12.4. Parameter list
This chapter describes the parameter on the menus accessed via the control panel and Configurator software.
To learn how to access the menus described below see “Menu navigation” chapter.
12.4.1 Operator Menu
This section describes each item on the operator menu. Use this menu to view the measured values and
basic settings of the power controller.
The password to access this menu is 0.
Parameter
Name
Description
Range Unit Modbus
Address
Par.
Type
SET POINT
View the set point
0 to 100
%
15
Read
Only
V Output
Indicates the average (RMS) voltage of all
phases
0 to 1023 V
10
Read
Only
I Output
Indicates the average (RMS) current of all
phases
0 to 1023 V
11
Read
Only
Power
Indicates the average (RMS) power output
0 to 100
%
12
Read
Only
V Input
Indicates the average (RMS) voltage input
0 to
65535
V
47
Read
Only
Frequency
Indicates frequency of the power input
0 to
655.35
Hz
9
Read
Only
Power Factor Indicates power factor of the output power
0 to 1000
102
Read
Only
Load Ω
Indicates the resistance of the load
0 to
655.35
Ω
46
Read
Only
I Limit
Indicates the maximum percent of the nomi-
nal current that the power control allows. This
parameter indicates RMS current by default.
When parameter 52 is set to 1, this parameter
indicates peak current
0 to 100
%
17
Read
Only
Out Scale
Indicates the percentage by which the power
demand set point is scaled
0 to
100.0
%
16
Read
Only
Nominal V
Indicates the user-set, nominal value for the
line voltage input
0 to 1023 V
37
Read
Only
Nominal I
Indicates the user-set, nominal load current
0 to
999.9
A
38
Read
Only