6 - Installation
6.1 - Unit handling
Be careful to avoid rough handling on the unit.
Do not
lift the unit by the condensate outlet or by the water
connections.
Use a lifting truck to facilitate the unit
installation.
Warning
Sharp edges and coil surfaces are a potential hazard.
Avoid contact with them.
6.2 - Installation location
1. The units are designed to be installed above the false
ceiling.
2. Install the unit in a position having sufficient strength to
carry the weight of the unit.
3. Install the unit in a position where ducts can be connected
to inlet and outlet sides of the unit.
4. Install the unit in a position from where condensate can
be run to waste easily.
5. Check the distance between the upper slab and false
ceiling to ensure the unit will suit the distance.
6. Ensure there is sufficient space around the unit to service
it (see table hereafter for minimum clearances on service
side of filters and fan-motor assembly access).
Warning
Do not install the unit in a machinery shop or kitchen
where vapour from oil or its mist flows into the unit.
6.3 - Minimum service clearances
Leave sufficient space
on the bottom and the sides
of the
unit to assure maintenance works or replacement of one or
several internal components.
Sizes
4.05
5.05
6.05
A (mm)
1600
2000
2000
B (mm)
500
500
600
C (mm)
500
500
500
C
B