5-15
Confi guration
5.3.3.2. The Boot / Sequence Delay Period.
The Boot / Sequence Delay value will be applied differently for Reboot
operations as opposed to simple On/Off operations as described below:
1.
Reboot Cycles:
a)
Single Plug:
The Boot/Seq. Delay determines how long the plug
will remain Off before it is switched back On again.
b)
Several Plugs:
The Boot/Seq. Delay determines how long the plug
will remain in the "Off" condition, and also how long the NBB will
pause before proceeding to the next plug specified.
2.
On/Off Switching:
The Boot/Seq. Delay determines how long the NBB
will pause before proceeding to the next plug specified by the
ON command.
Examples:
Assume that the Boot / Sequence Delays for each plug have been
set as follows: Plug 1 = 1 Second, Plug 2 = 2 Seconds, Plug 3 = 5 Seconds,
Plug 4 = 1 Minute, Plug 5 = 1 Second
If an "On" command is applied to the first five plugs, the NBB will respond
as follows:
1. Turn On Plug 1, Wait 1 Second.
2. Turn On Plug 2, Wait 2 Seconds
3. Turn On Plug 3, Wait 5 Seconds
4. Turn On Plug 4, Wait 1 Minute
5. Turn On Plug 5
If a "Reboot" Command is applied to Plug 3, the NBB will respond as follows:
1. Turn Off Plug 3, Wait 5 Seconds, Turn On Plug 3.
If a Reboot Command is applied to the first five plugs, the NBB will respond
as follows:
1. Turn Off the first five plugs (short delay between plugs.)
2. Wait 1 Second, Turn On Plug 1, Wait 1 Second.
3. Wait 2 Seconds, Turn On Plug 2, Wait 2 Seconds.
4. Wait 5 Seconds, Turn On Plug 3, Wait 5 Seconds.
5. Wait 1 Minute, Turn on Plug 4, Wait 1 Minute.
6. Wait 1 Second, Turn on Plug 5.
Содержание NBB-1600-D20, NBB-1600DE-D20, NBB-1600CE-D16
Страница 2: ......
Страница 12: ...2 4 NBB 1600 D20 D16 Series Network Boot Bars User s Guide...
Страница 18: ...3 6 NBB 1600 D20 D16 Series Network Boot Bars User s Guide...
Страница 22: ...4 4 NBB 1600 D20 D16 Series Network Boot Bars User s Guide...
Страница 57: ...Apx 1 A Interface Descriptions A 1 Console Port Interface Figure A 1 Console Port Interface...
Страница 63: ......
Страница 64: ...5 Sterling Irvine California 92618 949 586 9950 Toll Free 1 800 854 7226 Fax 949 583 9514 http www wti com...