Parameter Name
Description
Default
Modbus
Address
Par.
Type
Retransmit
Choose wich parameter is retransmitted by the
analog output
12
68
Read
Write
Option
Description
Value
None
Do not retransmit value
0
Set Point
Set point
15
V Output
RMS voltage output
10
I Output
RMS current output
11
Power
Average output power
12
DEFAULT: Power
12
Parameter Name
Description
Default
Range
Unit Modbus
Address
Par.
Type
Retransmit Sale
Set the value of retransmitted
parameter to be represented by the
full scale of the analog output.
See the table below
0
0 to 9999
124
Read
Write
Retransmit
Recommended
Retransmission
Scaling
Resulting Signal
(4 to 20 mADC)
Resulting Signal
(0 to 20 mADC)
Resulting Signal
(0 to 10 VDC)
Max Value
Set Point
100
4mADC = 0%
20mADC = 100%
0mADC = 0%
20mADC = 100%
0VDC = 0%
10VDC = 100%
100.0
V Output
xV
where
x
is
the Nominal Line
Voltage
4mADC = 0V
20mADC = xV
0mADC = 0V
20mADC = xV
0VDC = 0V
10VDC = xV
999.9
I Output
xA
where
x
is
the Nominal Line
Current
4mADC = 0A
20mADC = xA
0mADC = 0A
20mADC = xA
0VDC = 0A
10VDC = xA
999.9
Power
100
4mADC = 0%
20mADC = 100%
0mADC = 0%
20mADC = 100%
0VDC = 0%
10VDC = 100%
100
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Retransmit Type
Choose type of signal for the retransmission output
1
69
Read
Write
Option
Value
0-10V
1
4-20mA
0
0-20mA
2
DEFAULT: 0-10V
1
Parameter Name
Description
Default
Modbus
Address
Par.
Type
I Limit Local /
Remote
Choose how the current limit is set
0
14,bit 4
Read
Write
Option
Description
Value
Local
Set point set via keypad or commu-
nication
0
Analog In2
Set point set via analog input
1
DEFAULT:
Local
RMS voltage output
0
www.west-cs.co.uk