English

3 - Electrical power supply and connection terminal blocks

On the Aqu@Net system, the FCC controller is supplied directly
with 230 V / 1 phase / 50 Hz current and pilots the RCL control
under very low voltage.

It comprises 6 terminal blocks as described below :

1-

The first terminal block, known as the power supply block enables
230 V supply to be provided to the system. Each terminal is
marked on the plastic cover with L for the phase, N for neutral
and the ground symbol for ground.

2-

The second terminal block is used for connecting the fan coil
unit's constituent elements (fan, cooling mode valve, heating
mode valve, electrical resistances etc.). The terminals are
connected at the factory according to the requested application.

3-

The third terminal block marked MIU is the location set aside
for an additional communication PCB.

4-

The fourth terminal block is provided for connecting the RCL
control.

There are two connection possibilities for this component :

- The FCC is supplied with a ceiling type fan coil unit : In this

case the RCL control is supplied as a kit.

- The FCC is supplied with a low wall mounted type fan coil

unit : In this case the RCL control is mounted on a bracket on
the casing side opposite to the hydraulic connections side.

5-

The fifth terminal block comprises 3 connectors marked as
follows on the plastic cover:

WPT :

 Water temperature probe.

It is only fitted to B and D type systems. It enables mode changing
in relation to water temperature that is measured via a probe
on the pipe work. For this reason, special care must be taken
when assembling this probe.

This probe must be fitted with a 4 way valve and upstream
of the valve on the water inlet 

(refer to diagram below).

We recommend that the probe is fitted with an electrician's
type collar, using contact paste and thermal insulation on the
pipe work.

RAT :

 Intake air temperature probe.

The intake air temperature probe enables the fan coil unit to
be controlled by the air temperature reigning around the unit.
The major advantage of this system is that several units can be
controlled with a single RCL control.
This probe is connected at the factory in all cases and is installed
on the fan air intake.

ALARM :

 Condensates upper level alarm probe.

In the case of fan coil units, this connector is systematically
supplied with a shunt and it not used.
In the case of chilled water cassettes, this contact switch is
connected to the condensates tray upper level contact switch.
This switch's function is to shut down the cassette (ventilation
and valve). Its operation is visualised by a rapid flashing of the
LED on the RCL control.

6-

The sixth terminal block has 4 terminals marked in pairs on the
plastic cover as follows :

WIN :

 Window contact switch (contact switch closed = window

closed). For this reason, this contact is always supplied with a
shunt.

UNOC :

 Enables the room unoccupied / occupied function to

be activated via a dry contact switch (contact switch closed =
unoccupied mode). For this reason this contact switch is always
left free of potential.

2

1

6

5

4

3

Pipe work probe
location

FCC controller terminal blocks

Содержание Aquanet

Страница 1: ...ual Manuel d installation et de maintenance Communicating Electronic Control for Fan Coil Units R gulation lectronique communicante pour ventilo convecteurs IOM AQN W 1GBF Date April 2003 Avril 2003 S...

Страница 2: ...II...

Страница 3: ...nection to a condensate pump upper level contact switch RAT Intake air temperature red connector and red wire always wired at factory WPT Water pipe temperature white connector black wire wired at fac...

Страница 4: ...pears when the room temperature is displayed If the house is not present then the desired room temperature is being displayed TEMP These keys enable the desired temperature in the room to be raised or...

Страница 5: ...entilation function when the inlet water temperature is below 35 C and below that of the room temperature by 5 K 0 J1 J2 1 0 1 DIP switches J1 and J2 settings accessible at the rear of the control Ref...

Страница 6: ...s 2 terminals 7 and 8 marked UNOC intended to be connected to a closing contact switch for activating the unoccupied function contact switch closed function activated The aim of the unoccupied functio...

Страница 7: ...n to water temperature that is measured via a probe on the pipe work For this reason special care must be taken when assembling this probe This probe must be fitted with a 4 way valve and upstream of...

Страница 8: ...communication bus and without addressing Max number of fan coil units 15 P1 P2 P3 P4 3 3 3 3 3 Unscrew the lower screw on the RCL control 3 3 3 3 3 Separate the RCL control from its support bracket w...

Страница 9: ...read diameter 3 5 mm Head protrusion 3 5 mm STEP 2 3 3 3 3 3 Make the electrical connections between the support bracket terminals and the FCC controller and terminal 1 of the blue connector to the te...

Страница 10: ...Press the ON OFF key once again The green LED should light up Check locally that all the units change into High Speed Ventilation mode after 5 to 10 seconds The fan coil units are synchronised If this...

Страница 11: ...VF Cooling valve GMV Fan motor unit SR SR Intake air probe RED RED P1 Remote RCL Ground to the casing 0 J1 J2 1 0 1 Recommended J1 and J2 DIP switch settings on RCL control Factory wiring Client wirin...

Страница 12: ...0 J1 J2 1 0 1 Recommended J1 and J2 DIP switch settings on RCL control Aqu Net System A COOLING ONLY VENTILATION only SR Intake air probe GMV Fan motor unit Client wiring Factory wiring YELLOW GREEN R...

Страница 13: ...LY 0 J1 J2 1 0 1 Recommended J1 and J2 DIP switch settings on RCL control Aqu Net System A HEATING ONLY valve action VENTILATION water temperature probe WTP Water temperature probe SR Intake air probe...

Страница 14: ...R SUPPLY SR 0 J1 J2 1 0 1 Recommended J1 and J2 DIP switch settings on RCL control Aqu Net System B 2 PIPE REVERSIBLE valve action VENTILATION EH2 N WTP Water temperature probe SR Intake air probe GMV...

Страница 15: ...IP switch settings on RCL control Aqu Net System C 2 PIPE 2 WIRE 7 General wiring diagrams contd EH2 N Pump N F N SR Intake air probe R2 2 nd stage electrical heating resistance WTP Water temperature...

Страница 16: ...E GMV VC VF NEUTRAL BLUE VL1 N BLACK HS VIOLET MS VL2 N Pump N EH2 N EH1 N F N RED ALARM RAT WPT Remote RCL P1 4 3 2 1 Ground to the casing WHITE TERMINAL BLOCK REF 228 N NIU L Pump WIN UNOC J1 RED 23...

Страница 17: ...schreibung angegebenen Produkte den Bestimungen der nachstehend erw hnten EG Richtlinien und den nationalen Gesetzesvorschriffen entsprechen in denen diese Richtinien umgesetz sind Niederspannungsrich...

Страница 18: ...without prior notice Non contractual photos Dans un souci d am lioration constante nos produits peuvent tre modifi s sans pr avis Photos non contractuelles Wesper S A 42 cours Jean Jaur s 17800 Pons F...

Отзывы: