Westinghouse KD Скачать руководство пользователя страница 20

2  SEC. OHM 

M IN. 

184A529 

Fig. 

3. 

Out- of-S tep  Blocking O perations. 

separately  fused  supply,  along  with  the  phase  back­
up  relays. 

Transmitter  Control 

Break  contacts,  Z S  (ZS·¢¢ 

'ZB-3¢) 

los• 

85 

CO  contact 

7-8, 

and  the- test  pushbutton  break  con­

tact,  PB,  in  fig.  2,  connect  the  transmitter  "start" 

lead to minus.  When any one of these  contacts  opens, 

the  "start"  lead  is  connected  to  positive  through 
resistor,  R2.  This  positive  potential  will  key  the 
transmitter  on  (or  shift  the  frequency,  when  a  fre­
quency  shift  channel  is  utilized),  to  block  remote 
breaker  tripping,  provided that  the  "stop "  lead  is  not 
tied  to  minus,  through  contact  CSP  or  CSG.  CSP 

CSG  coils  are  energized  by  ZP 

D0  contacts,  re­

spectively, so that any time  a fault  is  detected  in  the 
trip  direction  the  "stop"  lead  is  tied  to  minus  to 

prevent  transmission  of  a  blocking  signal.  Thus,  the 

stop  lead  has  precedence  over  the  start  lead.  If,  for 

example,  the  channel  is  being  used  for  voice  com­
munication  at  the  instant  of  an  internal  fault,  the 

stop  circuit  will  interrupt  transmission  to  permit 

tripping,  provided that either ZP  or  D0  operates. 

A  blocking  signal  is  required  from  breaker  B, 

fig. 

1 , 

during  an  external  fault  because  the  phase  or 

ground  tripping  units  would  otherwise  trip  at  breaker 

A. 

At  breaker  B  either  the  10s  or  the 

ZS 

contact 

opens  to  put  positive  voltage  on  the  start  lead;  since 

neither  the  CSP  nor  the  CSG  contacts  close  at  B 
the  stop  lead  is  not  energized,  and,  therefore,  a 
blocking  signal  is transmitted. 

Receiver  Relay  Comparison  Circuits 

Receiver  relay,  RR,  has an  RRH  holding coil and 

an  RRT  tripping  coil  as  shown  in  Fig.  2.  RRH  is 
energized  by  the  receiver  output  when  a  blocking 

signal  is  transmitted;  RRT  coil  is  energized  when­

ever  the  local  tripping  relay  contacts  close  in  an 
attempt  to  tri p  the  breaker.  RRH  coil  current  holds 
the  RRP  and  RRG  contacts  open;  RRT  coil  current 

closes  the  RRP  and  RRG  contacts  in  the  absence  of 

RRH  coil  current. 

Tliis  is  the  key  point,  which 

produces  the  comparison  function  - the  force  pro­

duced  by  RRH  current  is  stronger  than  the  opposing 
force produced  by RRT  current,  so  that  the  RRP  and 
RRG  contacts  will  be  closed  by  RRT  current  only 
when no  blocking  signal is  received. 

In  Fig.  1,  ZP  or  D0 

I0  contacts  close  at breaker 

A  whether  the  fault  is  internal,  or  external  to  the 
right  of  breaker  B;  in  either  case,  CSP  or  CSG  is 
energized  and  RRT,  in  turn,  is  energized.  For  the 

external  fault  only,  the  transmitter  at  B  sends  a 

blocking  signal,  which  produces  a  receiver  output  at 
A,  which energizes  the  RRH  coil  to  prevent  RRP  and 
RRG  contacts  from  closing;  thus,  tripping  is  pre­

vented. 

Conversely,  for  an  ihternal  fault,  tripping 

units  operate  at  both  stations  to  energize  CSP  or 
CSG  contacts  to  prevent  transmission  of  a  blocking 
signal;  another set  of  CSP /CSG contacts energize t he 
RRT  coil.  Since  neither  station  receives  a  blocking 
signal,  both  RRH  coils  are  deenergized;  both  RR 
relays  operate  to  close  their  RRP  and  RRG  contacts 
to  permit  either  ZP  or  D0 

I0  contacts  to  energize 

the  trip  coil. 

A  reactor  is  shown  in  series  with  the  RRT  coil 

in  fig.  2.  This  reactor  is  used  only  with  audio  tone 
or  frequency  shift  carrier  channels,  where  the  channel 
delay  time  is  abnormally  large.  This  reactor  delays 
RRT  coil  current  buildup  long  enough  to  compensate 

for  the  RRH  coil  current  buildup  time  occasioned  by 

the  channel  delay. 

Otherwise  undesired  tripping 

might occur before  a  blocking signal  can  be  received. 

Operation  will  now  be  summarized. 

External  Phase  Fault  Operation 

Refer  to  Table  I,  which  tabulates  external  phase 

fault  functioning  at  the  top.  The  external  fault  is  to 
the  right  of  breaker  B  as  shown  in  the  upper  left  of 
Table  I. 

At  breaker  B, 

Z'S 

contact  opens  and  the  ZP  con­

tact  remains  open,  so  that CSP  is  not  energized;  the 
start  lead  is  at  positive  and  the  stop  lead  is  open, 

www 

. ElectricalPartManuals 

. com 

Содержание KD

Страница 1: ...his system can be utilized with minor differ ences with either on off or frequency shift type of operation over pilot wire tones microwave or power line carrier channels Blocking of tripping is ef fected by either keying on or shifting the transmitter frequency EQUIPMENT COMPLEMENT K Dar is the designation for a group of relays which are itemized below Directional Fault Detecting Relays 1 Type KD ...

Страница 2: ... UNIT OF KA RELAY CURRENT POLARIZEO OIRECTIOMAL UNIT OF XRO RELAY VOLTAGE POLARIZEO OIRECTIONAL UNIT OF XRO RELAY INOICATING CONTACTOR SWITCH OF XO XRO RELAYS GROUNO OVERCURRENT TRIP UNIT OF XRO RELAY GROUMO START OVERCURRENT UNIT OF KA RELAY MILLIAMMETER OPERATION INOICATOR OF KA RELAY AUXILIARY UNIT OF XS RELAY REC 1VER RELAY UNIT CONTACTS OF XA RELAY HOLDING COIL OF RECEIVER RELAY UNIT OF KA RE...

Страница 3: ...ws an optional time delay backup path through T3 contact which bypasses the RRP contact circuit T3 contact TX Z3 coil are from the TD 2 timing relay which is associ ated with an independent 2 zone distance backup circuit not shown Operation of ZP energizes TX Z3 coil which starts the timer If the fault either internai or external is not cleared by other means the breaker will be tripped after time...

Страница 4: ...duces a receiver output at A which energizes the RRH coil to prevent RRP and RRG contacts from closing thus tripping is pre vented Conversely for an ihternal fault tripping units operate at both stations to energize CSP or CSG contacts to prevent transmission of a blocking signal another set of CSP CSG contacts energize t he RRT coil Since neither station receives a blocking signal both RRH coils ...

Страница 5: ...OPEN OPEN GROUND Do CSG CSG ENERGIZES CLOSES CLOSES CSG Do CSG CSG ENERG I ZES CLOSES CLOSES CSG RRH COIL C3 R M RCVR FAUI T RRH ENERGIZED RRH DE ENERGIZED NOTE I FAULT RRH DE ENERGIZED RRH DE ENERGIZED FAULT RRH ENERGIZED RRH DENER GIZED FAULT RRH DE ENERGIZED RRH DE ENERGIZED TRIP CIRCUIT zp tOo I Iro R 2a c RRP RRG HELD OPEN BY RRH CURRENT RRP RRG HELD OPEN BY MAGNETIC BIAS NOHI TRIP THROUGH ZP...

Страница 6: ...swing describes an arc which intersects the Z circle at point Q and ZP 3 circle at point OS P During an out of step condition the Z0s contact in figure 2 opens before ZP 3 contact closes OS 6 unit is energized and after 4 cycles an OS con tact opens the ZP 3 trip circuit All this occurs before the swing reaches point P in Fig 3 During a fault the ZP 3 contact closes almost at the same instant that...

Страница 7: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 8: ...WESTINGHOUSE ELECTRIC CORPORATION RELAY DEPARTMENT NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 9: ...line carrier channels Blocking of tripping is ef fected by either keying on or shifting the transmitter frequency These instructions contemplate the use of separate primary and back up relays in line with local back up philosophies Fig 4 shows the details of this arrangement This contrasts to the previous 3 zone system where the zone 2 phase distance units provided carrier tripping as well as back...

Страница 10: ...ECTIONAL UNIT OF KRD RELAY ItS IRDICATIRG CONTACTOR SWITCH OF KO KRD RELAYS Io GROUND OVERCURREMT TRIP UIU T OF KRD RELAY los GROUND START OVERCURRENT UNIT OF KA RELAY MA M I LLIA14HETER 01 OPERATION INDICATOR OF KA RELAY OS AUXILIARY UNIT OF KS RELAY RRG RRP RECEIVER RELAY UNIT CONTACTS OF KA RELAY RRH HOLDING COIL OF RECEIVER RELAY URIT OF KA RELAY RRT TRIPPING COIL OF RECEIVER RELAY URIT OF KA ...

Страница 11: ...A fig 1 also operate for faults on the adja cent system therefore the ZP contacts must be supervised by a contact which does not close during external faults This supervising contact is RRP in fig 2 For internal faults the RRP contact closes to permit one of the ZP contacts to energize the breaker trip coil 52 TC The trip path is from positive through ICS coil ZP or ZP 3 OS contacts 85 CO contact ...

Страница 12: ...oil current holds the RRP and RRG contacts open RRT coil current closes the RRP and RRG contacts in the absence of RRH coil current Tliis is the key point which produces the comparison function the force pro duced by RRH current is stronger than the opposing force produced by RRT current so that the RRP and RRG contacts will be closed by RRT current only when no blocking signal is received In Fig ...

Страница 13: ...OSES NOTE 2 CSG los Do CSG CSG BKQ B OPENS ENERGIZES CLOSES CLOSES NOTE 2 CSG RRH COIL J R M RCVR FAULT RRH ENERGIZED RRH DE ENERGIZED HlOTE I FAULT RRH DE ENERGIZED RRH DE ENERGIZED FAULT RRH ENERGIZED RRH DENER Gl ZED FAULT RRH DE ENERGIZED RRH DE ENERGIZED TRIP CIRCUIT zp Do I Ira c 2a c RRP RRG HELD OPEN BY RRH CURRENT RRP RRG HELD OPEN BY MAGNETIC BIAS NOTEI TRIP THROUGH ZP RRP TRIP THROUGH Z...

Страница 14: ...00 2000 CCnHACT _3_ _4 S 6 7 8 hf c t r o X DENOTES CONTACT CI O EO I I I I I CJc I I SAME AS ZONE 1 ZONE 2 INTERNAL 5CHE IVIA TICS DEVICE NO DEVICE DWG t JO 43 RECL ON O F iOGoGLE SW DS41 f 9 85 CO C l R ON OFF S oo ITCH 85 P8 DEVICE No C A R TE T P SH BUTTON CAR D C SUPPL Y ON OFF TOUGLE SWITCH KR SLHT DEl UNIT 250VO TRESI TOR UNIT RELAY DS 41 GOO F 14 r C z c 1 C z oc Nc E t c i KD ZONE 2 KD PI...

Страница 15: ...15 1 0 t 1 85Z co TIME DISTANCE PLOT 21 Z 21 J rz o j 21 S o r _ _ _ _ _ _ 1 _ _ _ _ _ _ _ I P CARRIER POS DJ t c J L C L II BA CK UPRELAYING 7NT iO i01 Th 1M n 10 2 RT 1X L l l 1 1 2 Th TM lCS _ q 3 ill w II RECLOSINC CIRCUIT Pos t 1 0 IOI SC sl co 79 16 79X T 19 f bb 0 TO CLOSING CKT 7 OR 60LN 52X NEG r 19M l 79Z 791 T 14 s o 791 ill 5 15 Fig 4 Detailed schematic of the K Dar 4 zone directional ...

Страница 16: ...ult value ZLoad to the fault value represented by the line 0 F in Fig 3 When a swing or out of step condition occurs the imped ance seen by Z0s ZP changes gradually as the voltage decreases and the current increases In Fig 3 the swing describes an arc which intersects the Z0s circle at point Q and ZP 3 circle at point P During an out of step condition the Z0s contact in figure 2 opens before ZP 3 ...

Страница 17: ...power line carrier channels Blocking of tripping is ef fected by either keying on or shifting the transmitter frequency These instructions contemplate the use of separate primary and back up relays in line witli local back up philosophies Fig 4 shows the details of this arrangement This contrasts to the previous 3 zone system where the zone 2 phase distance units provided carrier tripping as well ...

Страница 18: ...C 85CO 290Bl54 ALARM UNIT OF KA 4 RELAY GROUND AUXILIARY UNIT OF U 4 RELA Y ASE AUXI LIARY UNIT OF KA 4 RELAY CURRENT POLARIZED 0IRECTI OMAL UN IT OF KRD 4 RELAY VOLTAGE POLARIZED DIRECTIONAL UNIT OF KR0 4 RELAY INDICATING CONTACTOR SWITCH Of KD4 KR0 4 RELAYS GROUND OVERCURREMT TRIP UNIT OF U0 4 RELAY GROUND START OVERCURRENT UNIT OF KA 4 RELAY Ml LLIANMETER OPERATION INDICATOR OF ICA 4RELAY AUXIL...

Страница 19: ... 1 also operate for faults on the adja cent system therefore the ZP contacts must be supervised by a contact which does not close during external faults This supervising contact is RRP in fig 2 For internal faults the RRP contact closes to permit one of the ZP contacts to energize the breaker trip coil 5 2 TC The trip path is from positive through ICS coil ZP or ZP 3 OS contacts 85 CO contact 1 2 ...

Страница 20: ...ontacts open RRT coil current closes the RRP and RRG contacts in the absence of RRH coil current Tliis is the key point which produces the comparison function the force pro duced by RRH current is stronger than the opposing force produced by RRT current so that the RRP and RRG contacts will be closed by RRT current only when no blocking signal is received In Fig 1 ZP or D0 I0 contacts close at bre...

Страница 21: ...TE 2 CSG Do los CSG CSG BKA B OPENS ENERG I ZES CLOSES CLOSES NOTE 21 CSG R R H C O I L c r R M RC I R FAULT RRH ENERGI ZED RRH DE ENERGIZED NOTE I FAULT RRH DE ENERG IZED RRH DE ENERGIZED FAULT RRH ENERGIZED RRH DENER Gl ZED FAULT RRH DE ENERGIZED RRH DE ENERGIZED T R IP C I RCUIT zp I Do I Iro R c 2o c RRP RRG HELD OPEN BY RRH CURRENT RRP RRG HELD OPEN BY MAGNETIC BIAS NOTEI TRIP THROUGH ZP RRP ...

Страница 22: ...DEVICE NO 21 1 2 s 6 T 67N 67NT t 67N1 61tH J L 7 84LH sox 5AME A S Z O N E I ZONE Z INTfRNAL I I S C EMATICS OEVte E C i QW OFF 10 5tr S CA ON OF SWITCH CAR TEST 1 If SI IET OFT UN r 250 v J 7 liE SISTO IJlQCIUNG DIODE ON I KO ii ON E 2 Kl PIL O T T R I P 0 4 N MG Ei B R FAIL IWX BKR FAIL AU KRD 4 K R P I R P SGR 12 A M T OX K0 3 CUR T DETE TOR DW5 NO S OifASJS t A s 1 8 4 A I s 62 A S I 1 29 A 7...

Страница 23: ...ONN CTION TO lli OCK ONE 2 TRIPPING O U R N G OUT OF ST P CONDITION IF i ONE 2 I S BLOCKED uSE t L7EitNATF CONNFC110N 6 M P gto ZPI VG TMROU5H T 3 CHJ IN5 1Tt t CL0S N6 CIRCUIT POS _ r 0 1101 SC t Z O V 60 C P S sl as 6 co iO IJ 52 6 1 T J l 8 0 CCO S N J C J4 T 7 J 71M Nf6 __ _ __ _ __ _ _ t t7 9 X 3 546701 5 Fig 4 Detailed schematic of the K Dar 4 zone direc tional c omparison blocking system 7 ...

Страница 24: ... sud denly from the prefault value Z Load to the fault value represented by the line 0 F in Fig 3 When a swing or out of step condition occurs the imped ance seen by Z 0s ZP changes gradually as the voltage decreases and the current increases In Fig 3 the swing describes an arc which intersects the Z 0s circle at point Q and ZP 3 circle at point P During an out of step condition the Z 0s contact i...

Отзывы: