background image

12

6049-2001

Hints

The MA-49 uses the RS-422/485 interface.
RS-422/485 was designed for multidrop applications. When a system is installed it 
should form a bus structure (see diagrams). Star shaped networks should never be 
created, there are other Westermo products designed to work in star net applications.
To correctly install, an RS-422/485 network should be terminated at the correct points. 

The recommendation is to terminate the receivers at both end of network. 
See diagrams for details of how this is done with RS-485 (2 wire) and RS-422 (4 wire).

On 4 wire systems when the MA-49 is on a slave system, it’s transmitter is linked to 
the same bus as all the other slave transmitters. A status signal (RTS or DTR) is used to
control the MA-49’s transmitter, to ensure only one slave is active on the bus at one
time. The status signal is also used to control direction for RS-485 (2 wire) transmission.

If any problems do occur on set up of the MA-49, the LED’s will be helpful.

• RTS:Indicates that the RS-422/485 transmitter is activated.

• CTS: Follows RTS.

• DCD:Simulated carrier due to the setting of S2.

• RD:Data received on the RS-422/485 interface.

• TD:Data received on the RS-232 interface.

• +12V, –12V:Indicates positive and negative power supply respectivly.

=Termination

Max 32 connections

Max 1 200 metres

Max 0.3 metre

=Termination

Max 32 connections

A
B

A

B

A

B

A

B

A’
B’
A
B

B’ A’

A’

B

B

A

B’ A’ B A

A

B’

N.B.

R+/R–, T+/T– definitations are not standard, it can help to shift A and B 
if the unit not will work.

Содержание MA-49

Страница 1: ...RS 422 485 Wandler RS 232 RS 422 485 INSTALLATIONSANVISNING INSTALLATION MANUAL INSTALLATIONS ANLEITUNG 6049 2001 www westermo se MA 49 Westermo Teleindustri AB 1999 REV A Galvanic Isolation Transient...

Страница 2: ...nsmission and transformer supply Isolation voltage 1 500 V Overvoltage protection Breakdown voltage transmitter and receiver 7 V Surge capacity 0 6 kW for 1ms Power supply External through PS 02 mount...

Страница 3: ...S2 DTR DTR DTR ON 1 2 3 4 5 6 S2 DTR DTR Always high ON 1 2 3 4 5 6 S2 Always active Always high Always high ON 1 2 3 4 5 6 S2 Always active Always high Always high ON 1 2 3 4 5 6 S2 0ms ON 1 2 3 4 5...

Страница 4: ...ut O Output MA 49 Terminal connection DCE RS 232 C V 24 25 Position D sub female Look right for a section of rack RV 01 with one MA 49 mounted Terminal connection to a 25 position D sub female connect...

Страница 5: ...and larger diameter is used Use shielded cable in heavy industrial environments Line connection 1 If shielded cable is used connect the shield only at one end to avoid ground currents Twisted pairs A...

Страница 6: ...us as all the other slave transmitters A status signal RTS or DTR is used to control the MA 49 s transmitter to ensure only one slave is active on the bus at one time The status signal is also used to...

Страница 7: ...13 6049 2001 OWN COMMENTS...

Страница 8: ...ermo se Westermo Web site www westermo se Westermo Teleindustri AB have distributors in several countries contact us for further information Westermo Data Communications Ltd Unit 14 Talisman Business...

Отзывы: