridge 

not  an  ohmmeter  to  measure 

resistance. 

6.  ( 

) Connections 

Proper  connections  must  be  made 

before 

the transformer 

is  energized.  Check  all  electrical  connections  to  be  sure 
they  are  made  to  the  correct  terminal  and  are  mechan­

ically  secure.  Check the  following items: 

DO  NOT  CHANGE  CONNECTIONS  ON  A  TRANS­

FORMER  THAT  IS  ENERGIZED  NOR  MAKE  ANY 

CONNECTIONS  EXCEPT  AS  AUTHORIZED  BY  THE 
NAMEPLATE  OR  CONNECTION  DIAGRAM.  TO  DO 
SO  WILL  CAUSE  DANGER  TO  LIFE  AND  DAMAGE 
TO PROPERTY. 

)  a)  Line  connections  must  be  made  without 

placing more  than  1 00  pounds  cantilever force  on Type 
RCP,  Type 

RJ 

( 1 5   KV  and  below)  and  all  cast  resin 

and  cast  resin  welded  bushings.  Above  1 5   KV,  exter­
nal  connections  must  not  impose  strains  on  the  bush­
ing  in  excess  of  those  specified  by  Table  8,  ANSI 
STANDARD  C76.2 - 1 977.  Bushings  should  be checked 

for  cleanliness  at  time  connections  are  made  and 

cleaned if necessary . 

CAUTION 

A  loose  connection  will  result  in  a hot joint causing daD1· 

age  to the adapter and could cause transformer failure. 

Содержание PS-1002

Страница 1: ...gencies which may arise during installation operation or maintenance and all details and varia ions of this equipment do not purport to be covered by these instructions If further information is desired by purchaser regarding his particular installation operation or maintenance of his equipment the local Westighouse Electric Corporation representative should be contacted ...

Страница 2: ...ove 25 Kv class 13 5 13 3 Wall Mounted Bushings 2 5 Kv 25 Kv class 17 5 14 Lightning Arresters 18 5 15 Current Transformers 20 5 16 Inertaire 20 5 17 Radiators 20 6 INSTALLATION 21 6 1 Precautions 21 6 2 Location and Mounting 22 6 3 Assembly 22 6 4 Filling in the Field 22 6 5 Air Terminal Chamber and Switchgear Adapter Installation 22 6 6 Preparation for Energization 23 7 OPERATION 24 7 I Basic Tr...

Страница 3: ...cement is recommended rather than repair If information is desired in greater detail copies of in struction leaflets referred to but not included with this book can be obtained by contacting your Westinghouse Sales Office 2 RECEIVING NOTE INSPECTION OF TRANSFORMER PACK AGES AND PARTS IS REQUIRED PRIOR TO UN WADING FROM CARRIER IN ORDER TO ESTAB LISH THE CONDITION OF THE EQUIPMENT UPON DELIVERY 2 1...

Страница 4: ...plug a thread at a time until the pressure starts to relieve itself I CAUTION I The fdling plug can be blown off if the plug is removed from a pressurized transformer too quickly Personnel could be injured by the plug Oil or oil vapor could be expeUed creating a fire hazard b Ventilate the gas space with dry air to purge it of the nitrogen gas that it contains Refer to Section 8 6 ltM dbWil TO AVO...

Страница 5: ...ovided on the transformer tank wall Only these hooks can be used in lifting the complete transformer Refer to the outline for the proper lifting hook locations All four lifting hooks must be used for proper handling CAUTION Lifting the transformer in places other than the tank wall lifting hooks may result in damage to the transformer causing oil leaks It may also result in the dropping of the tra...

Страница 6: ...replace the bags and the silica gel before storing Type 0 bushings must be stored with the top end elevated at an angle of at least 20 from the horizontal above the bottom end A check of oil height and of power factor and capacitance should be made before putting an oil filled condenser bushing into service after prolonged stor age Refer to Westinghouse Bushing Manual T D 33 360 for instructions o...

