PD060-135
Control Settings

 

 

Pressure Actuated

Fan Cycling Pressure Control

(Adjustable)

High Pressure Control

(Manual Reset)

Low Pressure Control

(Auto  Reset)

Oil Pressure Safety Control

(Non-Adjustable)

Manual Reset

Legend Factory Setting

FCP 1 Cut-In 280 PSIG

FCP2

cut-out 170 PSIG

HP 1 Cut-In 300 PSIG

H P 2   cut-out 365 PSIG

LP 1 Cut-In 25 PSIG

L P 2   cut-out 5 PSIG

OP1

OP2

Cut-Out Pressure

OP3

Differential 9 PSIG

OP4

Receiver Pressure Control

(Optional Heated Receiver)

Low Pressure Freeze Control

(Manual Reset)

P1

P 2

LPF 1

LPF 2

Cut-In

cut-out

cut-out

180 PSIG

210 PSIG

48 Psig

Temperature Actuated

Chiller Low Water Temperature

Thermostat

Legend Factory Setting

T1

cut-out 37°F

Chiller Water Cycling

Thermostat (Adjustable) T 2   Dial Set At 

Fan Cycling Ambient

Thermostat (Adjustable)

FCT 1 FCT 1

Cut-In

cut-out

FCT 2 FCT 2

Cut-In

cut-out

FCT 3 FCT 3

Cut-In 38°F

cut-out

Chiller Heater Thermostat

(Non Adjustable)

Receiver Heater Thermostat

(Optional Heated Receiver)

(Optional Heated Receiver)

T 3   Cut-In

cut-out

 F

T 4   Cut-In

T 5   cut-out

Unit Operating Limitations

1.

2.
3.
4.
5.
6.

Maximum ambient air to condenser is 1 

For minimum ambient operation (see winter control data page 3).

Maximum allowable cooler water pressure is 150

 PSIG.

Maximum allowable water temperature to cooler is 
Units must not have leaving water temperatures of 

 or lower unless provided with  capacity control or used with a glycol  solution.

Unit must be allowed to pump down at the end of each operating cycle (except on safety control shut down.) Where timeclock shut down, low
ambient lock out or remote manual shut down is required consult factory.

Содержание PD06OD

Страница 1: ......

Страница 2: ...accessible to servicing Drain connections should be provid ed at all low points to permit complete drainage of chiller and piping system The chiller water piping should be insulated to reduce heat pic...

Страница 3: ...As a result the unit may cycle on low pressure con trol with the possibility of evaporator freezing Westinghouse offers two types of system con trol allowing the units to operate at the winter ambien...

Страница 4: ...2 Dial Set At 55 F Fan Cycling Ambient Thermostat Adjustable FCT 1 FCT 1 Cut In 75 F cut out 72 F FCT 2 FCT 2 Cut In 55 F cut out 52 F FCT 3 FCT 3 Cut In 38 F cut out 35 F Chiller Heater Thermostat N...

Страница 5: ......

Страница 6: ......

Страница 7: ...s Cl C3 C5 C7 respectively to energize fan contactor C9 when the high side pressure in creases to the cut in setting of FCP1 or FCP2 fan cycling pressure controll Fan Motor M2 and M3 are energized thr...

Страница 8: ......

Страница 9: ...tacts CIA C3A C5A C7A of contactors Cl C3 C5 C7 respectively to energize fan contactor C9 when the high side pressure in creases to the cut in setting of FCP1 or FCP2 fan cycling pressure control Fan...

Страница 10: ......

Страница 11: ...m g All lead connections tight h Wiring complies with local codes a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated a All belts adjusted...

Страница 12: ...ssure switch checked Yes Low pressure freeze control If part winding start time delay is Temperature of air entering condenser Temperature of air leaving condenser Temperature of Chilled Water enterin...

Отзывы: