Notes:
(1) Any horizontal run of vent
must have a ¼ inch (6mm) rise
for every 1 foot (305mm) of
run towards the termination.
Never allow the vent to run
downward. This could cause
high temperatures and may
present the possibility of a
fire.
(2) The location of the horizontal
vent termination on an
exterior wall must meet all
local and national building
codes, and must not be easily blocked or obstructed. Termination
clearances must comply with the
V
enT
T
erminaTion
r
esTricTions
section.
Step 4
. Attach the termination to the termination stand-off
with four screws (refer to Figure 31a). Before attaching the
Vent Termination to the termination stand-off, run a bead of
non-hardening sealant around its outside edges, so as to make
a seal between it and the termination stand-off.
Step 5
. Place the termination assembly against the wall board with
the vent termination center with the cut out hole. Secure the
termination assembly to the exterior wall with eight (8) wood
screws provided (refer to Figure 31b). The arrow on the vent
cap should be pointing up. Ensure that proper clearances to
combustible materials are maintained. Attach intake heat shield
to the termination stand-off with the pre-drill holes (refer to
Figure 32).
Notes:
The eight (8) wood screws provided should be replaced with
appropriate fasteners for stucco, brick, concrete, or other types of
sidings.
i
nStallation
S
et
-u
P
Figure 30: Horizontal Venting and Cut Away.
Figure 31b: Fastening Horizontal
Termination Cap in Place.
Figure 31a: Attach Termination Stand-off
24
Figure 28:Thimble Framing
Figure 29:Thimble
Содержание DV62
Страница 6: ...Specifications Rating Label Figure 3 Rating Label SAM PLE 6 ...
Страница 13: ...13 Planning Your Installation Figure 15 Facing Trim Installation General Installation of Facing Trim ...
Страница 17: ...17 Planning Your Installation Figure 21 Allowable Vent Configurations Chart ...
Страница 49: ...49 Parts Diagram ...
Страница 50: ...Parts Diagram Options 50 ...