Leonardo Off-Grid 4kW/5000/48 MG
User manual
EN
11
4.
230V AC input on
AC IN
connection through AC plug and play connectors (RST type
if present);
5.
230V AC output on
AC OUT
connection through AC plug and play connectors (RST type);
6.
place the suitable/dedicated cable to the
temperature sensor
of the batteries as close as possible to
them to monitoring precisely the temperature.
Together with the device, is provided a cable to connect the batteries of a total length 1.5m and cable cross section
35mmq. Suggestion: install the battery pack at a total distance so to maintain the original length of the cable.
In case the battery pack is composed of further elements in series or in parallel using a cable with a minimum cable
cross section of 35mmq.
Since the device is equipped with a 1.5 m long and 35 mmq section battery connection cable, it is absolutely
recommended to install the battery bank at a distance such as to keep the original connection cable. To increase the
distance with the battery bank causes an electrical drop on the cable during operation and therefore an incorrect
reading of the battery voltage.
Use the cable supplied to connect to the main battery terminals and in the case of a battery bank made up of several
elements in series or in parallel, use a cable with a minimum section of 25mmq for wiring each element in series or in
parallel.
It is recommended to install the unit on a solid wall in a vertical position in order to ensure adequate air circulation due
to forced ventilation of the unit. For this reason, installation in dusty and dirty areas must also be avoided.
Pic.12 Wiring Cable
PV INPUT +
No. 4 positive inputs
Plug and play wiring
4-6mm^2
(In Pic. male counterparts)
AC INPUT
Wiring through plug and play
connectors 3-pin - 6 mm^2
DC input Battery
Cable Length 1.5 m
Section 35 mm^2
AC OUT
Wiring through plug and play
connectors 3-pin - 6 mm^2
PV INPUT -
No. 4 negative inputs
Plug and play wiring
4-6mm^2
(In Pic. female counterparts)
DRY CONTACT MAX SELF-
CONSUMPTION
No. 3 pins of the contact
COM-BLACK NC-WHITE NO-RED
DATA-LOGGER
BLACK PLUG
WHITE PLUG
SYNC
RESET BUTTON
Temperature Sensor
Input
Cable Length 1.5 m