5-13
Confi guration
5.3.3.2. The Boot / Sequence Delay Period.
The Boot / Sequence Delay value will be applied differently for Reboot
operations as opposed to simple On/Off operations as described below:
1.
Reboot Cycles:
a)
Single Plug:
The Boot/Seq. Delay determines how long the plug
will remain Off before it is switched back On again.
b)
Several Plugs:
The Boot/Seq. Delay determines how long the plug
will remain "Off", and also how long the IPS will pause before
proceeding to the next plug.
2.
On/Off Switching:
The Boot/Seq. Delay determines how long the IPS
will pause before proceeding to the next plug.
Examples:
Assume that a user is only allowed access to plugs one through
four, and that the Boot / Sequence Delays for each plug have been set as
follows: Plug 1 = 1 Second, Plug 2 = 2 Seconds, Plug 3 = 5 Seconds,
Plug 4 = 1 Minute.
If the user applies an "On" command to all four plugs, the IPS will respond as
follows:
1. Turn On Plug 1, Wait 1 Second.
2. Turn On Plug 2, Wait 2 Seconds.
3. Turn On Plug 3, Wait 5 Seconds.
4. Turn On Plug 4.
If a "Reboot" Command is applied to Plug 3, the IPS will respond as follows:
1. Turn Off Plug 3, Wait 5 Seconds, Turn On Plug 3.
If a Reboot Command is applied to all four plugs, the IPS will respond
as follows:
1. Turn Off all four plugs (short delay between plugs.)
2. Wait 1 Second, Turn On Plug 1, Wait 1 Second.
3. Wait 2 Seconds, Turn On Plug 2, Wait 2 Seconds.
4. Wait 5 Seconds, Turn On Plug 3, Wait 5 Seconds.
5. Wait 1 Minute, Turn on Plug 4.
Содержание IPS-800CE-D16, IPS-1600CE-D16
Страница 1: ...WTI Part No 13619 Rev A IPS 800CE D16 IPS 1600CE D16 InternetPowerSwitches User s Guide...
Страница 2: ......
Страница 18: ...4 4 IPS 800CE D16 IPS 1600CE D16 User s Guide...
Страница 51: ...Apx 1 A Interface Description A 1 Serial COM RS232 Port Interface Figure A 1 COM Port Interface...
Страница 57: ......
Страница 58: ...5 Sterling Irvine California 92618 949 586 9950 Toll Free 1 800 854 7226 Fax 949 583 9514 http www wti com...