Страница 7: ...IRAISFORIER IS DESIGNED FOR OPERl IOI BEIIEEI PRESSURE LilliS OF 6 5 LBS PER SOUlRE IICH POSIIIIE U0 1 5 LBS PER SQUIRE IICI IEGliiiE Fig l Typical Nameplate THIS IRINSfORMER Will CIRRY7000 m WITHOUT EXCEEDING 65 C AVERAGE IEMPERITURE RISE IHEN IOEOUIIE COOLING EQUIPMENT IS IOOEO THE 15 C LIOUIO lEVEl IS I 0 00 INCHES BElOW TOP OF HIGHEST MANHOlE flANGE LIOUIO lEVEl CHANGES 0 50 INCHES FOR EACH 10...

Страница 8: ...tch position and of inter nal terminal boards when present 13 NOTES AND WARNINGS The notes below the connection chart contain important information for use in operation and maintenance Read the notes because spe cial features or warnings will be in the nameplate notes 14 PHASE RELATION The phase rotation and phase angle shift between the high voltage and low voltage is represented by a phasor diag...

Страница 9: ...out appreciably helping the transfer of heat from the oil to the sensitive element The thermom eter should not be tightened in the well any more than is necessary to place the dial in an upright position Fig 3 Front and Side View ofIndicator with Alarm Contacts 7 The thermometer can be furnished with a Single pole single throw contact for fan starting and a Single pole double throw contact for hig...

Страница 10: ...re normally fur nished with a mechanical pressure relief device on the Fig 4 ReliefDel ice in Sealed Position transformer cover The device consists of a self resetting spring loaded diaphragm and a mechanical operation in dicator semaphore Should the tank pressure increase above 10 psig the gas pressure will lift the diaphragm and vent the excess pressure Immediately after the pressure returns to ...

Страница 11: ...uge A red pointer is furnished to show the highest tern perature attained since last reset and is resettable by means of a push button projecting through the bottom of thedial bezel The gauge has four single pole normally open con tacts with normal settings of 70 75 112 and 117 C 9 Fig 5 Front View of Winding Temperature Gauge Should it become necessary to adjust any of these con tacts from the ab...

Страница 12: ... relay may fail when vacuum is pulled on the transformer A seal in relay reset switch and the associated circuitry are mounted in a separate control cabinet The seal in re lay is energized when the sudden pressure micro switch operates and remains so until manually reset with the re set switch Seal in relay loads should be limited to the values given in the table listing given on the wiring dia gr...

Страница 13: ...ng temperature The circuit is energized from the load side of the panel power circuit The manual auto switch provides a 11 means of starting the fans independently of the position of the thermal switch With the thermal switch in the closed position the fans may be stopped by opening the AB breaker An Auto Off Manual switch is supplied in stead of the Manual Auto switch when requested by the custom...

Страница 14: ...re used See Fig 9 DRAW LEAD TERMINAL TERMINAL CAP i ifl g ffLING SILICONE RUBBER L GASKET Fig 9 Typical Cross Section of RJ Draw Lead Bushing installation of RJ Draw Lead Connection The terminal which is crimped to the draw lead has a steel pin pressed through a hole in the terminal diameter below the threads About 1 4 inch of pin extends on both sides of the terminal to engage a slot inside the p...

Страница 15: ...ed for voltage classes of 34 5 KV and above Westinghouse bushing Types RCP OS and 0 are normally supplied Each bush ing consists principally of a cylindrical condenser assem bly protected on its outer end with a porcelain weather casing made by the wet process The space between the condenser and the weather casing is filled with a high di electric strength compound or WEMCO C transformer oil depen...

Страница 16: ...INS EXPANSION BOWL FLANGE VALVE SEALING GASKET GASKET STOP FLANGE BOTTOM PORCELAIN TERMINAL CAP RETAINING GASKET rr MAGNETIC GAUGE GASKET AND STOP PORCELAIN __ TOP PART OF OIL CHAMBER OIL IMPREGNATED KRAFT PAPER CONDENSER WITH METAL FOILS SCREW CAN BE REMO VED TO REPLACE GAUGE GLASS OR DIAL VOL TAGE TAP RECEPTACLE NAMEPLAT E SEALING GASKET AND GASKET STOP BOTTOM PART OF OIL CHAMBER BOTTOM TERMINAL...

Страница 17: ... CAST RESIN CONDENSER CONFINED GASKET ___ _r ON COVER BOSS NOTE CONDENSER DETAILS OMITTED IN SECT IONED AREAS FOR CLARITY PURPOSES MINIMUM OIL LEVEL LEAD COVERED WITH TAPE I 12 THREADED STUD A Bushing with Draw Through Cable Lead B Bushing with Threaded End Conductor Fig 12 Outdoor Condenser Bushings Type RCP 15 ...

Страница 18: ... other sharp objects that could damage the con denser When cleaning the condenser use a clean cloth saturated with transformer oil It is recommended that condenser bushings which have been removed for shipment have the power factor and capacitance measured before they are installed in the transformer to find if internal shipping damage has oc curred This may avoid expensive disassembly from the tr...

Страница 19: ...ectors must not impose strains on the bush ing in excess of those specified by Table 8 ANSI Standard C76 2 1 977 Limit the cantilever load to 100 pounds on type RCP type RJ IS KV and below and all cast resin and cast resin welded bushings Greater force may cause bushing damage that can result in violent trans former failure 1 7 5 13 3 Wall Mounted Bushings 2 5 K V 25 K V Class Fig 14 Cast Resin Bu...

Страница 20: ...ible connections to the air or liquid ends of the bushing conductor in order to limit the thermal ex pansion forces on the bushing As a general rule a maxi mum cantilever or axial load of 1 00 pounds acting at the end of the bushing conductor should not be exceeded For detailed instructions on application installation or replacement request Instruction Leaflet 47 OS 1 1 for the weld on version or ...

Страница 21: ... BODY 0 0 NO N MAG N ET I C BUSH I NG P LAT E I NTEG RAL PART OF X FO R M E R TAN K S I L I CO N E 0 R I NGS 0 0 0 0 LI QU I D S I D E Non M agnetic B ushing Plate I ntegral Part 0 0 Cast Epoxy Body Aluminum Clamping Flange of X Former Tank R eta ined Cork Buna N or N itrile Gasket Stai n less Steel F lange Sil icone 0 R i ngs 0 0 0 0 Liquid Side 19 ...

Страница 22: ...rmer is shipped CURRENT TRANSFORMER SECONDARY LEADS MUST BE CONNECTED TO A LOAD OR SHORT CIR CUITED WHEN THE TRANSFORMER IS ENERGIZED IF THE SECONDARY LEADS ARE OPEN EX TREMELY HIGH PEAKS OR PULSES OF VOLTAGE ARE PRESENT AT THE SECONDARY TERMINALS THESE HIGH PEAKS OF VOLTAGE MAY NOT REG ISTER ON CONVENTIONAL VOLTMETERS BUT THEY CAN BREAK DOWN INSULATION AND ARE DANGEROUS TO PERSONNEL 5 1 6 Inertai...

Страница 23: ...iding Transformer Damage Transformers are generally shipped sealed and ready for energizing without opening the tank In cases where it is necessary to open the tank for changing terminal board connections or installing high voltage bushings extreme care is required to protect the insulation from damage Internal parts are located to provide the necessary elec trical clearances and must not be bent ...

Страница 24: ...efore removing manhole bolts Internal pressure can blow the manhole cover off injuring person nel If possible fill transformers shipped in dry gas with fluid before opening the tank When the transformer can not be filled with fluid before the tank is opened limit the total open time to 24 hours Refer to Sections 8 4 through 8 6 for instructions on liquid filling and ventila tion of transformer tan...

Страница 25: ...tings for leaks A leak above the liquid level can be located by applying a soap solution to all joints pipe fit tings and cable connections The transformer must be de energized when checked by this method When the pressure test is complete reduce the internal pressure 2 Insulating Liquid Test Before energizing the transfom1er the liquid must be tested in accordance with Section 8 I The dielectric ...

Страница 26: ...ON THE POWER FACTOR TEST TER MINAL THE TERMINAL MAY FLASHOVER LIFE COULD BE IN DANGER 7 Make a physical examination of control circuit wiring and alarm devices Look for cut or broken insulation and open connections 8 Liquid level should be at the correct level according to Section 5 4 Table 2 9 Refinish all paint scratches See Section 8 8 10 Tighten all external bolts and hardware Check handholes ...

Страница 27: ...rature of the air for any 24 hour period should not exceed 30 C 86 F The dial thermometer should read less than the sum of the maximum ambient temperature and the rated temperature rise during normal operation That is the maximum top liquid temperature for a 5 5 C rise transformer is 95 C and 1 05 C for a 65 C rise transformer The transformer s useful life will be short ened if the transformer is ...

Страница 28: ...move a bolted hand hole runs the risk of being hit by the cover if the internal pressure is not vented first 3 Oil filled transformers present a fire h azard to the in stallation area All liquid leaks must be repaired imme diately because transformer liquid is very flammable 4 Should an internal arc occur in the unit the internal pressure will increase and may increase so rapidly that the tank may...

Страница 29: ...airly represents the liquid in the tank A sufficient amount of liquid should therefore be drawn off before the sample is taken to insure that the sample will not be that which is stored in the sampling pipe If the sample taken contains free water it is not suitable for dielectric tests and the sample should be discarded A second sample should then be taken after at least two quarts of liquid have ...

Страница 30: ...perations specified in the following are intended to be accomplished as contin uous uninterrupted processes Insulation Resistance Temperature Correction Transformer Correc Transformer Correc Tempera tion Tempera tion ture C Factor ture C Factor 9 5 8 9 0 3 5 2 5 9 0 6 6 0 3 0 1 8 8 5 4 9 0 2 5 1 3 8 0 3 6 2 2 0 1 0 7 5 26 8 1 5 0 7 3 7 0 2 0 0 10 0 5 4 6 5 14 8 5 0 4 0 6 0 1 1 0 0 0 3 0 5 5 8 1 5 ...

Страница 31: ...ngs Drain any liquid which was not drained before repairs were made Apply the required vacuum level prior to fill ing and hold it for the specified time according to Table 4 If the time the core and coil assembly is out of liquid be fore evacuation for refilling is started does not exceed 16 hours liquid flow into the tank may start as soon as the required vacuum is obtained Then admit liquid into...

Страница 32: ... conserve dry air place a light cover of ply wood hardboard or plastic over the manhole opening The work should be performed in a sequence such that when accessories such as bushings are being installed only one opening other than the manhole will be open at any time Dry Air and Nitrogen When nitrogen is called for the nitrogen used should have a dewpoint not higher than 50 C 58 F and total impuri...

Страница 33: ...1 leaflets may be obtained through the nearest Westing house Sales Office Removing and Replacing Welded On Covers I L 47 600 2 1 Instructions for Repairing Tank Leaks l L 48 069 20 Cleaning Transformer Insulation LL 48 069 13 9 REPAIR 9 1 It is the responsibility of the owner to inspect main tain and keep the transformer in good repair 9 2 Report all failures during the warrantee period to your We...

Страница 34: ...2 or Instructions for Han dling WEMCO FR Insulating Oil LB 47 053 l I CAUTION I When working inside a transformer tank extreme care must be exercised to avoid dropping tools or other objects into the core and coils or into the tank Objects dropped on the coils or left in the tank can cause a fai lure to the transformer 9 10 The core and coil assembly can be repaired or re placed by Westinghouse pe...

Страница 35: ...MEMORANDUM ...

Страница 36: ...PS 1 002 479 979 Supercedes PS 1 001 1 076 Printed in U S A ...

Отзывы: